![Spirax Sarco DP27 Installation And Maintenance Instructions Manual Download Page 19](http://html1.mh-extra.com/html/spirax-sarco/dp27/dp27_installation-and-maintenance-instructions-manual_1347918019.webp)
IM-P470-03
CH Issue 7
19
5.2 How to renew the pilot filter element
1.
Isolate the reducing valve and zero the pressure.
2.
Unscrew the filter cap and carefully withdraw the filter element.
3.
Replace the element and tighten the filter cap to 90 - 100 N m.
Note:
The gasket is re-usable.
Filter element
Filter cap
5.3 How to renew or change the pressure adjustment spring
Isolate the reducing valve and zero the pressure in order to change the pressure adjustment
spring.
1.
Release the adjustment lock-nut.
2.
Turn the adjustment screw anticlockwise.
Ensure there is no compression on the
pressure adjustment spring.
3.
Undo the 4 off spring housing securing
nuts and remove the spring housing.
4.
Remove the pressure adjustment spring
and the top spring plate.
5.
Reassemble in reverse order.
1
2
3, 6
4