5. Technical Specifications
5.1 Electrical Specifications
a. Operating Voltage
: 18-32 VDC
b. Power Consumption
:
Max. 80mA in Stand-by
Max. 120mA in Alarm
c. Electric input protection
:
The input circuit is protected against voltage reversed polarity voltage transients,
surges and spikes according to MIL-STD-1275A.
d. Electrical Interface
:
Terminals
Function
1
POWER SUPPLY IN (+)
2
RTN
3
MANUAL BIT
4
ALARM RELAY (NO)
5
ALARM RELAY (COMMON.)
6
ALARM RELAY (NC)
7
FAULT RELAY (NO)
8
FAULT RELAY (COMMON.)
9
ACCESSORY RELAY (NO)
10
ACCESSORY RELAY (COMMON)
11
4-20mA(-)
12
4-20mA(+)