METERING AND DIAGNOSITCS

This SpectraPure purification system has been fully equipped with sufficient instrumentation 
to make monitoring and troubleshooting an easy process. The provided pressure gauge is 
used to determine the tap water pressure and to evaluate the condition of the sediment 
and carbon prefilters.

(The pressure will drop as the pre-filters become clogged by dirt [turbidity] from the tap 
water).

The digital TDS meter (left side) will provide a reliable means of evaluating the efficiency of 
the RO membrane. This meter will indicate the tap water conductivity and the RO water 
conductivity. The difference between the two meter readings will be used to calculate the 
percentage of rejection of the (TFC) RO membrane.           

The Digital TDS meter (right side) will be used to determine the condition of the two stages 
of the DI system. As the reading on the meter begin to increase, the operator will be alerted 
to the possibility that the DI system may have deteriorated past the exhaustion point and 
that the DI cartridges may need to be replaced. 

Fig. A: System Components

TFC RO Membrane

(MEM-150)

.5 micron 

MicroTec™

Sediment 

Pre-Filter

(SF-MT-.5-

10)

 .5 micron 

Carbon 

Block Pre-

Filter (CF-.5-

10)

Pressure

Guage

(2) TDS 

Monitors

DI 

Cartridge #1

DI-MC-10

DI 

Cartridge #2

DI-SB-10

SpectraPure®Inc

 Fax  480.894.6109 Fax us toll-free 1.877.527.7873

E-mail: [email protected] Visit us on the web www.spectrapure.com

19

SpectraPure

®

USING THE PRESSURE GAUGE

The pressure gauge is used to monitor the condition of the Sediment and Carbon

Pre-Filters. With the Sediment and Carbon filters removed, the gauge will indicate 

the “actual” input water tap water pressure. When the prefilters are “new”, the 

pressure shown on the gauge will be slightly less than the actual tap water 

pressure and as the filters age the pressure will drop due to the dirt that will 

collect in the prefilters. When the pressure on the gauge drops below 40-PSI or as 

the filters collect particulates and the pressure drop is greater than 15% to 20% of 

the normal water pressure, the pre-filters are in need of replacement.

NOTE: When the pressure on the pressure gauge drops below the normal 

readings; do not “assume” that the sediment filter is the only cause. In some

 geographical areas where the input water contains a high percentage of very 

small micron particulates, the carbon filter may become clogged before the 

sediment filter. (The filters may look “new” but still cause the water pressure to 

drop). Do not judge the condition of the prefilters by their color, always use the 

pressure gauge to determine the condition of the prefilters. 

MAINTENANCE

The maintenance and trouble-shooting procedures have been made easy and 
effective with a combination of the Pressure gauge and two dual Inline TDS  
meters. 
 

-  When there is a pressure drop of 15% of your normal house 

 

   pressure that is an indication that your pre-filters need to be

 

   replaced.

 

-  The TDS monitors will let you know when the TDS level rises. All 

 

   our membranes have a 98% rejection. When the TDS level starts

 

   to rise the % rejection will decrease. You should replace the 

 

   membrane before the % rejection gets to 90%.

It is highly recommended that one set of Sediment and Carbon 
replacement filters should be on hand and ready for installation as soon as the 
fist monitor indicates that a cartridge change or replacement is required. We do 
not recommend that you have a replacement 
membrane and DI because they do have a shelf life. 

STORAGE

1.   It is recommended that you store your RO System in a cool place
        when not being used.
2.   Your RO System must be protected from freezing or   temperatures 
 

 above 100° F (38°C).

Summary of Contents for THE MAXCAP RO/DI System

Page 1: ...ilter Wrench Optional Accessories Model Optional Part FAU SMP Quick Connect Faucet Coupler TK CL 10 Total Chlorine Test Kit VA FVK 4 Flush Valve Kit BPLF MO 115 Low Flow Booster Pump 115V BPLF MO 230...

Page 2: ...for any consequential damages arising from installation or use of the product including any water or mold damage due to flooding which may occur due to malfunction or faulty installation including bu...

Page 3: ...ered purchaser After repair or replacement the factory will return the unit or part freight prepaid to the customer 2 We assume no warranty liability in connection with our equipment other than as her...

Page 4: ...sure greater than 80 psi will require a pressure reducing valve SpectraPure Inc Fax 480 894 6109 Fax us toll free 1 877 527 7873 E mail spectra spectrapure com Visit us on the web www spectrapure com...

Page 5: ...water is passed through a 0 5 micron Micro Tec sediment pre filter This filter is required to remove excess turbidity particulate matter that may cause the carbon block filter to plug 2 The second st...

Page 6: ...ure When the prefilters are new the pressure shown on the gauge will be slightly less than the actual tap water pressure and as the filters age the pressure will drop due to the dirt that will collect...

Page 7: ...vi Acidify feed water to the RO membrane to improve its rejection h Faulty monitor probe Test and Replace if required SpectraPure Inc Fax 480 894 6109 Fax us toll free 1 877 527 7873 E mail spectra s...

Page 8: ...at is located inside of the tubing Do not remove or discard this restrictor the system will not produce permeate water without the flow restrictor All of the following conditions must be met before wa...

Page 9: ...assure you of maximum life and reliability of your SpectraPure System Failure to perform this procedure can permanently damage the membrane and will void the pro rated Membrane Warranty In order to m...

Page 10: ...RO membrane may be calculated and the resultant number may then be used to determine the condition of the membrane and thus the operator will know when the membrane needs to be replaced Membrane failu...

Page 11: ...te the yellow concentrate tubing Fig C Remove the tubing from its push fitting at the membrane as follows a Firmly depress and hold the push fitting collar down with your thumbnail b While the push fi...

Page 12: ...fe the sediment pre filter must be changed when a 15 20 drop in pressure is observed OR at least 6 month intervals If your water contains a great deal of sediment the pre filter may require more frequ...

Reviews: