CZE MANUAL
7
118030-001 REV
F
PIN
FUNCTION
1,2,3
Chassis Ground & 24Vdc Return
4
High Voltage Enable/Inhibit
5
Voltage Test Point: 10V±2% = 0 to Rated
Output
6
Output Current Test Point: 10V±2% = 0 to
Rated Output
7
Chassis Ground
8
Remote Voltage Control
9
Remote Current Control
10
+10.24Vdc Reference
11
Test Point and Remote Programming Return
12
Polarity Control Signal
13
Positive Polarity Indicator
14, 15
+24Vdc Input
16
Chassis Ground
17
Negative Polarity Indicator
18
I – Mode Indicator
19
V- Mode Indicator
20
Current Return Test Point
21
Load Return
22
Ground Fault Indication
23,24,25
Spares
Note: If Enable/Inhibit is not used, connect Pin 4 to Pin
10.
Remote Programming:
Permits remote adjustment of the output voltage and
current via an external voltage source. By adjusting the
voltage source from 0V to 10V the desired output may be
selected.
Remote Monitor:
Test points, pins 5 and 6 of the input connector, monitor
voltage and current outputs. The output polarity is
positive from 0V to 10V equal to 0 to 100% of the output
±0.5%. Output impedance is 10k Ohms.
High Voltage Enable/Inhibit:
The external TTL signal allows the user to inhibit the
power supply output without switching the HIGH
VOLTAGE OFF.
Summary of Contents for CZE Series
Page 14: ...CZE MANUAL 6 118030 001 REV F Figure 2 1 CZE1000 Dimensions Connector Interface ...
Page 16: ...CZE MANUAL 5 118030 001 REV F Figure 2 2 CZE2000 Dimensions Connector Interface ...
Page 23: ...CZE MANUAL 13 118030 001 REV F Figure 3 5 CZE HV ON OFF Control ...
Page 29: ...CZE MANUAL 19 118030 001 REV F Figure 5 1 Floating Ground Interface Circuit ...