background image

IM-P381-01 

 CH Issue 5

5

         Correct installation

Incorrect installation

Fig. 1 

These  product  are  designed  and  constructed  to  withstand  the  force  encountered  in      
normal use. Use of these products for any purpose other than as temperature controllers 
could cause injury or fatality to personnel.

WARNING: 

The  sensor  must  not  be  subjected  to  mercury  or  ammonium  salts.

Check that the control system supplied is of the temperature range required. It is important 
that the whole of the temperature sensing area of the sensor is fully immersed in the fluid 
being controlled, see Figure 1. 
The sensors can be held in a screwed nipple by means of a compression ring. Screw the 
nipple into the boss provided on the plant, thread the union nut and compression ring over 
the sensor. Insert the sensor fully into the nipple and tighten up the nut and compression ring. 
Do not overtighten. 
Where the sensors are used in conjunction with a pocket, either to allow easy withdrawal or 
as a protection against corrosion, the separate screwed nipple is dispensed with and the 
union nut and compression ring attached directly to the top of the pocket. Therefore insert 
the pocket in place of the screwed nipple.
When  using  a  special  long  pocket  with  the  SA122  or  SA123  sensor,  the  screwed  nipple, 
compression ring and nut are dispensed with and a rubber sealing bung provided, which is 
fitted over the capillary and slid into place to secure the sensor into the pocket. Screw the 
pocket into place, then feed the sensor bulb to the bottom of the pocket, using the rubber 
bung to seal the top.
When using a pocket it is advisable to fill the gap between the pocket and the sensor with         
a heat conducting medium such as oil, but when using a special long pocket in conjuction 
with the SA122 or SA123 sensors it should not be filled above the top of the sensor.
The  adjustment  mechanism  should  not  be  subjected  to  an  ambient  temperature  above           
50

°

C (122

°

F) or below -35

°

C (-31

°

F). The capillary tube between the sensor and the valve must 

be run and supported in such a way that it will not become damaged. Avoid all sharp bends. 
See Sections 5 and 6 'Display adjustment' and 'Commissioning'.

3. Installation

Summary of Contents for SA121

Page 1: ...ol Systems Knob Adjustment Installation and Maintenance Instructions 1 Safety information 2 Use 3 Installation 4 Pre commissioning checks 5 Display adjustment 6 Commissioning 7 Decommissioning 8 Maint...

Page 2: ...acted to confirm the suitability of the product for the application being considered ii Check material suitability pressure and temperature and their maximum and minimum values If the maximum operatin...

Page 3: ...u have suitable tools and or consumables available Use only genuine Spirax Sarco replacement parts 1 10 Protective clothing Consider whether you and or others in the vicinity require any protective cl...

Page 4: ...tions this product is recyclable and no ecological hazard is anticipated with its disposal providing due care is taken 1 16 Returning products Customers and stockists are reminded that under EC Health...

Page 5: ...inst corrosion the separate screwed nipple is dispensed with and the union nut and compression ring attached directly to the top of the pocket Therefore insert the pocket in place of the screwed nippl...

Page 6: ...occur and the warranty will be invalidated Before commissioning this unit please ensure that the system temperature cannot exceed the overtemperature protection value Table 2 Metric Self acting temper...

Page 7: ...without changing the temperature setting Reference Figure 3 opposite for the following instructions Adjust to the desired setting by turning the knob clockwise to lower the temperature and anticlockw...

Page 8: ...7 Decommissioning 8 Maintenance and spare parts There are no serviceable parts As a safety precaution if the unit is to be decommissioned it is important to reset the unit to its maximum factory sett...

Reviews: