Table C-1: Immunity to false alarm sources
(continued)
Radiation source
Immunity distance
SharpEye
40/40C-I and D-I
SharpEye
40/40C-M and D-
M
SharpEye
40/40C-LB and D-
LB
SharpEye
40/40C-L4B and
D-L4B
Vehicle exhaust diesel fume
For SharpEye 40/40D-IH only
IAD
IAD
N/A
N/A
Table C-2: Welding immunity distance
Level
Range
Distance
1
>10 ft (3 m)
>1.6 ft (0.5 m)
2
>50 ft (15 m)
>6 ft (2 m)
3
>100 ft (30 m)
>12 ft (4 m)
4
>150 ft (45 m)
>17 ft (6 m)
5
>215 ft (65 m)
>25 ft (7.5 m)
6
>295 ft (90 m)
>33 ft (10 m)
Table C-3: Halogen immunity distance
Sensitivity level
Detection range
Halogen distance
SharpEye 40/40C-LB and D-LB
SharpEye 40/40C-L4B and D-L4B
750 W
1000 W
750 W
1000 W
1
10 ft (3 m)
>13 ft (4 m)
>15 ft (4.5 m)
>6 ft (2 m)
>8 ft (2.5 m)
2
50 ft (15 m)
>43 ft (13 m)
>50 ft (15 m)
>15 ft (4.5 m)
>16 ft (5 m)
3
93 ft (28 m)
>66 ft (20 m)
>70 ft (21 m)
>27 ft (8 m)
>30 ft (9 m)
Immunity to false alarm sources
Reference Manual
December 2021
00909-0100-4975
48
Spectrex.net
Summary of Contents for SharpEye 40/40C Series
Page 4: ...4 ...
Page 10: ...Introduction Reference Manual December 2021 00909 0100 4975 10 Spectrex net ...
Page 24: ...Installation Reference Manual December 2021 00909 0100 4975 24 Spectrex net ...
Page 30: ...Maintenance Reference Manual December 2021 00909 0100 4975 30 Spectrex net ...
Page 40: ...Specifications Reference Manual December 2021 00909 0100 4975 40 Spectrex net ...
Page 42: ...Reference data Reference Manual December 2021 00909 0100 4975 42 Spectrex net ...
Page 46: ...FM fuel test responses Reference Manual December 2021 00909 0100 4975 46 Spectrex net ...
Page 49: ...Reference Manual 00909 0100 4975 December 2021 SharpEye 40 40 49 ...