Spectrex SharpEye 40/40 Series User Manual Download Page 79

 

Accessories 

TM40/40L Rev. (Ag), February 2019 

79 

 

D.3

 

Duct Mount  

The duct mount (P/N 777670) is suitable for use with the SharpEye 40/40 Series 
Optical Flame Detectors 40/40L, LB, L4 & L4B, for both the aluminum and st.st. 
enclosure.  

The duct mount allows flame detection in areas where high temperatures exist or 
where the detector cannot be installed inside the area. It comprises a special duct 
mount arrangement with a specific optical window to allow installation in high 
temperature duct applications.  

The duct mount limits the cone of vision of the installed detector to 65° 
horizontal and 65° vertical. 

The temperature allowed for the duct mount to be installed is:  

55°C to +200°C / 

67°F to +392°F.  

For more instructions refer to 

TM777670

 

Figure 18: Duct Mount 

Summary of Contents for SharpEye 40/40 Series

Page 1: ...40 40 Series UV IR Flame Detector Models 40 40L LB and 40 40L4 L4B User Guide 8200 Market Blvd Chanhassen MN 55317 USA Phone 1 973 239 8398 Website www spectrex net Email spectrex csc rmtna emerson com ...

Page 2: ......

Page 3: ...ion or any use of any product or circuit described herein neither does it convey license under its patent rights or the rights of others Warranty SPECTREX agrees to extend to Purchaser Distributor a warranty on the SPECTREX supplied components of the SharpEye products SPECTREX warrants to Purchaser Distributor that the products are free from defects in materials and workmanship for a period of fiv...

Page 4: ......

Page 5: ... 2 4 2 Heated Optics 22 2 4 3 HART Protocol 22 2 4 4 RS 485 Modbus 22 2 4 5 Product Certification 22 2 5 Performance Considerations 25 2 5 1 Detection Sensitivity 25 2 5 2 Cone of Vision 26 2 5 3 False Alarm Prevention 27 2 5 4 Visual Indicators 28 2 5 5 Output Signals 29 2 5 6 Detector Status 30 2 5 7 Auxiliary Relay as End of Line 32 2 6 Internal Detector Tests 32 2 6 1 Continuous Feature Test 3...

Page 6: ...ng the Detector 44 3 7 1 Verifying the Detector Wiring 46 3 8 Configuring Your Detector 47 3 8 1 Alarm Delay 48 3 8 2 Address Setup 48 3 8 3 Function Setup 48 3 8 4 Heated Optics 49 4 Operating the Detector 51 4 1 Powering Up 51 4 2 Safety Precautions 51 4 2 1 Default Functions Settings 52 4 3 Testing Procedures 52 4 3 1 Automatic BIT Test 53 4 3 2 Manual BIT Test 53 4 3 3 Testing with Flame Simul...

Page 7: ...lectronic Modules 62 A 5 4 Electrical Connection 2 entries 62 A 5 5 Dimensions 62 A 5 6 Weight 62 A 6 Environmental Specifications 62 A 6 1 High Temperature 62 A 6 2 Low Temperature 62 A 6 3 Humidity 63 A 6 4 Salt Fog 63 A 6 5 Dust 63 A 6 6 Vibration 63 A 6 7 Mechanical Shock 63 A 6 8 Electromagnetic Compatibility EMC 64 Appendix B Wiring Instructions 65 B 1 General Instructions for Electrical Wir...

Page 8: ...attery Replacement 76 D 1 7 Technical Specifications 77 D 2 Tilt Mount 78 D 3 Duct Mount 79 D 4 Weather Cover 80 D 5 Air Shield 81 Appendix E SIL 2 Features 82 E 1 40 40LB L4B Flame Detectors 82 E 1 1 Safety Relevant Parameters 82 E 1 2 Guidelines for Configuring Installing Operating and Service 82 Appendix F End of Line Resistor 84 Technical Support 88 ...

Page 9: ...for 4 Wire Controllers Using Option 1 or 2 Wiring 68 Figure 10 0 20mA Wiring Option 1 Sink 4 Wire Default 69 Figure 11 0 20mA Wiring Option 1 Converted to Source 3 Wire 69 Figure 12 0 20mA Wiring Option 1 Non isolated Sink 3 Wire 70 Figure 13 0 20mA Wiring Option 2 and 3 Source 3 Wire available with the HART Protocol 70 Figure 14 RS 485 Networking 71 Figure 15 Flame Simulator FS 1200 73 Figure 16 ...

Page 10: ...sful Manual BIT 35 Table 12 Results of an Unsuccessful Manual BIT 35 Table 13 Tools 39 Table 14 Model 40 40L LB L4 and L4B Wiring Options 46 Table 15 Functions 48 Table 16 Default Function Values 52 Table 17 Results of Successful Flame Simulator Test 54 Table 18 Troubleshooting Table 56 Table 19 Electrical Specifications 58 Table 20 Contact Ratings 59 Table 21 20mA Current Output 59 Table 22 Elect...

Page 11: ...how to install the detector including preparations before installation wiring and mode settings Chapter 4 Operating the Detector describes how to power up and test the detector The chapter also lists safety precautions you should take when operating the detector Chapter 5 Maintenance and Troubleshooting describes basic maintenance troubleshooting and support procedures Appendix A Specifications li...

Page 12: ...ase Jay Cooley Ian Buchanan 7 February 2017 Eighth Release Jay Cooley Ian Buchanan 8 February 2015 Ninth Release Ian Buchanan Eric Zinn 9 June 2015 Tenth Release Ian Buchanan Eric Zinn 10 November 2015 Eleventh Release Ian Buchanan Eric Zinn 11 January 2016 Twelfth Release Ian Buchanan Eric Zinn 12 July 2016 Thirteenth Release Ian Buchanan Eric Zinn 13 October 2016 Fourteenth Release Jay Cooley Ia...

Page 13: ...way Addressable Remote Transducer communications protocol IAD Immune at Any Distance IECEx International Electro Technical Commission Explosion IP Internet Protocol IPA Isopropyl Alcohol IR Infrared IR3 Refers to the 3 IR sensors in the VID JP5 Jet Fuel LED Light Emitting Diode MODBUS Serial communications protocol using Master Slave messaging N A Not Applicable N C Normally Closed NFPA National F...

Page 14: ...About this Guide 14 SharpEye 40 40L LB and 40 40L4 L4B User Guide Abbreviation Term Meaning UNC Unified Coarse Thread VAC Volts Alternating Current ...

Page 15: ...t this guide Warning This indicates a potentially hazardous situation that could result in serious injury and or major damage to the equipment Caution This indicates a situation that could result in minor injury and or damage to the equipment Note This provides supplementary information emphasizes a point or procedure or gives a tip to facilitate operation ...

Page 16: ......

Page 17: ...e parameters as well as performing other maintenance and monitoring tasks is possible by means of RS 485 based Modbus communication or HART communication in models with 0 20mA output Warning The detector is not field repairable due to the meticulous alignment and calibration of the sensors and the respective circuits Do not attempt to modify or repair the internal circuits or change their settings...

Page 18: ...iring options Temperature ranges Type of cable entries Housing material type Required approval The configuration detail is included in the product part number on the product label and takes the form 40 40L LB L4 L4B XXXXX where XXXXX defines the model according to the above requirements To modify the default or pre ordered configuration and perform maintenance tasks please refer to the HART Protoc...

Page 19: ...Power Manual BIT Fault Relay N O Alarm Relay N O N C 0 20mA Source RS 485 HART 4 Power Manual BIT Fault Relay N C Alarm Relay N O Auxiliary N O RS 485 5 Power Manual BIT Fault Relay N O Alarm Relay N O Auxiliary N O RS 485 Note Wiring option 1 is the default The mA sink output can be altered to source type with a link between Terminals 1 and 8 No other wiring options can be changed onsite Table 2 ...

Page 20: ...nformation in Checking the Product Type on page 38 2 3 Features and Benefits UV IR Dual Sensor Built In Test BIT Manual and Automatic see Built In Test BIT on page 33 Heated Window Prevents effects of ice snow and condensation Electrical Interface Dry contact relays Communication network RS 485 0 20mA output HART Protocol Communication protocol see HART Protocol on page 22 Exde Integral junction b...

Page 21: ...xyl and hydrogen fires as well as metal and inorganic fires The IR sensor in models 40 40L4 and L4B is sensitive over a range of 4 4 4 6µm spectral band where the CO2 has a unique spectral peak that enables it to detect the combustion product of any organic substance The UV sensor is sensitive to radiation over the range of 0 185 0 260µm The UV Channel incorporates a special logic circuit that eli...

Page 22: ...used to communicate between intelligent field instruments and host systems HART is the global standard for smart process instrumentation and the majority of smart field devices installed in plants worldwide are HART enabled HART is available in wiring options 1 2 and 3 see Table 1 HART technology is easy to use and very reliable Through the HART connection you are able to perform Detector setup De...

Page 23: ...0 001 Weather Cover P N 777163 and P N 777268 Duct Mount P N 777670 and Air Shield P N 777650 are included in the approval This product is suitable for use in hazardous Zones 1 and 2 with IIC gas group vapors present and Zones 21 and 22 with IIIC dust type present 2 4 5 3 FM CSA The 40 40L LB L4 L4B Flame Detectors are approved per FM and CSA Explosion Proof and Functionality per FM3260 Class I Di...

Page 24: ...es a functional test environmental test EMI EMC test and software check For more details see VdS Report No BMA 12120 for models 40 40L LB and Reports No s BMA 12120 and BMA 12121 for models 40 40L4 L4B 2 4 5 6 Inmetro UL The 40 40L LB L4 and L4B Flame Detectors are in compliance with the standards ABNT NBR IEC 60079 0 ABNT NBR IEC 60079 1 ABNT NBR IEC 60079 7 ABNT NBR IEC 60079 18 ABNT NBR IEC 600...

Page 25: ...rning Pre alarm Alarm The detection distance for the alarm level is 50ft 15m for models 40 40L LB and 93ft 28m for models 40 40L4 L4B from a standard fire The detection distance for the warning level is approximately 10 higher than for the alarm distance For some typical ambient conditions the Zeta parameter as defined in NFPA 72 for the detector is 0 005 1 m Note Zeta parameters may vary signific...

Page 26: ...5 93 28 N Heptane 50 15 93 28 LPG 43 13 60 18 JP5 37 11 70 21 Kerosene 37 11 70 21 Diesel Fuel 37 11 70 21 Polypropylene 33 10 60 18 Hydrogen 33 10 Methane 26 8 60 18 Ethanol 95 25 7 5 57 17 IPA 25 7 5 70 21 Methanol 25 7 5 57 17 Paper 16 5 33 10 30 0 75m high 10 0 25m width plume fire 2 5 2 Cone of Vision Horizontal 100 Figure 1 Horizontal Field of View ...

Page 27: ...Alarm Sources Radiation Source Immunity Distance ft m Indirect or reflected sunlight IAD Vehicle headlights low beam conforming to MS53023 1 IAD Incandescent frosted glass light 300W IAD Fluorescent light with white enamel reflector standard office or shop 70W or 2 35W IAD Electric arc 12mm 15 32 gap at 4000V alternating current 60Hz IAD Arc welding 6mm 5 16 rod 210A 9 8 3 Ambient light extremes d...

Page 28: ...tion heater 1000W with fan IAD Quartz lamp 1000W 12 4 Mercury vapor lamp IAD Grinding metal 3 3 1 Lit cigar IAD Lit cigarette IAD Match wood stick including flare up 3 3 1 Notes IAD Immune at Any Distance All sources are chopped from 0 20Hz 2 5 4 Visual Indicators One 3 color LED indicator is located inside the detector window as shown in Figure 3 The detector statuses are listed in Table 5 Table ...

Page 29: ... to the default configuration or the wiring options selected for the 40 40L LB L4 and L4B detectors Determine the outputs for your model according to Table 6 The detector incorporates several types of output suitable to different control systems 0 20mA stepped with HART Relays alarm fault auxiliary RS 485 Modbus Indicator LED ...

Page 30: ... L4B Options 2XXXX and 3XXXX Source with the HART protocol RS 485 All versions Modbus protocol 2 5 6 Detector Status The possible detector function statuses are listed in Table 7 A more detailed fault analysis can be seen via HART or RS 485 Table 7 Detector Status Status Description Normal Normal operation BIT Built In Test being performed Warning Fire detected changed to Warning pre alarm state A...

Page 31: ...ire is no longer detected 2 The alarm state can be optionally latched via programmed function default is non latched 3 The detector will remain in BIT Fault state until it has passed a successful BIT 4 The auxiliary relay can be activated at the warning level or alarm level depending on programmed function Note The outputs depend on the wiring options 2 5 6 1 Optional Latching Alarms are set as no...

Page 32: ...IT page 33 2 6 1 Continuous Feature Test During normal operation the detector tests itself continuously and indicates a fault if a failure is found This type of test complies with SIL 2 requirements The detector continuously tests Input voltage level All internal regulator voltage levels Voltage level status of sensor and sensor circuitry for noise or disconnection in the electronic circuitry 0 20...

Page 33: ...ote In Manual BIT the outputs may also be tested and Control System inhibit should be applied if this could initiate other systems 2 6 3 1 How the BIT Operates The detector s status remains unchanged if the result of a BIT is the same as the current status normal or BIT fault The detector s status changes from normal to BIT fault or vice versa if the BIT differs from the current status Note In BIT...

Page 34: ... options 1 2 and 3 normal 4mA Power LED Green flashing 1Hz on normal Table 10 Results of an Unsuccessful BIT Output Result Fault Relay Wiring options 1 2 and 4 changes to open Wiring options 3 and 5 changes to closed 0 20mA Output Wiring options 1 2 and 3 BIT fault 2mA Power LED Yellow flashing 4Hz BIT Procedure Performed every 1 minute 2 6 3 3 Manual BIT The BIT is manually initiated by momentari...

Page 35: ...ptions 1 2 and 3 Initiates 20mA only when the function alarm BIT is set to Yes Initiates 16mA when the function auxiliary BIT is set to Yes and the function alarm BIT is set to No Power LED Green Flashing 1Hz Table 12 Results of an Unsuccessful Manual BIT Output Result Fault Relay Wiring options 1 2 and 4 changes to Open Wiring options 3 and 5 changes to Closed 0 20mA Output Wiring options 1 2 and...

Page 36: ......

Page 37: ...ed Type of flammable materials 3 1 2 Wiring The wire gauge must be designed according to the distance from the detector to the controller and the number of detectors on the same power line See Wiring Instructions on page 65 To fully comply with EMC directive and protect against interference caused by RFI and EMI the cable to the detector must be shielded and the detector must be grounded The shiel...

Page 38: ...ived the following contents Delivery form Flame detector Plastic weather cover User manual Quality document Tool keys per shipment Check and record the following Verify the appropriate Purchase Order Record the Part Number P N and Serial Number of the detectors and the installation date in an appropriate logbook Verify that all components required for the detector installation are readily availabl...

Page 39: ...r site wiring The selection of wire gauge should be based on the number of detectors used on the same line and the distance from the control unit in compliance with specifications see General Instructions for Electrical Wiring on page 65 3 4 Certification Instructions Warning Do not open the detector even when isolated in the presence of any open flame 3 4 1 Special Instructions for Safe Use The d...

Page 40: ...hould be verified that the temperature of the air duct process vessel should not be capable of heating or cooling any part of the equipment enclosure to a temperature outside the marked maximum ambient temperature range prior to switching the equipment on when taking into account surrounding ambient temperature 3 4 2 General Instructions The cable entry point may exceed 167 F 75 C Suitable precaut...

Page 41: ... well shielded in order to comply with EMC requirement see Table 22 Ground the detector to the nearest ground point not more than 3m from the detector location Install the detector with the cable entries placed downwards 3 5 1 Conduit Installation The conduit used for the cabling must comply with the following To avoid water condensation or water in the detector install the detector with the condu...

Page 42: ...0L LB and 40 40L4 L4B User Guide 3 6 Installing the Tilt Mount The tilt mount P N 40 40 001 enables the detector to be rotated up to 60º in all directions Figure 4 shows the detector mounted on the tilt mount Figure 4 Detector with Tilt Mount ...

Page 43: ... tilt mount assembly Figure 5 Tilt Mount Assembly Figure 6 shows the tilt mount assembly with dimensions in both millimeters and inches Figure 6 Tilt Mount Assembly dimensions in millimeters and inches Tilt holding plate Tilt mount Horizontal locking screw Detector holding plate Vertical locking screw ...

Page 44: ...Point the detector towards the protected area and make certain that the view of the area is unobstructed Secure the detector in that position by tightening the locking screws on the tilt mount making sure the detector is in the correct position The detector is now correctly located aligned and ready to be connected to the system 3 7 Connecting the Detector This section describes how to connect the...

Page 45: ...minal The detector must be well grounded to earth ground 7 Verify the wiring Warning Improper wiring may damage the detector 8 Check the wires for secure mechanical connection and press them neatly against the terminal to prevent them from interfering while closing the back cover Figure 6 9 Place and secure the detector s back cover by screwing the 3 socket head screws in the cover bolts Figure 4 ...

Page 46: ...24VDC 24VDC 24VDC 2 0VDC 0VDC 0VDC 0VDC 0VDC 3 Manual BIT Manual BIT Manual BIT Manual BIT Manual BIT 4 Fault Relay N C Fault Relay N C Fault Relay N O Fault Relay N C Fault Relay N O 5 6 Alarm Relay N O Alarm Relay N O Alarm Relay N O Alarm Relay N O Alarm Relay N O 7 Alarm Relay C Alarm Relay C Alarm Relay C Alarm Relay C Alarm Relay C 8 0 20mA In Alarm Relay N C Alarm Relay N C Auxiliary N O Au...

Page 47: ... auxiliary output is N O SPST relay Depending on the function configuration the auxiliary relay may act in parallel with the alarm relay to activate another external device or it may provide a warning signal 3 8 Configuring Your Detector You can reprogram the function setup using the RS 485 connection or the HART default functions settings USB RS 485 Harness Kit P N 794079 The USB RS 485 Harness K...

Page 48: ...delays the execution of the alarm outputs by the specified period of time The detector then evaluates the condition for 3 seconds If the alarm level is still present the alarm outputs are activated If this condition no longer exists the detector returns to its standby state The alarm delay option affects the output relays and the 0 20mA The LEDs and outputs indicate warning levels during the delay...

Page 49: ...Manual BIT does not activate the Auxiliary Relay EOL Yes Auxiliary relay is used as End of Line No Auxiliary relay operates in accordance with Functions 2 and 5 default Only available in Models 40 40L LB L4 L4B 4XXXX and 5XXXX 3 8 4 Heated Optics The heated optics can be defined as one of the following modes Heated Mode Off Not operated On Continuously Auto Per temperature change In Auto mode the ...

Page 50: ......

Page 51: ...ashes at 4Hz BIT is executed If successful the green LED flashes at 1Hz the fault relay contacts close and mA output is 4mA 3 Enter Normal mode Caution The majority of detectors are used in the default non latched alarm mode Only perform a reset when the latched alarm option has been programmed To reset the detector when it is in a latched alarm state Disconnect power Terminal Number 1 or Terminal...

Page 52: ... available This function is not used Automatic BIT Yes Alarm BIT No Auxiliary BIT No In wiring options 1 2 and 3 the auxiliary relay is not available This function is not used EOL No In wiring options 1 2 and 3 the auxiliary relay is not available This function is not used Heat Mode Auto Heat On 41 F 5 C The detector starts heating the window for any temperature below this value in degrees Celsius...

Page 53: ... to a real fire condition The detector is exposed to radiation at the required detection level As a result the detector will generate a Fire Alarm signal See Flame Simulator FS 1200 on page 73 for more information Caution If the detector is exposed to a flame simulator the alarm and accessory relays and 0 20mA are activated during the simulation Therefore automatic extinguishing systems and any ex...

Page 54: ...l Flame Simulator Test Component Action Notes 0 20mA Turn to 20mA For a few seconds and then returns to 4mA Alarm Relay Activated For a few seconds and then returns to Normal Auxiliary Relay Activated For a few seconds and then returns to Normal Fault Relay Remains active during the test LED Red steady ...

Page 55: ...of cleaning operations depends upon the local environmental conditions and specific applications The fire detection system designer will give his recommendations To clean the detector viewing window and reflector 1 Disconnect power to the detector before proceeding with any maintenance including window lens cleaning 2 Use water and detergent and then rinse the viewing window with clean water 3 Whe...

Page 56: ...g Table Problem Cause Corrective Action LEDs Off Fault Relay at N O 0 20mA at 0mA No power to the unit Check that the correct power is sent to the detector Check power polarity Check wiring in the detector Send the detector back for repairs Yellow amber LED flashes at 4Hz Fault Relay at N O 0 20mA at 0mA Fault Detector Low Voltage Faulty Detector Check the voltage at the detector verify at least 2...

Page 57: ...ypropylene 33 10 30 0 75m high 10 0 25m width plume fire 40 40L4 L4B Detection Range at highest sensitivity setting for 1ft2 0 1m2 pan fire Fuel ft m Fuel ft m Gasoline 93 28 Polypropylene 60 18 n Heptane 93 28 LPG 60 18 IPA 70 21 Methane 60 18 JP5 70 21 Ethanol 95 57 17 Kerosene 70 21 Methanol 57 17 Diesel Fuel 70 21 Paper 33 10 30 0 75m high 10 0 25m width plume fire Response Time Typically 5 se...

Page 58: ... 3 04W 2 56W Alarm when heater on 3 68W 3 2W Maximum Current Max 18 32VDC Normal 90mA 85mA Normal when heater on 105mA 100mA Alarm 130mA 115mA Alarm when heater on 160mA 145mA A 2 1 Electrical Input Protection The input circuit is protected against voltage reversed polarity voltage transients surges and spikes according to MIL STD 1275B A 3 Outputs A 3 1 Electrical Interface There are 5 output wir...

Page 59: ...DT N O N C 2A at 30DVC Auxiliary SPDT N O 2A at 30VDC Fault1 2 SPDT N C or N O 2A at 30VDC 1 The fault relay in wiring options 1 2 and 4 is normally energized closed during normal operation of the detector The relay is de energized open in a fault condition or low voltage situation 2 In wiring options 3 and 5 the relay is normally energized open during normal operation of the detector The relay is...

Page 60: ...nstallations with computerized controllers The communications protocol is Modbus compatible This protocol is a standard and widely used It enables continuous communication between a standard Modbus controller Master device and a serial Network of up to 247 detectors A 3 5 Heated Optics The front window can be heated to improve performance in ice condensation and snow conditions The heater increase...

Page 61: ...96 C Db 55 C Ta 75 C Or Ex II 2G D Ex db eb op is IIC T4 Gb Ex tb op is IIIC T106 C Db 55 C Ta 85 C TR CU EAC 1 Ex db eb op is IIC T4 Gb X Ex tb op is IIIC T96 C Db X 55 C Ta 75 C Or 1 Ex db eb op is IIC T4 Gb X Ex tb op is IIIC T106 C Db X 55 C Ta 85 C Or 1 Ex db eb mb op is II T4 Gb X Ex tb op is IIIC T98 C Db X 55 C Ta 75 C A 4 2 Functional Approvals EN54 10 approved per VdS FM approved per FM3...

Page 62: ...nduit Or M25 x 1 5 A 5 5 Dimensions 4 x 4 6 x 6 18 101 6 x 117 x 157 mm A 5 6 Weight Stainless Steel 6 1lb 2 8kg Aluminum 2 8lb 1 3kg A 6 Environmental Specifications The SharpEye 40 40L LB L4 L4B is designed to withstand harsh environmental conditions A 6 1 High Temperature Designed to meet MIL STD 810C Method 501 1 Procedure II Operating temperature 167 F 75 C Storage temperature 185 F 85 C A 6 ...

Page 63: ...8 hours A 6 5 Dust Designed to meet MIL STD 810C Method 510 1 Procedure I Exposure to a dust concentration of 0 3g ft2 at a velocity of 1750fpm for 12 hours A 6 6 Vibration Designed to meet MIL STD 810C Method 514 2 Procedure VIII Vibration at an acceleration of 1 1g within the frequency range of 5 30Hz and an acceleration of 3g within the frequency range of 30 500Hz A 6 7 Mechanical Shock Designe...

Page 64: ...urge IEC 61000 4 5 EN 50130 4 Conducted Disturbances IEC 61000 4 6 EN 50130 4 Power Frequency Magnetic Field IEC 61000 4 8 EN 50130 4 Radiated Emission IEC 61000 6 3 EN 55022 Conducted Emission IEC 61000 6 3 EN 55022 Immunity to Main Supply Voltage Variations IEC 61000 4 29 EN 50130 4 Caution To fully comply with EMC directive 2014 30 EU and protect against interference caused by RFI and EMI the c...

Page 65: ...0 88 2 Use Table 24 to select wire gauge for power supply wires DO NOT connect any circuit or load to detectors supply inputs Select number of detectors connected in 1 circuit Select wiring length per your installation requirements Refer to power supply range for voltage extreme applied Table 24 Wiring Length in ft m Number of Detectors Recommended Wire Diameter AWG Power Supply Range VDC 24 18 16...

Page 66: ...late the voltage drop on the wire as follows V 2L x R x N x 0 2A 100 20 V Minimum required voltage of the power supply 0 2A is the maximum power consumption of the detector For example if N 1 1 detector in loop L 1000m Wire size 1 5mm see Table 24 the resistance per 100m for 1 5mm is 1 4Ω Calculate the voltage drop in the wire as follows 2 x 1000 x 1 4Ω x 1 x 0 2A 5 6V 100 The minimum voltage of t...

Page 67: ...Wiring Instructions TM40 40L Rev Ag February 2019 67 B 2 Typical Wiring Configurations This section describes examples of typical wiring configurations Figure 8 Wiring Terminals ...

Page 68: ...ink 0 20mA Sink 2 40 40L LB L4 L4B 2XXXX Fault Relay N C Alarm Relay N C 0 20mA Source 3 40 40L LB L4 L4B 3XXXX Fault Relay N O Alarm Relay N C 0 20mA Source 4 40 40L LB L4 L4B 4XXXX Fault Relay N C Auxiliary Relay N O Auxiliary Relay N O 5 40 40L LB L4 L4B 5XXXX Fault Relay N O Auxiliary Relay N O Auxiliary Relay N O Figure 9 Typical Wiring for 4 Wire Controllers Using Option 1 or 2 Wiring ...

Page 69: ...Wiring Instructions TM40 40L Rev Ag February 2019 69 Figure 10 0 20mA Wiring Option 1 Sink 4 Wire Default Figure 11 0 20mA Wiring Option 1 Converted to Source 3 Wire ...

Page 70: ...40L LB and 40 40L4 L4B User Guide Figure 12 0 20mA Wiring Option 1 Non isolated Sink 3 Wire Figure 13 0 20mA Wiring Option 2 and 3 Source 3 Wire available with the HART Protocol Note There are no 0 20mA outputs in wiring options 4 and 5 ...

Page 71: ...t up to 32 detectors in an addressable system with 4 wires only 2 for power and 2 for communication Using repeaters the number of detectors can be much larger 32 detectors for each repeater up to 247 on the same 4 wires When using the RS 485 network it is possible to read each detector status FAULT WARNING and ALARM and to initiate a BIT for each detector individually For more details contact SPEC...

Page 72: ......

Page 73: ...flame detectors The FS 1200 includes a halogen lamp that emits UV and IR energy This energy is accumulated by a reflector directed towards the detector which allows the detectors to be tested under simulated fire conditions without the associated risks of an open flame Figure 15 Flame Simulator FS 1200 D 1 1 Ordering Information The P N of the Flame Simulator Kit is 380114 1 The kit is supplied in...

Page 74: ... simulates a real fire condition and may activate the extinguishing system or other alarms If activation is not desired disconnect inhibit them before the test and reconnect after the simulation To simulate a fire 1 Verify you are at the correct distance from the detector according to the type of detector and the detector sensitivity 2 Using the mechanical sight aim the flame simulator toward the ...

Page 75: ...duction in the range Warning Keep the flame simulator in a safe place when not in use D 1 5 Charging the Battery The flame simulator uses lithium ion batteries as a rechargeable power source When the batteries are fully charged the simulator operates at least 1 000 times without having to be recharged The simulator will not operate when the voltage from the batteries is lower than the required ope...

Page 76: ...8 Insert the battery into the flame simulator 9 Screw on the locking disc Item 3 10 Screw on the back cover Item 4 11 Lock the back cover with the locking screw D 1 6 Battery Replacement To replace the battery 1 Place the flame simulator on a table in a safe area not exceeding 104 F 40 C 2 Release the locking screw 3 Unscrew the battery back cover Item 4 counterclockwise 4 Unscrew the locking disc...

Page 77: ... ATEX IECEx Ex II 2 G D Ex d ib op is IIB H2 T5 Gb 20 C to 50 C 4 F to 122 F D 1 7 1 EMI Compatibility Table 27 Immunity Tests Immunity Tests Title Basic Standard Level to be tested Electrostatic Discharge ESD IEC 61000 4 2 6kV 8kV contact air Radiated Electromagnetic Field IEC 61000 4 3 20V m 80MHz 1GHz 10V m 1 4 2GHz 3V m 2 0 2 7GHz Conducted Disturbances IEC 61000 4 6 10Vrms 150kHz 80MHz Immuni...

Page 78: ...Accessories 78 SharpEye 40 40L LB and 40 40L4 L4B User Guide D 2 Tilt Mount The tilt mount P N 40 40 001 provides accurate directional selection for optimum area coverage Figure 17 Tilt Mount ...

Page 79: ...re high temperatures exist or where the detector cannot be installed inside the area It comprises a special duct mount arrangement with a specific optical window to allow installation in high temperature duct applications The duct mount limits the cone of vision of the installed detector to 65 horizontal and 65 vertical The temperature allowed for the duct mount to be installed is 55 C to 200 C 67...

Page 80: ...ssories 80 SharpEye 40 40L LB and 40 40L4 L4B User Guide D 4 Weather Cover The weather cover P N 777163 protects the detector from different weather conditions such as snow and rain Figure 19 Weather Cover ...

Page 81: ...tly in order to clean its optical window The special air shield developed for SharpEye 40 40 series optical flame detectors allows their installation under environmental conditions where they may be exposed to oil vapors sand dust and other particulate matter The temperature of the air supply to the air shield should not exceed 60 C 140 F at any time Air pressure source Clean dry and oil free air ...

Page 82: ... alert conditions according to SIL 2 can be implemented by an Alert signal via 20mA current loop Or Alert signal via alarm relay and the fault relay E 1 2 1 Conditions for Safe Operating The flame detector must consist only of the approved hardware and software modules The 24V power supply must fulfill the requirements for PELV SELV of EN 60950 The automatic BIT Built In Test must be activated The...

Page 83: ...ated at 0 6 of the nominal specified relay contact current The maximum contact rating that is allowed per SIL 2 is 30VDC The contact of the alarm relay opens if there is a fire alarm During the forwarding and evaluation of the alarm the relay contact opens E 1 2 4 Other The complete function of the flame detector flame detection function of the 0 20mA interface and the relays must be examined at l...

Page 84: ...minal compartment The EOL resistor can be situated in the rear part which is Ex e or Ex d depending on the application When the resistor is assembled the rear part can be used as Ex d only To meet the allowed power consumption the total resistance should be higher than 1 5KΩ Figure 21 End of Line Resistor Assembly ...

Page 85: ......

Page 86: ......

Page 87: ......

Page 88: ...Technical Support For technical assistance or support contact 8200 Market Blvd Chanhassen MN 55317 USA Phone 1 973 239 8398 Email spectrex csc rmtna emerson com Website www spectrex net ...

Reviews: