background image

 

General Instructions for Electrical Wiring

 

65 

B

 

Wiring Instructions 

 

In this appendix… 

General Instructions for Electrical Wiring 

page 65 

Typical Wiring Configurations 

page 67 

B.1

 

General Instructions for Electrical Wiring 

Follow the instructions detailed in this section for determining the correct 
wire gauge to be used for the installation. 

1

 

Use Table 25 to determine the required wire gauge/size for general 
wiring, such as relay wiring. Calculate the permitted voltage drop with 
respect to load current, wire gauge, and length of wires. 

Table 25: Maximum DC Resistance at 68°F/20ºC for Copper Wire 

AWG # 

mm

2

 

Ohm per 100ft 

Ohm per 100m 

26 

0.12

0.15 

4.32 

14.15 

24 

0.16

0.24 

3.42 

11.22 

22 

0.30

0.38 

1.71 

5.60 

20 

0.51

0.61 

1.07 

3.50 

18 

0.81

0.96 

0.67 

2.20 

16 

1.22

1.43 

0.43 

1.40 

14 

1.94

2.28 

0.27 

0.88 

12 

3.09

3.40 

0.17 

0.55 

10 

4.56

6.64 

0.11 

0.35 

2

 

Use Table 26 to select wire gauge for power supply wires. DO NOT 

connect any circuit or load to detectors’ supply inputs.

 

 

Select 

Number of detectors

 connected in 1 circuit. 

 

Select wiring 

Length

 per your installation requirements. 

 

Refer to 

Power Supply Range

 for voltage extreme applied. 

www.acornfiresecurity.com

www.acornfiresecurity.com

Summary of Contents for SharpEye 40/40I

Page 1: ...me Detector User Guide FM CSA Approved Class I Div 1 Groups B C D Class II III Div 1 Groups E F G ATEX IECEx Approved Ex II 2G D Ex db eb op is IIC T4 Gb Ex tb op is IIIC T96 C Db www acornfiresecurity com www acornfiresecurity com ...

Page 2: ...www acornfiresecurity com www acornfiresecurity com ...

Page 3: ...ponsibility for using maintaining or servicing the product The detector is not field repairable due to the meticulous alignment and calibration of the sensors and the respective circuits Do not attempt to modify or repair the internal circuits or change their settings as this will impair the system s performance and void the SPECTREX product warranty Warranty SPECTREX agrees to extend to Purchaser...

Page 4: ...ruary 2013 Sixth Release Ian Buchanan Eric Zinn 6 July 2013 Seventh Release Ian Buchanan Eric Zinn 7 February 2015 Eighth Release Ian Buchanan Eric Zinn 8 June 2015 Ninth Release Ian Buchanan Eric Zinn 9 August 2015 Tenth Release Ian Buchanan Eric Zinn 10 January 2016 Eleventh Release Ian Buchanan Eric Zinn 11 July 2016 Twelfth Release Ian Buchanan Eric Zinn 12 October 2016 Thirteenth Release Jay ...

Page 5: ...t Certification 19 1 5 Performance Considerations 21 1 5 1 Detection Sensitivity 21 1 5 2 Cone of Vision 23 1 5 3 False Alarm Prevention 24 1 5 4 Visual Indicators 25 1 5 5 Output Signals 26 1 5 6 Detector Status 27 1 5 7 Auxiliary Relay as End of Line 28 1 6 Internal Detector Tests 28 1 6 1 Continuous Feature Test 28 1 6 2 Built In Test BIT 29 2 Installing the Detector 33 2 1 General Guidelines 3...

Page 6: ... 3 Operating the Detector 47 3 1 Powering Up 47 3 2 Safety Precautions 48 3 2 1 Default Functions Settings 48 3 3 Testing Procedures 49 3 3 1 Automatic BIT Test 49 3 3 2 Manual BIT Test 49 3 3 3 Testing with Flame Simulator Model FS 1100 49 4 Maintenance and Troubleshooting 51 4 1 Maintenance 51 4 1 1 General Procedures 51 4 1 2 Periodic Procedures 52 4 1 3 Keeping Maintenance Records 52 4 2 Troub...

Page 7: ... 1 1 Ordering Information 74 D 1 2 Unpacking 74 D 1 3 Operating Instructions 74 D 1 4 Range 75 D 1 5 Charging the Battery 75 D 1 6 Battery Replacement 76 D 1 7 Technical Specifications 77 D 2 Tilt Mount 78 D 3 Duct Mount 79 D 4 Weather Cover 80 D 5 Cone Viewer 81 D 6 Air Shield 82 E SIL 2 Features 83 E 1 40 40I Flame Detector 83 E 1 1 Safety Relevant Parameters 83 E 1 2 Guidelines for Configuring ...

Page 8: ... 4 Wire Controllers Using Option 1 or 2 Wiring 68 Figure 10 0 20mA Wiring Option 1 Sink 4 Wire Default 69 Figure 11 0 20mA Wiring Option 1 Converted to Source 3 Wire 69 Figure 12 0 20mA Wiring Option 1 Non isolated Sink 3 Wire 70 Figure 13 0 20mA Wiring Options 2 and 3 Source 3 Wire available with the HART Protocol 70 Figure 14 RS 485 Networking 71 Figure 15 Flame Simulator FS 1100 73 Figure 16 Fl...

Page 9: ...31 Table 13 Results of an Unsuccessful Manual BIT 31 Table 14 Tools 35 Table 15 Model 40 40I Wiring Options 42 Table 16 Sensitivity Settings 44 Table 17 Functions 45 Table 18 Default Function Values 48 Table 19 Results of Successful Flame Simulator Test 50 Table 20 Troubleshooting Table 53 Table 21 Electrical Specifications 58 Table 22 Contact Ratings 59 Table 23 20mA Current Output 60 Table 24 El...

Page 10: ...power up and test the detector The chapter also lists safety precautions you should take when operating the detector Chapter 4 Maintenance and Troubleshooting describes basic maintenance troubleshooting and support procedures Appendix A Technical Specifications lists the detectors technical and other specifications Appendix B Wiring Instructions lists the wiring instructions for connecting the det...

Page 11: ...l Electrotechnical Commission Explosion IPA Isopropyl Alcohol IR Infrared JP5 Jet Fuel Latched Refers to relays remaining in the On state even after the On condition has been removed LED Light Emitting Diode LPG Liquefied Petroleum Gas mA Milliamps 0 001 amps MODBUS Master slave messaging structure N C Normally Closed N O Normally Open N A Not Applicable NFPA National Fire Protection Association N...

Page 12: ...www acornfiresecurity com www acornfiresecurity com ...

Page 13: ... for improved performance in ice snow and condensation conditions Detection performance can be easily adapted to all environments applications and requirements by changing the detector s configuration parameters Adjusting these parameters as well as performing other maintenance and monitoring tasks is possible by means of RS 485 based Modbus communication or HART communication in models with 0 20m...

Page 14: ...s The 40 40I Flame Detector is provided in various configurations depending on Wiring options Temperature ranges Type of cable entries Housing material type Required approval The configuration detail is included in the product part number on the product label and takes the form 40 40I XXXXX where XXXXX defines the model according to the above requirements To modify the default or pre ordered confi...

Page 15: ...TM 40 40I Rev 14 February 2017 Model and Types 15 The Part Numbers are defined as Note Aluminum housing is not available in the FM version www acornfiresecurity com www acornfiresecurity com ...

Page 16: ...S 485 5 Power Manual BIT Fault Relay N O Alarm Relay N O Auxiliary N O RS 485 Note Wiring option 1 is the default The mA Sink output can be altered to Source type with a link between terminals 1 and 8 No other wiring options can be changed onsite For example product number 40 40I 321SC has the following options Wiring Option 3 Power Manual BIT RS 485 0 20mA Source with the HART protocol Fault Rela...

Page 17: ...s effects of ice snow and condensation Electrical Interface Dry contact relays Communication network RS 485 0 20mA output HART Protocol Communication protocol see HART Protocol on page 18 Exde Integral junction box for easy wiring SIL 2 TÜV approved Hazardous Area Certification ATEX IECEx FM CSA Functionality Approval EN54 10 approved by VdS FM approved per FM3260 Accessories are approved as part ...

Page 18: ...rces The SharpEye 40 40I also includes an additional IR sensor sensitive to a different band within the emission peak of hot CO2 This sensor s signal is compared to those of the other 3 thereby increasing sensitivity for some types of flames such as gas flames 1 4 2 Heated Optics The SharpEye 40 40 Flame Detector uses heated optics The heater increases the temperature of the optical surface by 5 8...

Page 19: ...c tools 1 4 5 Product Certification The 40 40I Flame Detectors have the following certifications ATEX IECEx page 19 FM CSA page 20 SIL 2 page 20 EN54 10 page 20 Inmetro UL page 20 TR CU EAC page 8 1 4 5 1 ATEX IECEx The 40 40I Flame Detector is certified to ATEX per SIRA 07ATEX1250X and IECEx per IECEx SIR 07 0085X Ex II 2G D Ex db eb op is IIC T4 Gb Ex tb op is IIIC T96 C Db 55 C Ta 75 C or Ex II...

Page 20: ... can be implemented by Alert signal via 0 20mA current loop or Alert signal via alarm relay and fault relay For more details and guidelines for configuring installing operating and service see SIL 2 Features on page 83 and TÜV Report No 968 EZ 348 04 16 1 4 5 4 EN54 10 The 40 40I Flame Detector is certified to EN54 10 and CPD The detector has been tested and approved per EN54 10 by VdS This test i...

Page 21: ...ention page 24 Visual Indicators page 25 Output Signals page 26 Detector Status page 27 Auxiliary Relay as End of Line page 28 1 5 1 Detection Sensitivity Detection sensitivity is the maximum distance at which the detector reliably detects a specific size of fire and typical type of fuel standard fire 1 5 1 1 Standard Fire Defined as a 1ft2 0 1m2 n heptane pan fire with maximum wind speed of 6 5ft...

Page 22: ...ty conditions etc 1 5 1 3 Other Fuels The detector reacts to other types of fire as follows The baseline fire refers to n heptane 1ft2 0 1m2 and is defined as 100 sensitivity For fuel fire standard pan fire size 1ft2 0 1m2 For gas flame 30 0 75m high 10 0 25m width plume fire Maximum Response Time 10 sec Table 3 Fuel Sensitivity Ranges Type of Fuel Percent of Max Distance at Each Sensitivity Range...

Page 23: ...ebruary 2017 Performance Considerations 23 1 5 2 Cone of Vision Horizontal 100 Figure 1 Horizontal Field of View Vertical 50 down 45 up Figure 2 Vertical Field of View www acornfiresecurity com www acornfiresecurity com ...

Page 24: ...alternating current 60Hz IAD Arc welding 6mm 5 16 rod 210A See Table 5 Ambient light extremes darkness to bright light with snow water rain desert glare and fog IAD Bright colored clothing including red and safety orange IAD Electronic flash 180 watt seconds minimum output IAD Movie light 625W quartz DWY lamp Sylvania S G 55 or equivalent 6 5 2 Blue green dome light conforming to M251073 1 IAD Fla...

Page 25: ...5 7 5 1 5 4 Visual Indicators One 3 color LED indicator is located inside the detector window as shown in Figure 3 The detector statuses are listed in Table 6 Table 6 LED Indications Detector Status LED color LED mode Fault BIT Fault Yellow 4Hz flashing Normal Green 1Hz flashing Warning Red 2Hz flashing Alarm Red Steady Figure 3 Indicator LED Indicator LED www acornfiresecurity com www acornfirese...

Page 26: ...ut Types Output Type Version Detector Status Alarm Relay 40 40I Options 1XXXX 4XXXX and 5XXXX The relay is N O 40 40I Options 2XXXX and 3XXXX The relay is N O and N C Auxiliary Relay 40 40I Options 4XXXX and 5XXXX The relay is N O Fault Relay 40 40I Options 1XXXX 2XXXX and 4XXXX The relay is N C energized 40 40I Options 3XXXX and 5XXXX The relay is N O energized 0 20mA Current Output 40 40I Option...

Page 27: ...e to a software fault or due to an electrical failure The detector will NOT detect fire in this condition In each state the detector activates different outputs as specified in Table 9 Table 9 Output Signals Versus Detector State Detector State LED Indicator LED Mode Alarm Relay Auxiliary Relay Fault Relay mA output Normal Green 1Hz Off Off On 4mA Warning Red 2Hz Off On 4 On 16mA Alarm 1 Red Const...

Page 28: ...mmable function auxiliary relay is set to YES Notes The auxiliary relay is available only in Models with suffix 4XXXX and 5XXXX The 0 20mA is available only in Models with suffix 1XXXX 2XXXX and 3XXXX 1 5 7 Auxiliary Relay as End of Line The auxiliary relay can be used as End of Line in models with suffix 4XXXX and 5XXXX only In this case the auxiliary relay is active as long as the detector is po...

Page 29: ...ed 1 6 2 Built In Test BIT The detector s Built In Test BIT also checks the following Electronic circuitry Sensors Window cleanliness The detector can be set to perform the BIT in the following modes Automatically and manually Manually only Note In Manual BIT the outputs may also be tested and Control System inhibit should be applied if this could initiate other systems 1 6 2 1 How the BIT Operate...

Page 30: ...s normal operation Table 10 Results of a Successful BIT Output Result Fault Relay Model 1XXX 2XXX and 4XXX wiring options 1 2 and 4 remains Closed Model 3XXX and 5XXX wiring options 3 and 5 remains Open 0 20mA Output Wiring options 1 2 and 3 Normal 4mA Power LED Green Flashing 1Hz On Normal Table 11 Results of an Unsuccessful BIT Output Result Fault Relay Wiring options 1 2 and 4 changes to Open W...

Page 31: ... is activated for 3 sec only when the function auxiliary BIT is set to Yes 0 20mA Output Wiring options 1 2 and 3 Initiates 20mA only when the function alarm BIT is set to Yes Initiates 16mA when the function auxiliary BIT is set to Yes and the function alarm BIT is set to No Power LED Green Flashing 1Hz Table 13 Results of an Unsuccessful Manual BIT Output Result Fault Relay Wiring options 1 2 an...

Page 32: ...www acornfiresecurity com www acornfiresecurity com ...

Page 33: ... an efficient installation consider the following guidelines Sensitivity To determine the level of sensitivity consider the following Size of fire at the required distance to be detected Type of flammable materials Wiring The wire gauge must be designed according to the distance from the detector to the controller and the number of detectors on the same power line See Wiring Instructions on page 6...

Page 34: ... flame detectors and installation of Ex approved products 2 2 Unpacking the Product Upon receipt of your detector verify that you have received the following contents Delivery form Flame detector Plastic weather cover User manual Quality document Tool keys per shipment Check and record the following 1 Verify the appropriate Purchase Order 2 Record the Part Number P N and Serial Number of the detec...

Page 35: ...m wires may be used for site wiring The selection of wire gauge should be based on the number of detectors used on the same line and the distance from the control unit in compliance with specifications see General Instructions for Electrical Wiring on page 65 2 4 Certification Instructions Warning Do not open the detector even when isolated in the presence of any open flame 2 4 1 Special Instructi...

Page 36: ...ing or cooling any part of the equipment enclosure to a temperature outside the marked maximum ambient temperature range prior to switching the equipment on when taking into account surrounding ambient temperature 2 4 2 General Instructions The cable entry point may exceed 167 F 75 C Suitable precautions should be taken when selecting the cable The equipment may be used with flammable gases and va...

Page 37: ...ement see Electromagnetic Compatibility EMC on page 63 Ground the detector to the nearest ground point not more than 3m from the detector location Install the detector with the cable entries placed downwards 2 5 1 Conduit Installation The conduit used for the cabling must comply with the following To avoid water condensation or water in the detector install the detector with the conduits placed do...

Page 38: ...ount 2 6 Installing the Tilt Mount The tilt mount P N 40 40 001 enables the detector to be rotated up to 60º in all directions Figure 4 shows the detector mounted on the tilt mount Figure 4 Detector with Tilt Mount www acornfiresecurity com www acornfiresecurity com ...

Page 39: ...gure 5 Tilt Mount Assembly Figure 6 shows the tilt mount assembly with dimensions in both millimeters and inches Figure 6 Tilt Mount Assembly dimensions in millimeters and inches TiltMount TiltHolding Plate Horizontal Locking Screw VerticalLocking Screw Detector Holding Plate www acornfiresecurity com www acornfiresecurity com ...

Page 40: ...the protected area and make certain that the view of the area is unobstructed Secure the detector in that position by tightening the locking screws on the tilt mount making sure the detector is in the correct position The detector is now correctly located aligned and ready to be connected to the system 2 7 Connecting the Detector This section describes how to connect the electric cabling to the de...

Page 41: ...mechanical connection and press them neatly against the terminal to prevent them from interfering while closing the back cover Figure 7 9 Place and secure the detector s back cover by screwing the 3 socket head screws in the cover bolts Figure 4 2 7 1 Verifying the Detector Wiring The detector has 5 output wiring options within the Exde integral terminal section of the enclosure There are 12 termi...

Page 42: ...larm Relay C Alarm Relay C Alarm Relay C 8 0 20mA In Alarm Relay N C Alarm Relay N C Auxiliary N O Auxiliary N O 9 0 20mA Out 0 20mA Out 0 20mA Out Auxiliary C Auxiliary C 10 RS 485 1 RS 485 1 RS 485 1 RS 485 1 RS 485 1 11 RS 485 1 RS 485 1 RS 485 1 RS 485 1 RS 485 1 12 RS 485 GND RS 485 GND RS 485 GND RS 485 GND RS 485 GND Available with the HART protocol Notes RS 485 is used for the communicatio...

Page 43: ...gnostics on all 40 40 series flame detectors Refer to manual TM777070 for programming instructions when using the Mini Laptop Kit USB RS 485 Harness Kit P N 794079 The USB RS 485 Harness Kit with RS 485 USB converter used with the SPECTREX host software enables you to connect to any available PC or laptop to re configure settings or perform diagnostics on all 40 40 series flame detectors Refer to ...

Page 44: ... may be present The time delay for fire alarms in this mode ranges from 2 5 15 seconds and is usually less than 10 seconds Other delay settings are available 0 3 5 10 15 20 or 30 seconds When an alarm detection level condition occurs the detector delays the execution of the alarm outputs by the specified period of time The detector then evaluates the condition for 3 seconds If the alarm level is s...

Page 45: ...xiliary BIT Yes Successful Manual BIT activates the Auxiliary Relay for approximately 3 seconds default No Successful Manual BIT does not activate the Auxiliary Relay EOL Yes Auxiliary Relay is used as End of Line No Auxiliary Relay operates in accordance with Functions 2 and 5 default Note Only available in Models 40 40I 4XXXX and 5XXXX 2 8 5 Heated Optics The heated optics can be defined as one ...

Page 46: ...www acornfiresecurity com www acornfiresecurity com ...

Page 47: ... detector 1 Turn on the power 2 Wait up to 60 seconds for the detector to finish the start up procedure Applying power initiates the following sequence of events The yellow LED flashes at 4Hz BIT is executed If successful the green LED flashes at 1Hz the fault relay contacts close and mA output is 4mA 3 Enter Normal mode Note The majority of detectors are used in the default non latched alarm mode...

Page 48: ...ess RS 485 terminals for maintenance External devices such as automatic extinguishing systems must be disconnected or disabled before carrying out any maintenance 3 2 1 Default Functions Settings Table 18 lists the default function configuration supplied with the detector Table 18 Default Function Values Function Value Notes Sensitivity 30 Alarm Delay A Antiflare Alarm Latch No Auxiliary Relay No ...

Page 49: ... with Flame Simulator Model FS 1100 page 49 3 3 1 Automatic BIT Test Check that the indicators show normal conditions See Powering Up on page 47 3 3 2 Manual BIT Test Important If the function setup alarm BIT and or auxiliary BIT are set to Yes default is No the alarm auxiliary relay and 0 20mA outputs are activated during a Manual BIT Therefore automatic extinguishing systems or any external devi...

Page 50: ...r Model FS 1100 at the target point of the detector Figure 14 such that the radiation emitted by it is facing directly towards the detector See Flame Simulator FS 1100 on page 73 3 Press the operation button once After few seconds a successful test shows the results listed in Table 19 Table 19 Results of Successful Flame Simulator Test Component Action Notes 0 20mA Turn to 20mA For a few seconds a...

Page 51: ...ral Procedures Maintenance should be performed by suitably qualified personnel who are familiar with local codes and practice Maintenance requires ordinary tools 4 1 1 1 Cleaning The detector must be kept as clean as possible Clean the viewing window and the reflector of the flame detector periodically The frequency of cleaning operations depends upon the local environmental conditions and specifi...

Page 52: ... described in Powering Up on page 47 4 1 2 2 Functional Test Procedure Perform a functional test of the detector as described in Internal Detector Tests on page 28 4 1 3 Keeping Maintenance Records Maintenance operations performed on a detector should be recorded in a log book The record should include the following Installation date Contractor Serial and tag number Entries for every maintenance o...

Page 53: ... flashes at 4Hz Fault Relay at N O 0 20mA at 0mA Fault Detector Low Voltage Faulty Detector Check the voltage at the detector verify at least 24V at the detector terminal Send the detector back for repairs Yellow LED flashes at 4Hz Fault Relay at N O 0 20mA at 2mA BIT Fault Faulty Detector Clean detector window Re power the detector Replace the detector Red LED constantly on If no fire exists then...

Page 54: ...www acornfiresecurity com www acornfiresecurity com ...

Page 55: ...Appendix 55 Appendix www acornfiresecurity com www acornfiresecurity com ...

Page 56: ...www acornfiresecurity com www acornfiresecurity com ...

Page 57: ... fire Fuel ft m Fuel ft m n Heptane 215 65 Kerosene 150 45 Gasoline 215 65 Ethanol 95 135 40 Diesel Fuel 150 45 Methanol 115 35 JP5 150 45 IPA Isopropyl Alcohol 135 40 Methane 150 45 Polypropylene Pellets 115 35 LPG 150 45 Office Paper 83 25 30 0 75m high 10 0 25m width plume fire Response Time Typically 5 seconds Adjustable Time Delay Up to 30 seconds Sensitivity Ranges Four sensitive ranges for ...

Page 58: ... Normal 70mA 65mA Normal when Heater On 95mA 90mA Alarm 110mA 95mA Alarm when Heater On 135mA 120mA Power Consumption Max 18 32VDC Normal 1 95W 1 85W Normal when Heater On 2 56W 2 45W Alarm 3 04W 2 56W Alarm when Heater On 3 68W 3 2W Maximum Current Max 18 32VDC Normal 90mA 85mA Normal when Heater On 105mA 100mA Alarm 130mA 115mA Alarm when Heater On 160mA 145mA Electrical Input Protection The inp...

Page 59: ...elay N O Alarm Relay N O Option 5 Power RS 485 Fault Relay N O Auxiliary Relay N O Alarm Relay N O Electrical Outputs Dry Contact Relays Table 22 Contact Ratings Relay Name Type Normal Position Maximum Rating Alarm SPDT N O N C 2A at 30VDC Auxiliary SPST N O 2A at 30VDC Fault see Notes 1 and 2 SPST N C or N O 2A at 30VDC Notes 1 The fault relay in wiring options 1 2 and 4 is normally energized clo...

Page 60: ...that can be used in installations with computerized controllers The communications protocol is Modbus compatible This protocol is a standard and widely used It enables continuous communication between a standard Modbus controller Master device and a serial Network of up to 247 detectors Heated Optics The front window can be heated to improve performance in ice condensation and snow conditions The ...

Page 61: ...X 55 C Ta 75 C or 1Ex d e IIC T4 Gb X Ex tb IIIC T106 C Db X 55 C Ta 85 C Functional Approvals EN54 10 approved by VdS FM approved per FM3260 A 5 Mechanical Specifications Enclosure Stainless Steel 316 or Aluminum heavy duty copper free less than 1 red epoxy enamel finish Water and Dust Tight NEMA 250 type 6p IP 66 and IP 67 per EN 60529 Electronic Modules Conformal coated Electrical Connection 2 ...

Page 62: ...ity of up to 95 for the operational temperature range Salt Fog Designed to meet MIL STD 810C method 509 1 procedure I Exposure to a 5 Salt Solution Fog for 48 hours Dust Designed to meet MIL STD 810C method 510 1 procedure I Exposure to a dust concentration of 0 3 grams cubic ft at a velocity of 1750fpm for 12 hours Vibration Designed to meet MIL STD 810C method 514 2 procedure VIII Vibration at a...

Page 63: ...cted Disturbances IEC 61000 4 6 IEC 61326 3 Power Frequency Magnetic Field IEC 61000 4 8 IEC 61326 3 Radiated Emission IEC 61000 6 3 EN 55022 Conducted Emission IEC 61000 6 3 EN 55022 Immunity to Main Supply Voltage Variations MIL STD 1275B To fully comply with EMC directive 2014 30 EU and protect against interference caused by RFI and EMI the cable to the detector must be shielded and the detecto...

Page 64: ...www acornfiresecurity com www acornfiresecurity com ...

Page 65: ...t to load current wire gauge and length of wires Table 25 Maximum DC Resistance at 68 F 20ºC for Copper Wire AWG mm2 Ohm per 100ft Ohm per 100m 26 0 12 0 15 4 32 14 15 24 0 16 0 24 3 42 11 22 22 0 30 0 38 1 71 5 60 20 0 51 0 61 1 07 3 50 18 0 81 0 96 0 67 2 20 16 1 22 1 43 0 43 1 40 14 1 94 2 28 0 27 0 88 12 3 09 3 40 0 17 0 55 10 4 56 6 64 0 11 0 35 2 Use Table 26 to select wire gauge for power s...

Page 66: ... and the detector considering the number of detectors on the same power line where L Actual wire length between the detector and the power supply N Number of detectors per loop R Resistance of wire per 100m see Table 26 V Voltage drop on the wire Calculate the voltage drop on the wire as follows V 2L x R x N x 0 2A 100 20 V Minimum required voltage of the power supply 0 2A is the maximum power con...

Page 67: ...bruary 2017 Typical Wiring Configurations 67 B 2 Typical Wiring Configurations This section describes examples of typical wiring configurations Figure 8 Wiring Terminals www acornfiresecurity com www acornfiresecurity com ...

Page 68: ...0mA Sink 2 40 40I 2XXXX Fault Relay N C Alarm Relay N C 0 20mA Source 3 40 40I 3XXXX Fault Relay N O Alarm Relay N C 0 20mA Source 4 40 40I 4XXXX Fault Relay N C Auxiliary Relay N O Auxiliary Relay C 5 40 40I 5XXXX Fault Relay N O Auxiliary Relay N O Auxiliary Relay C Figure 9 Typical Wiring for 4 Wire Controllers Using Option 1 or 2 Wiring www acornfiresecurity com www acornfiresecurity com ...

Page 69: ... 14 February 2017 Typical Wiring Configurations 69 Figure 10 0 20mA Wiring Option 1 Sink 4 Wire Default Figure 11 0 20mA Wiring Option 1 Converted to Source 3 Wire www acornfiresecurity com www acornfiresecurity com ...

Page 70: ...gurations Figure 12 0 20mA Wiring Option 1 Non isolated Sink 3 Wire Figure 13 0 20mA Wiring Options 2 and 3 Source 3 Wire available with the HART Protocol Note There are no 0 20mA outputs in wiring options 4 and 5 www acornfiresecurity com www acornfiresecurity com ...

Page 71: ...ssable system with 4 wires only 2 for power and 2 for communication Using repeaters the number of detectors can be much larger 32 detectors for each repeater up to 247 on the same 4 wires When using the RS 485 network it is possible to read each detector status FAULT WARNING and ALARM and to initiate a BIT for each detector individually For more details contact SPECTREX Figure 14 RS 485 Networking...

Page 72: ...www acornfiresecurity com www acornfiresecurity com ...

Page 73: ...e SharpEye IR3 Flame Detector D 1 Flame Simulator FS 1100 The Flame Simulator FS 1100 is designed specifically for use with SharpEye Flame Detectors The Flame Simulator emits IR radiation in a unique sequential pattern corresponding to and recognizable by the detector as fire which allows the detectors to be tested under simulated fire conditions without the associated risks of an open flame Figur...

Page 74: ...ason in a hazardous area Caution The following test simulates a real fire condition and may activate the extinguishing system or other alarms If activation is not desired disconnect inhibit them before the test and reconnect after the simulation To simulate a fire 1 Verify you are at the correct distance from the detector according to the type of detector and the detector sensitivity 2 Using the m...

Page 75: ...in the range Important Keep the flame simulator in a safe place when not in use D 1 5 Charging the Battery The flame simulator uses lithium ion batteries as a rechargeable power source When the batteries are fully charged the simulator operates at least 1 000 times without having to be recharged The simulator will not operate when the voltage from the batteries is lower than the required operation...

Page 76: ...he charger turns on 8 Disconnect the charger 9 Insert the battery into the flame simulator 10 Screw on the locking disc Item 3 11 Screw on the back cover Item 4 12 Lock the back cover with the locking screw D 1 6 Battery Replacement To replace the battery 1 Place the flame simulator on a table in a safe area not exceeding 104 F 40 C 2 Release the locking screw 3 Unscrew the battery back cover Item...

Page 77: ...b op is IIB H2 T5 Gb Ex ib op is tb IIIC T135 C Db 20 C to 50 C 4 F to 122 F EMI Compatibility Table 29 Immunity Tests Immunity Tests Title Basic Standard Level to be tested Electrostatic Discharge ESD IEC 61000 4 2 6kV 8kV contact air Radiated Electromagnetic Field IEC 61000 4 3 20V m 80MHz 1GHz 10V m 1 4 2GHz 3V m 2 0 2 7GHz Conducted Disturbances IEC 61000 4 6 10Vrms 150kHz 80MHz Immunity to Ma...

Page 78: ...me Detector User Guide 78 Tilt Mount D 2 Tilt Mount The tilt mount P N 40 40 001 provides accurate directional selection for optimum area coverage Figure 17 Tilt Mount www acornfiresecurity com www acornfiresecurity com ...

Page 79: ...ere the detector cannot be installed inside the area It comprises a special duct mount arrangement with a specific optical window to allow installation in high temperature duct applications The duct mount limits the cone of vision of the installed detector to 65 horizontal and 65 vertical The temperature allowed for the duct mount to be installed is 55 C to 200 C 67 F to 392 F For more instruction...

Page 80: ...r User Guide 80 Weather Cover D 4 Weather Cover The weather cover P N 777163 protects the detector from different weather conditions such as snow and rain Figure 19 Weather Cover www acornfiresecurity com www acornfiresecurity com ...

Page 81: ...ite The device is an add on accessory that enables designers and installers to optimize detector location and assess the actual coverage of installed detectors The device is universal and can be used with all 40 40 SharpEye Optical Flame Detectors Figure 20 Cone Viewer www acornfiresecurity com www acornfiresecurity com ...

Page 82: ...optical window The special air shield developed for SharpEye 40 40 series optical flame detectors allows their installation under environmental conditions where they may be exposed to oil vapors sand dust and other particulate matter The temperature of the air supply to the air shield should not exceed 60 C 140 F at any time Air pressure source Clean dry and oil free air Pressure 2 3 bar 30 45 psi...

Page 83: ...2 x 10 4 3 2 of SIL 2 if 0 20mA interface is used as alarm PFH 1 5 x 10 7 1 h 14 9 of SIL 2 for 0 20mA application SFF 95 fulfills the conditions of EN 61508 for SIL2 Alternative 2 Functional check of the detector every 365 days HFT 0 PFD 4 5 x 10 4 4 5 of SIL 2 if only alarm relay is used for alerting PFD 4 9 x 10 4 4 9 of SIL 2 if 0 20mA interface is used for signal current as alarm PFH 1 5 x 10...

Page 84: ...o 0 20mA Terminals The following allowed output current must be supervised with an accuracy of 5 Normal State 4mA Warning State 16mA Alarm State 20mA The receiving device must be programmed to indicate a fault condition when current levels reach overcurrent or undercurrent The 0 20mA can be used as low and high demand mode E 1 2 3 Using the Alarm Relay Contact for Alerting The following parameters...

Page 85: ... examined at least every 6 or 12 months see Safety Relevant Parameters on page 83 or whenever the flame detector must be switched off and on The window of the sensor must be examined at appropriate time intervals for partial contamination The HART and the RS 485 interfaces must not be used for the transmission of safety related data www acornfiresecurity com www acornfiresecurity com ...

Reviews: