6.9
UTILITY
S
elect the program “
Utility
” from the menu;
It is possible to enter the following submenu:
Oil setting
– Language – Technical Service - Calibration Test – User Management – Date Hour -
Measurement Unit
– Printing Heading – PC Communication – Hose Length – System Cleaning – Op-
eration Register.
Oil setting
: it adjust the charged oil quantity
The station is set to be used with the synthetic oil RL100 (graphic bar 50% visualized), it is possible to adjust
possible errors if it is used an oil with different viscosity.
Press the left arrow to decrease the charged quantity of oil and the right one to increase it.
Language
: it is possible to select one language among the 16 ones available
Technical Service
: it adusts the station parameters. The user cannot have access to it.
Calibration Test
: it enables to verify the correct functioning of the scale.
User Management
: it is possible to memorize up to 16 users (1-16)
Select User Management
Select the user
Choose and save a password
Note
: the station work also without logging in; it is possible to block the station and set it in order to make it
work only if a password is set (contact the supplier).
Date Hour
: the date and hour are displayed
Use the arrow keys to move up/down, right and left to move, “enter” to confirm and “C” to cancel.
Measurement Unit
: it is possible to select the measurement unit in Kg or pounds.
Select “MEASUREMENT UNIT” and press the key “ENTER”.
By using the arrow keys select the desired measurement unit.
Confirm with “ENTER”
Printing Heading
(Printer version only): it is possible to personalize the printing entering the user data
Arrow Keys (right/left) to move
Enter to confirm
Print to change the font
“C” to cancel
PC Communication
: it enables to update the menu and the Database
Note: the station is equipped with USB serial port, to communicate with the PC it is necessary to install the
software in the provided cd.
Hose length
: the standard equipment of the station includes two 3mt. hoses (High and Low Pressure), you
can perform the automatic compensation of the hoses adjusting the set parameters.
Use the arrow keys to change the length, “enter” to confirm and “C” to cancel.
System cleaning
: the station can perform a self-cleaning of the internal circuit, this particularly indicated for
the treatment of the gas contained in the internal bottle.
Set the minutes for the cleaning of the internal circuit of the a/c stations
Operation Register:
It is possible to visualize or print out (Printer version only) the quantity of gas that has
been charged and the single operations performed by the different users. There are two options available:
Gas report / Operations
Gas report:
(it displays the quantity of charged and treated gas)
Choose the period you would like to visualize by using the arrow keys up/down
Insert the user you would like to visualize
If you choose “User 00” you will see the total amount of gas displayed
Printer key to print out the visualized data (printer version only)
Operations:
(it displays the performed operations)
Summary of Contents for OK CLIMA
Page 2: ...SPIN s r l 02 02 2012 02 12 2 40...
Page 4: ...SPIN s r l 02 02 2012 02 12 4 40 5 5 6 1 6 2 7 3 8 4 9 5 11 6 12 7 18 8 20...
Page 10: ...SPIN s r l 02 02 2012 02 12 10 40 5 6...
Page 11: ...SPIN s r l 02 02 2012 02 12 11 40 4 1 8 2 E F 3 4 5 RL 100 H 5 8 10 R134 21CR 9 G H 7 H G...
Page 13: ...SPIN s r l 02 02 2012 02 12 13 40 6 2 Enter C 6 3 Enter C 9 6 1 2 C 0 5 0 5 5...
Page 14: ...SPIN s r l 02 02 2012 02 12 14 40 6 4 ERR2 C 6 1 0 5 0 5 5 Enter C...
Page 18: ...SPIN s r l 02 02 2012 02 12 18 40 150 9 100 150 AV68I 300 B C 11 A B C 7 11 A B C AV68I...
Page 19: ...SPIN s r l 02 02 2012 02 12 19 40 100 150 2 12...
Page 21: ...SPIN s r l 02 02 2012 02 12 21 40...
Page 28: ...SPIN s r l 02 02 2012 02 12 28 40 Fig 6 Change of the printer paper Fig 5...