Spirax Sarco LC2400 Installation And Maintenance Instructions Manual Download Page 11

IM-P402-84  AB Issue 6

11

The graphs can be used to check that the
calibration is correct by projecting up from the
pre-set steam calibration rise to confirm the
water level rise. Both methods of calculation
depend on an accurate assessment being made
of the rise in water level /change in set point
under full steam flow (maximum demand). This
rise in water level can vary according to
operating conditions, for example steady
maximum steam demand or intermittent,
sudden demand, and factors such as boiler

pressure and water TDS level. There will also
be a difference in level between the boiler and
the gauge glass under different firing conditions
and steam demands. Accordingly, further
adjustment to the settings may well be
necessary to achieve optimum performance. A
change in the pattern of steam demand, for
example when extra heating is needed in
winter, may also require the settings to be
adjusted.

Alternative graphical method of commissioning the steam input. (Probe with PA20 only)
Figure 6, (also shown on the controller front panel), and figure 7 offer a convenient, though less
accurate method of commissioning the steam input.

If the anticipated water level rise is:-
- less than 80 mm and the PA20 preamplifier is set to high sensitivity,
or
- less than 140 mm and the PA20 is set to medium sensitivity, then insert a range link between

terminals 4 and 5 of the LC2400 and use figure 6.

If the anticipated water level rise is:-
- greater than 80 mm and the PA20 is set to high sensitivity,
or
- greater than 140 mm and the PA20 is set to medium sensitivity, do not insert a range link and

use figure 7.

The graphs are used for a steam flowmeter with a change in output current of 16 mA (4-20 mA).
If a steam flowmeter has a fixed current output, use the following formula to scale the rise in water
level.

Scaled rise in water level (mm)  =

  Steam flow at 100% demand (kg /h)  

x

  Actual rise in

                                                       Maximum steam meter rating (kg /h)           level (mm)

To commission the LC2400 using the graphs:-
The two curves on each graph correspond to the sensitivity settings selected in the connector of
the PA20 preamplifier.

- From the set point position on the gauge glass measure the required rise in water level caused

by a steam demand.

- Note where the rise in water level meets the relevant curve on the graph.

- Read off the steam calibration setting on the bottom line of the graph.

- Set the 'steam' potentiometer to the position indicated by the graph.

The following examples demonstrate how to use the graphs:-

Example  1. If the water level is expected to rise by 60 mm when there is a 100% steam demand,
and the preamplifier sensitivity is high, then the steam calibration setting is 8. (Figure 6, link fitted).

Example 2. If the water level is expected to rise by 300 mm and the pre-amplifier is set to
medium sensitivity, then the steam calibration setting of 3.5 is obtained from the upper curve in
figure 7. The link is not fitted in this case.

7. Calibration notes

Summary of Contents for LC2400

Page 1: ...ler Installation and Maintenance Instructions IM P402 84 AB Issue 6 4025950 6 Printed in the UK Copyright 1999 1 Safety 2 Application 3 Description 4 Installation 5 Wiring 6 Commissioning 7 Calibratio...

Page 2: ...ystem uses an additional input from a water flowmeter to compensate for any variations in feedwater pressure 3 Description The Spirax Sarco LC2400 is used to connect a level controller to the4 20 mA o...

Page 3: ...the LC2400 wiring The LC2400 is powered by the current loops 4 20mA andsoneedsnoseparatepower supply Figures 1to 4 pages 4 5 6 and 7 show the wiring connections for various applications Clamping screw...

Page 4: ...ntrol relay Neutral Open Close Feedback input Feedback potentiometer 1 000 ohms Note Other actuators may have different connections Capacitance probe IN1 IN2 IN3 Connections to EL5600 series actuators...

Page 5: ...ller Fig 2 Two element level control with pneumatic valve Pneumatic valve with positioner Steam meter LC2400 Level controller LC2300 Live For range link see commissioning instructions Range link Test...

Page 6: ...o Feedback potentiometer is required Note Other actuators may have different connections Capacitance probe IN1 IN2 IN3 Connections to EL5600 Series actuators For link position and sensitivity see Prea...

Page 7: ...12 2 3 1 4 20 mA current loop 1 2 3 4 5 6 7 8 9 10 11 12 4 5 6 1 3 LC2300 Level controller LC2400 Steam meter Level probe Steam Fig 4 Three element level control with pneumatic valve Feedwater LC2300...

Page 8: ...ttom of the desired proportional band valve fully closed fully open position whichever is most convenient Adjust the LC2200 or LC2300 proportional band potentiometer until the 100 0 amber LED just lig...

Page 9: ...or a maximum flow of 12 000 kg h The output current of the meter for this size of boiler is Output current 8 000 kg h x 16 4 14 67 mA 12 000 g h Calculate the water calibration value with the followin...

Page 10: ...amplifier set to high sensitivity range link fitted Riseinwaterlevellessthan140mm PA20preamplifierset to mediumsensitivity rangelink fitted Preamplifier PA20 Medium sensitivity Preamplifier PA20 High...

Page 11: ...e LC2400 and use figure 6 If the anticipated water level rise is greater than 80 mm and the PA20 is set to high sensitivity or greater than 140 mm and the PA20 is set to medium sensitivity do not inse...

Page 12: ...nd Safety Executive Guidance Note PM5 For specific instructions for Spirax Sarco systems please see separate literature 9 Fault finding Green LED s not lit No supply from current loop present Loop con...

Reviews: