6.9 

UTILITY 

S

elect the program “

Utility

” from the menu; 

It is possible to enter the following submenu: 

Oil  setting 

–  Language  –  Technical  Service    -  Calibration  Test  –  User  Management  –  Date  Hour  - 

Measurement Unit 

– Printing Heading – PC Communication – Hose Length – System Cleaning – Op-

eration Register. 

 

Oil setting

: it adjust the charged oil quantity 

The station is set to be used with the synthetic oil RL100 (graphic bar 50% visualized), it is possible to adjust 
possible errors if it is used an oil with different viscosity. 

 

Press the left arrow to decrease the charged quantity of oil  and the right one to increase it. 

 

Language

: it is possible to select one language among the 16 ones available 

 

Technical Service

: it adusts the station parameters. The user cannot have access to it. 

 

Calibration Test

: it enables to verify the correct functioning of the scale. 

 

User Management

: it is possible to memorize up to 16 users (1-16) 

 

Select User Management 

 

Select the user 

 

Choose and save a password 

Note

: the station work also without logging in; it is possible to block the station and set it in order to make it 

work only if a password is set (contact the supplier). 
 

Date Hour

: the date and hour are displayed 

Use the arrow keys to move up/down, right and left to move, “enter” to confirm and “C” to cancel. 

 

Measurement Unit

: it is possible to select the measurement unit in Kg or pounds. 

 

Select “MEASUREMENT UNIT” and press the key “ENTER”. 

 

By using the arrow keys select the desired measurement unit. 

 

Confirm with “ENTER” 

 

Printing Heading 

(Printer version only): it is possible to personalize the printing  entering the user data 

 

Arrow Keys (right/left) to move 

 

Enter to confirm 

 

Print to change the font 

 

“C” to cancel 

 

PC Communication

: it enables to update the menu and the Database 

Note: the station is equipped with USB serial port, to communicate with the PC it is necessary to install the 
software in the provided cd. 
 

Hose length

: the standard equipment of the station includes two 3mt. hoses (High and Low Pressure), you 

can perform the automatic compensation of the hoses adjusting the set parameters. 
Use the arrow keys to change the length, “enter” to confirm and “C” to cancel. 
 

System cleaning

: the station can perform a self-cleaning of the internal circuit, this particularly indicated for 

the treatment of the gas contained in the internal bottle. 

 

Set the minutes for the cleaning of the internal circuit of the a/c stations 

 

Operation Register: 

It is possible to visualize or print out  (Printer version only) the quantity of gas that has 

been charged and the single operations performed by the different users. There are two options available:  

Gas report / Operations 
 

Gas report: 

(it displays the quantity of charged and treated gas) 

 

Choose the period you would like to visualize by using the arrow keys up/down 

 

Insert the user you would like to visualize 

 

If you choose “User 00” you will see the total amount of gas displayed

 

 

Printer key to print out the visualized data (printer version only)

 

Operations: 

(it displays the performed operations)

 

Summary of Contents for OK CLIMA

Page 1: ...DICIONADO Model Model Modell Modelo OK CLIMA ENTRY LEVEL OK CLIMA ENTRY LEVEL Printer Manufacturer Constructeur Hersteller Constructor SPIN s r l Offices Factory Bureaux et Usine B ro und Werk Oficina...

Page 2: ...SPIN s r l 02 02 2012 02 12 2 40...

Page 3: ...t CONFORME a los requisitos m nimos de seguridad y a las disposiciones de las Directivas CE 98 37 CE MACHINERY SAFETY DIRECTIVE DIRECTIVE DE S CURIT MA CHINES RICHTLINIE ZUR MASCHINEN DIRECTIVA MAQUIN...

Page 4: ...SPIN s r l 02 02 2012 02 12 4 40 5 5 6 1 6 2 7 3 8 4 9 5 11 6 12 7 18 8 20...

Page 5: ...SPIN s r l 02 02 2012 02 12 5 40 12 45 C Lep 70 A 80 A RAEE D Lgs 151 2005 2002 95 CE 2002 96 CE 2003 108 CE RAEE 30 000 00 100 000 00 2006 66 CE CR2032 Off...

Page 6: ...SPIN s r l 02 02 2012 02 12 6 40 1 1 OK CLIMA ENTRY LEVEL 1 OK CLIMA ENTRY LEVEL R134A 1 2 1 2 3 1 2 1 2 1 1...

Page 7: ...SPIN s r l 02 02 2012 02 12 7 40 2 1 250 400 70 0 1 12 5 1 10 230 50 70 2 IEC 651 IEC 804 3 550 x 520 x h 950 65 24 Printer NB Enter C Print 2 2 1 l 3 1 l 3 1 1 1 250 1 250 1 2 2 3...

Page 8: ...SPIN s r l 02 02 2012 02 12 8 40 3 0 AV68 AV68I 3 1 3 2 3 3 OK CLIMA ENTRY LEVEL R134A 3 4 16 80 4 1 1 5 PTC 3 4...

Page 9: ...SPIN s r l 02 02 2012 02 12 9 40 4 0 A B C D 7 E F G H I L USB M POLISNAP N O P Printer NB 4 1 1 1 6 0 2 6 3 3 4 17 5 6 0 5 0 5 6 4 6 150 7 0 5 6 2 8 6 0 9 ENTER 10 4 8 8 4...

Page 10: ...SPIN s r l 02 02 2012 02 12 10 40 5 6...

Page 11: ...SPIN s r l 02 02 2012 02 12 11 40 4 1 8 2 E F 3 4 5 RL 100 H 5 8 10 R134 21CR 9 G H 7 H G...

Page 12: ...SPIN s r l 02 02 2012 02 12 12 40 6 0 4 6 10 4 10 1 1 16 6 1 STOP 1500 A B C 15 0 5 2 0 7 5 13 C 20 0 5 2 5 10 16 C 25 0 5 2 5 12 18 C 30 0 5 3 12 20 6...

Page 13: ...SPIN s r l 02 02 2012 02 12 13 40 6 2 Enter C 6 3 Enter C 9 6 1 2 C 0 5 0 5 5...

Page 14: ...SPIN s r l 02 02 2012 02 12 14 40 6 4 ERR2 C 6 1 0 5 0 5 5 Enter C...

Page 15: ...SPIN s r l 02 02 2012 02 12 15 40 6 5 30 ENTER 1 1 30 ENTER Enter C ENTER ENTER ENTER Enter C 6 6 01 000 96 4 10 6 7 6 0 6 8...

Page 16: ...SPIN s r l 02 02 2012 02 12 16 40 6 9 UTILIT RL100 0 100 100 16 16 1 16 Enter C ENTER ENTER Printer Enter Print C NB USB CD 3 Enter C...

Page 17: ...SPIN s r l 02 02 2012 02 12 17 40 Enter Printer 00 Print Printer 00 Print Printer 6 10 Printer Printer Print Enter Enter C NB Print...

Page 18: ...SPIN s r l 02 02 2012 02 12 18 40 150 9 100 150 AV68I 300 B C 11 A B C 7 11 A B C AV68I...

Page 19: ...SPIN s r l 02 02 2012 02 12 19 40 100 150 2 12...

Page 20: ...SPIN s r l 02 02 2012 02 12 20 40 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 Fig 1 8...

Page 21: ...SPIN s r l 02 02 2012 02 12 21 40...

Page 22: ...page 26 Cap 4 Description of the station page 27 Cap 5 Preparation of the station page 29 Cap 6 Use of the station page 30 Recharge of the gas Pressure test A C Manual Half automatic Automatic Data b...

Page 23: ...local and national laws in force OUT OF ORDER At the end of the Machine s working life Disactivate the Machine by disconnecting it from the electric power supply and cutting the supply line cable Disa...

Page 24: ...STEMS AND THE DAMAGES INJURIES THEY CAN CAUSE THE OK CLIMA DEVICE IS CAPABLE TO PERFORM THE PHASES OF RECOVERY RECYCLING VACUUM AND RECHARGE IN A C SYSTEMS OF VEHICLES AND INDUSTRIAL VEHICLE WHICH CON...

Page 25: ...h 3 mt each Measurements of the devices 500 x 520 x h 950 mm Weight 65 Kg 24 column printer Printer version only NB the printer can be installed only when ordering the machine it is not possible to in...

Page 26: ...VE SECURITY NORMS THEY ARE PROVIDED TO ENSURE THE PROTECTION OF THE PERSONNEL WHICH USE THE SYSTEMS AND THE COOLING LIQUID FREON UNDER PRESSURE 3 3 PERFORMABLE OPERATIONS The OK CLIMA performs the fol...

Page 27: ...t Chap 6 3 ERROR 3 inactive ERROR 4 when the amount of cooling liquid contained in the internal bottle is too high 10 kg and you try to perform the recovery In this case you should perform a charge in...

Page 28: ...SPIN s r l 02 02 2012 02 12 28 40 Fig 6 Change of the printer paper Fig 5...

Page 29: ...3 Close the high and low pressure taps 4 Insert the plug into the socket and turn on the general switch M in order to switch on the station 5 Read on the display the amount of cooling liquid that is a...

Page 30: ...quantity of gas inside the bottle is less than 10kg If the quantity of gas inside the bottle is not sufficient less than 1 kg after the setting the display will show ERROR 1 and the message of insuffi...

Page 31: ...o cancel PLEASE NOTE The charging is performed simultaneously through high and low pressure if the pressure of the internal bottle is high 9 bar it is advisable to perform the charging through the hig...

Page 32: ...eeker accessories on request Press C to exit If the charge is performed regularly the display will show the quantity of charged gas To print out the data for Printer version only see the paragraph Dat...

Page 33: ...lect PROGRAM CHOICE and confirm with ENTER The number on the top on the right flashes By pressing the arrow keys or choose the number of the database corresponding to the car to be recharged The displ...

Page 34: ...nd press the key ENTER By using the arrow keys select the desired measurement unit Confirm with ENTER Printing Heading Printer version only it is possible to personalize the printing entering the user...

Page 35: ...ed operations at the end of the cycle Printing of the performed operations of the vehicle of the vehicle s plate and the Km Press the Print key Use the Enter key and the arrow keys to change the displ...

Page 36: ...ion after 150 hours of functioning of the compressor every time you switch on the station PUMP OIL Replace the pump oil every 100 150 hours of functioning or at least every 1 year even if the station...

Page 37: ...t least every 2 years even if the station is not always used Remove the rear panel from the station Unscrew the filter slowly and carefully Install the new filter according to the direction WARNINGS D...

Page 38: ...40 Number program Vehicle modell Vacuum time minutes Duration of Vacuum test minutes Amount of oil gr Amount of gas kg 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30...

Page 39: ...wer supply before working in the inside of the machine the operator may suffer injuries due to the contact with the wings of the electro fan 4 SUFFOCATION DUE TO GAS FREON If the operator does not ful...

Page 40: ...SPIN s r l 02 02 2012 02 12 40 40...

Reviews: