IM-P278-01-EN-ISS1
CTLS
8
4.2 To clean the strainer and replace the gasket
Isolate the valve and zero the pressure.
1
. Unscrew the unions and release pipework.
2.
Unscrew the nuts.
3.
Remove the top housing complete with the solenoid valve.
4.
Remove the screen and clean (or replace if necessary).
5.
Ensure the main valve return spring is still in position.
6.
Fit the new gasket.
7.
Replace the screen.
Assemble the top housing and tighten the nuts
to the torques shown in Table 1.
Refit the pipework and retighten the unions to
ensure a steam tight seal.
Refit the solenoid valve.
Bring the valve back into commission.
Table 1 Recommended tightening torques
Size of valve
Nut size
Tightening torques
½"
,
¾"
and
1"
DN15
,
DN20
,
DN25
and
DN32
M10
40 N m (30 lbf ft)
DN40
and
DN50
M12
45 N m (33 lbf ft)
DN80
M12
80 N m (59 lbf ft)
1
6
4
7
5
2
3