5 | Installation
Spectron Gas Control Systems GmbH
18
GES_FS4_0520
C1 and relay outputs 1 to 8 are used by the controller and must not be otherwise assigned. C1
is disconnected from the network as soon as an emergency stop or remote shutdown signal is
active.
The wiring of terminals C2 and the associated relay outputs 9 to 16 are provided for the follow-
ing functions:
– C2: 24V power supply for relay outputs 9 to 16
– 9: free
– 10: External horn (NO)
– 11: Emergency shutdown (NC)
– 12: Warning signal (NC)
– 13: Status valve 1 (NO)
– 14: Status valve 2 (NO)
– 15: Status valve 3 (NO)
– 16: Status valve 4 (NO)
5.3 Pneumatic connection
DANGER
Intended use
Operation of the product with gases other than those specified or outside the limits may result in
dangerous reactions in the system. Incorrect use poses considerable risks to operating person-
nel and the environment!
a) Only use the product for gases for which it was designed.
b) Only use the product in the specified limit values for pressure and withdrawal quantity.
c) Usage for another type of gas or outside the limit values is prohibited and constitutes mis-
use.
WARNING
Noise emission
When working on pressurised pneumatic supply, significant noise emission can occur. Acute
and chronic loss of hearing may result.
a) Never perform work on the pressurised pneumatic supply without hearing protection.
b) Only replace the silencers when the supply is unpressurised.
WARNING
Displacement of atmospheric oxygen
In the event of inert gas leaks, displacement of atmospheric oxygen may occur. Danger of suf-
focation!
a) The operator must ensure adequate ventilation and airing in all rooms with gas installations
and monitor the oxygen content.