Product Overview
24
SharpEye™
40/40L, LB and 40/40L4, L4B User Guide
2.4.5.4
SIL-2 (TÜV)
(Models 40/40LB and L4B only)
The 40/40LB, L4B Flame Detectors are approved per SIL-2 requirement per IEC
61508.4, Chapter 3.5.12.
The alert condition according to SIL-2 can be implemented by:
•
Alert signal via 0
–
20mA current loop
Or
•
Alert signal via alarm relay and fault relay
•
For more details and guidelines for configuring, installing, operating, and
service, see
on page 82 and
TÜV Report No. 968/EZ 348.
2.4.5.5
EN54-10
The 40/40L, LB, L4, L4B Flame Detectors are approved per EN54-10 and CPD.
•
The detector has been tested and approved per EN54-10 by VdS.
•
This test includes a functional test, environmental test, EMI/EMC test, and
software check.
•
For more details see VdS Report No. BMA 12120 for models 40/40L-LB and
Reports No's. BMA 12120 and BMA 12121 for models 40/40L4-L4B.
2.4.5.6
Inmetro (UL)
The 40/40L, LB, L4, and L4B Flame Detectors are in compliance with the
standards ABNT NBR IEC 60079-0, ABNT NBR IEC 60079-1, ABNT NBR IEC
60079-7, ABNT NBR IEC 60079-18, ABNT NBR IEC 60079-31, and INMETRO
decree No. 179 as of May 18th, 2010. Further details may be found on Certificate
of Compliance No. UL-BR 16.065XX.
2.4.5.7
TR CU/EAC
The 40/40L, LB, L4, and L4B Flame Detectors are in compliance with the standard
TR CU 012/2011 per:
1 Ex db eb op is IIC T4 Gb X
Ex tb op is IIIC T96°C Db X
(
–55°C ≤ Ta ≤ +75°C)
Or
1 Ex db eb op is IIC T4 Gb X
Ex tb op is IIIC T106°C Db X
(
–55°C ≤ Ta ≤ +85°C)
Or
1 Ex db eb mb op is IIC T4 Gb X
Ex tb op is IIIC T98°C Db X
(
–55°C ≤ Ta ≤ +75°C)