![Spirax Sarco HL 17 Installation And Maintenance Instructions Manual Download Page 13](http://html1.mh-extra.com/html/spirax-sarco/hl-17/hl-17_installation-and-maintenance-instructions-manual_1347928013.webp)
IM-P278-01-EN-ISS1
CTLS
13
30.
Thoroughly clean the lower diaphragm chamber making sure the contact faces are clean.
31.
Replace diaphragm plate and pushrod assembly and loosely fit the lower diaphragm chamber on two bolts
either side of the union connection to locate the spigot in the recess.
32.
Refit the diaphragms in exactly the same way as when dismantled.
33.
Push the lower diaphragm chamber home to locate in the recess and refit the M12 nuts and bolts.
Progressively and evenly tighten to a torque of 80 - 100 N m (59 - 74 lbf ft).
34.
Retighten the long union nut to ensure a steam tight seal.
34
33
30
31
32
31
Summary of Contents for HL 17
Page 20: ...IM P278 01 EN ISS1 CTLS 20...