SPENCE 2000 Series Instruction Manual Download Page 4

4

2000 Series

Figure 3.

 Type 2050 Three-way Valve

Valve Body (Figure 4)

1.  Place the 2000 Series Temperature Regulator in 

the direction of the arrow cast on the valve body 

so that the heating or cooling media will flow 

through it.

2.  Place strainer and steam trap ahead of the valve 

to protect the valve from the damaging effects of 

dirt, scale, foreign material and condensate.

3. 

Place a manual shut off valve before and after 

the valve.

4. 

Place a bypass line with a manual shut off valve 

around the valve for manual operation if the 

valve is out of service. Additional recommended 

installation diagrams can be found in the Spence 

Designer’s Guide.

5.  To avoid stresses on the valve or unions, cut the 

connecting pipes to the exact length required and 

should be in correct alignment.

6.  To connect the valve, remove the union ends from 

the valve body and attach them to the nipples on 

each side of the valve.

7.  When tightening the unions to the valve always 

use two wrenches.“Never use the valve frame for 

leverage.” The valve should be installed in the 

vertical position with the thermal assembly on top.

Bulb

The location of the bulb should be chosen carefully so 

that the temperature of the media around the bulb or 

well will be representative of the entire body of fluid 

being heated or cooled.

Note

For all applications where the bulb 

is mounted in the horizontal position 

the red dot on the bulb must be facing 

upward. When large volumes of oil are 

being heated it may be necessary to 

place the bulb near the heating coils to 

avoid dangerous hot spots which would 

result if the bulb was remote for the 

heating coils.

Plain bulbs (standard for 2000 Series), without a union 

bushing, are used in open tanks, ovens, drying, rooms, 

kilns, etc. Install the bulb vertically, pointing downward 

and held securely by suitable straps and clamps. If 

the application requires that the bulb be held in a 

horizontal position, the free end of the bulb must not 

be higher than the fixed end, and the red dot on the 

bulb must be upward.

INLET

(1)

INLET

(2)

INLET

OUTLET

(3)

OUTLET

(4)

OUTLET

(5)

MIXING

DIVERTING

1. 

Cold fluid inlet opens with increase in temperature rise

2. 

Hot fluid inlet closes with increase in temperature rise

3. 

Mixed fluid

4.  Opens with increase in temperature rise

5.  Closes with increase in temperature rise

Summary of Contents for 2000 Series

Page 1: ...hall install or service the 2000 Series Temperature Regulator Introduction Scope of the Manual This instruction manual covers operation installation maintenance and troubleshooting for 2000 Series Temperature Regulator Product Description The 2000 Series is a self operated temperature regulator available with single or double seat in direct or reverse acting It is also available with two seat area...

Page 2: ...For a reverse acting valve an increase in bulb temperature opens the valve cooling 1 The pressure temperature limits in this Instruction Manual and any applicable standard or code limitation should not be exceeded SIZE NPS DN ORIFICE MAXIMUM UPSTREAM PRESSURE PSIG BAR MAXIMUM DIFFERENCE BETWEEN INLET PRESSURE PSIG BAR Single Seat Types 2010 and 2020 Double Seat Types 2030 and 2040 Three way Type 2...

Page 3: ...e the disk to close the bottom outlet of the valve and open the side outlet of the valve until temperature is balanced again For diverting service simply rotate the valve installation The diverter inlet is the outlet mixing Installation WARNING Failure of the thermal system or foreign material lodged between the valve s closure members can lead to an over temperature and or an over pressure condit...

Page 4: ...vertical position with the thermal assembly on top Bulb The location of the bulb should be chosen carefully so that the temperature of the media around the bulb or well will be representative of the entire body of fluid being heated or cooled Note For all applications where the bulb is mounted in the horizontal position the red dot on the bulb must be facing upward When large volumes of oil are be...

Page 5: ...re rise 5 Closes with increase in temperature rise INITIAL PRESSURE SPENCE SERIES 2000 TEMPERATURE REGULATOR SHUTOFF VALVE SPENCE STRAINER SHUTOFF VALVE SPENCE STRAINER SPENCE FTS STEAM TRAP CONDENSATE MAIN SPENCE STRAINER CHECK VALVE PRESSURE RELIEF VALVE CHECK VALVE HOT WATER SERVICE T P RELIEF VALVE SHUTOFF VALVE BULB STORAGE TANK TYPE 2050 INDICATING MIXING REGULATOR INLET 1 INLET 2 OUTLET 3 G...

Page 6: ...r the bulb is inserted position it so that the red dot on the bulb is upward then tighten the jam nut to secure the bulb to the well Replacement Thermal Systems The vapor pressure in some systems is too high at ordinary ambient temperatures to permit removal of the shipping block without damage to the bellows To reduce the vapor pressure within safe limits the complete system bulb line and bellows...

Page 7: ...138 167 310 337 9 122 152 145 177 317 347 10 129 158 157 183 322 353 REGULATOR SETTING RANGE C 7 2 to 46 7 2 to 63 18 to 60 18 to 77 116 to 154 116 to 171 0 1 7 10 18 21 113 116 2 14 21 27 33 121 131 3 22 31 33 42 129 138 4 27 39 39 52 135 147 5 33 46 46 58 141 153 6 38 51 51 64 146 159 7 42 57 55 70 151 165 8 46 62 59 75 154 169 9 50 67 63 81 158 175 10 54 70 69 84 161 178 Control points at these...

Page 8: ...ed preset the regulator according to Table 3 The operating range of the regulator is indicated on the nameplate The setting scale is stamped on the side of the frame and is graduated 0 to 10 representing the limits of the operating range This is an arbitrary scale since it must necessarily vary for different temperature ranges Table 4 gives the approximate temperature equivalent for all scale sett...

Page 9: ...Nut 14 Indicator Assembly 15 Adjusting Spring 16 Safety Spring Assembly 17 Guide 18 E Ring 19 Thermal System Assembly Maintenance The adjusting nut of each regulator is permanently lubricated before leaving the factory and the valve stem is equipped with a spring loaded Teflon packing gland assembly so that no maintenance should be required for the life of the regulator The valve stem is set and l...

Page 10: ...T 1 1 4 T 1 1 2 T 2 T Union End Kit Single Seat Cast iron WAL2822 WAL2822 WAL2822 WAL2822 WAL2822 WAL2822 WAL2823 WAL2826 WAL2827 WAL2828 WAL2829 Union End Kit Double Seat Cast iron WAL2824 WAL2825 WAL2826 WAL2827 WAL2828 WAL2829 Union End Kit 3 Way Cast iron WAL2830 WAL2831 WAL2832 WAL2833 WAL2834 WAL2835 Body Assembly Kit 2010 Bronze 2010AC 2010BC 2010CC 2010DC 2010EC 2010TC 2010TD 2010TE 2010TF...

Page 11: ... 11 12 13 14 15 16 17 18 19 11 2000 Series Figure 8 2000 Series Temperature Regulator Assembly THERMAL ASSEMBLY KIT SAFETY SPING KIT FRAME KIT INDICATOR KIT V PACKING KIT BONNET KIT STEM GUIDE KIT 2 SETS BODY ASSEMBLY KIT ...

Page 12: ...s are property of their prospective owners The contents of this publication are presented for informational purposes only and while every effort has been made to ensure their accuracy they are not to be construed as warranties or guarantees express or implied regarding the products or services described herein or their use or applicability All sales are governed by our terms and conditions which a...

Reviews: