![Spirax Sarco FTC62 Installation And Maintenance Instructions Manual Download Page 10](http://html1.mh-extra.com/html/spirax-sarco/ftc62/ftc62_installation-and-maintenance-instructions-manual_1347923010.webp)
IM-P179-15
CMGT Issue 3
10
start of text under grey section header box
start of text continuing from previous page
TRANSLATION RUN OVER
0
0
100
200
300
400
20
40
60
80
100
2.5 FTC62 Pressure/temperature limits
(ISO 6552)
Flanged EN 1092 PN100
Te
mp
er
atu
re
°
C
Pressure bar g
The product
must not
be used in this region or beyond the parameter of the PMA or TMA of the
relative end connection.
Body design condition
PN100
PMA
Maximum allowable pressure
100 bar g @ 50
°C
TMA
Maximum allowable temperature
400
°C @ 59.5 bar g
Minimum allowable temperature
-10
°C
PMO
Maximum operating pressure for saturated steam service
70.8 bar g @ 287
°C
TMO
Maximum operating temperature
400
°C @ 59.5 bar g
Minimum operating temperature
Note:
For lower operating temperatures consult Spirax Sarco
0
°C
Minimum operating differential pressure
0.1 bar g
PMX Maximum differential pressure
FTC62-46
46 bar
FTC62-62
62 bar
Designed for a maximum cold hydraulic test pressure of: