TM 40/40I, Rev (14) February 2017
Internal Detector Tests
31
1.6.2.3 Manual BIT
The BIT is manually initiated by momentarily connecting Terminal 3 with
Terminal 2 (or a switch across these terminals in the safe area).
The results of a successful and unsuccessful Manual BIT are listed in
Table 12 and Table 13.
Table 12: Results of a Successful Manual BIT
Output
Result
Fault Relay
Wiring options 1, 2, and 4: remains Closed (Normal)
Wiring options 3 and 5: remains Open (Normal)
Alarm Relay
Activated for 3 sec (only when the function
alarm BIT
is
set to YES)
Auxiliary
Relay
For wiring options 4 and 5: is activated for 3 sec (only
when the function
auxiliary BIT
is set to
Yes
)
0
–
20mA
Output
Wiring options 1, 2, and 3:
Initiates 20mA only when the function alarm BIT is set
to Yes
Initiates 16mA when the function auxiliary BIT is set to
Yes and the function alarm
BIT
is set to
No
Power LED
Green, Flashing, 1Hz
Table 13: Results of an Unsuccessful Manual BIT
Output
Result
Fault Relay
Wiring options 1, 2, and 4: changes to Open
Wiring options 3 and 5: changes to Closed
0
–
20mA
Output
Wiring options 1, 2, and 3: Indicates BIT Fault (2mA)
Power LED
Yellow, Flashing, 4Hz
1.6.2.4 Manual BIT only selected
The BIT is initiated manually by momentarily connecting Terminal Number 3
with Terminal Number 2 (or a switch across these terminals in the safe
area).
Summary of Contents for SharpEye 40/40I
Page 2: ...www acornfiresecurity com www acornfiresecurity com ...
Page 12: ...www acornfiresecurity com www acornfiresecurity com ...
Page 32: ...www acornfiresecurity com www acornfiresecurity com ...
Page 46: ...www acornfiresecurity com www acornfiresecurity com ...
Page 54: ...www acornfiresecurity com www acornfiresecurity com ...
Page 55: ...Appendix 55 Appendix www acornfiresecurity com www acornfiresecurity com ...
Page 56: ...www acornfiresecurity com www acornfiresecurity com ...
Page 64: ...www acornfiresecurity com www acornfiresecurity com ...
Page 72: ...www acornfiresecurity com www acornfiresecurity com ...