Spartherm Mini Z1 H2O Installation And Operating Manual Download Page 18

- 35 - 

2.8. Overheat discharge valve 

 

Since the heating for the H

2

O fireplace insert is not automatic and cannot 

be quickly switched off, the hot water attachment must be equipped with 
an overheat discharge valve in accordance with DIN 4751 – Part 2 or DIN 
EN 12828 to prevent hazardous situations in the event of a fault, e.g., a 
power failure. A safety device is installed for this purpose in the H

2

fireplace insert (safety heat exchanger) to protect against overheating. 
This safety device must not be used as a water heater. 
 
The overheat discharge valve supplied (e.g., SYR, type 3065) is tested 
and approved for a minimum water flow rate of 900 kg/h. The sensor on 
the capillary tubing must be inserted and permanently fixed in the 
connection opening of the H

2

O fireplace insert (in the sealed-in immersion 

sleeve) that is marked accordingly. 
 

The following points must always be observed during installation to 
ensure the safety device can work properly: 

  During installation the enclosed installation and operating manual 

supplied by the overheat discharge valve manufacturer must be fol-
lowed! 

  The fittings of the overheat discharge valve may only be installed in 

the feed pipe. This is to ensure that there is no standing water in the 
safety heat exchanger when used as intended. 

  The fittings of the overheat discharge valve must 

not

 be sited in the 

hot area of the heat chamber (convection chamber) of the fireplace 
system (max. ambient temperature 80°C). Select the position on the 
basis of the length of the capillary tubing. 

  A minimum flow pressure of 2.0 bar must be available at the cold 

water intake. This pressure must be maintained at all times. Fluctua-
tions in water system pressure must not occur. This means, for ex-
ample, that supply from a domestic water system that is itself de-
pendent on the mains supply is 

not

 permitted. 

  A minimum water flow rate of approx. 900 kg/h must be ensured. It 

must not be possible to shut off this supply pipe. 

  The heating insert must be aligned so that the front bleed valve is at 

the highest point. 

 
All safety-relevant components must be integrated in the system in such a 
manner that checks may be carried out on their operation and for possible 
leaks at any time. The discharge of the overheat discharge valve must be 
executed in such a manner that a test may be carried out at any time (e.g. 
via an outlet with siphon). 

- 36 - 

2.9. Thermal pump control system 

 

The fireplace insert must always be used with a load unit. A JUMO or 
Afriso thermostat switch is also supplied with the cell. This must be 
electrically integrated into the power supply of the load unit (circulating 
pump).  
The appropriate rolled-up capillary tube should be unrolled and inserted 
into the marked immersion sleeve at the top front right/left and secured 
with the clip supplied. 

Ensure there are no kinks in the capillary tube!

 

This switch ensures that the circulating pump only cuts in if the water 
temperature is adequate and is switched off again if the temperature 
drops below the specified level. The connection is made as shown in 

Fig. 

4a-b

. Control of the circulating pump by means of a boiler control system 

or similar device is not recommended. During installation the enclosed 
installation and operating manual for the thermostat must be followed. The

 

thermostat sensor must be inserted and permanently fixed in the 
connection opening of the H

2

O fireplace insert (sealed immersion sleeve) 

that is marked accordingly. 

 

 
The maximum loading capacity of the thermal pump control system is 
approx. 

500 W

 at 230 V AC.  

The factory setting of the minimum thermostat can be adjusted by means 
of the control dial and has been preset to a range of approx. 62°C to 
approx. 72°C. The start-up temperature of the pump is set on this 
thermostat. Optionally, if conditions so warrant, the setting range can be 
adjusted by the company performing installation. If the control dial is 
removed, the setting range can be varied by moving the locking disc, 
which can be reseated in a different position by removing the screws. In 
the minimum setting (the locking disc is fastened through the holes 
marked “min”), the setting range can be adjusted from approx. 57°C to 
approx. 67°C. 

Please note

: The minimum setting of approx. 57°C may result in values 

below the dew point. The maximum setting (locking disc fastened through 
the holes marked “max.”) ranges from 67°C to 77°C. 
 
The JUMO heatTHERM fittings must 

not

 be sited in the hot area of the 

heat chamber (convection chamber) of the fireplace (max. ambient 
temperature 80°C). Select the position in the cold area on the basis of the 
capillary tubing length! 
 
 
 
 
 

Summary of Contents for Mini Z1 H2O

Page 1: ...on the good name of our firm is inextricably linked to the credo of our owner Gerhard Manfred Rokossa High technical quality combined with modern design and on site customer service carried out to the...

Page 2: ...ncorporation into a heating system 38 2 11 Chimney connection connecting piece 53 2 12 Height limitation door stop 53 3 Initial commissioning 56 4 Operation 57 5 Cleaning and maintenance 59 5 1 Cleani...

Page 3: ...o modifications to the closing device are permitted No additional heat exchangers supplementary heating surfaces etc which 6 extract heat from the flue gas may be incorporated into the connecting pipe...

Page 4: ...O Varia A FDh H 2 O Unit Weight empty without accessories 235 235 245 330 350 380 395 396 kg Nominal output range 4 9 9 1 7 13 7 7 14 3 10 18 7 14 8 27 5 10 3 19 7 3 13 5 7 3 13 5 kW Nominal heat out...

Page 5: ...9 Mini Z1 H2O Fig 1a 10 Mini Z1 H2O XL Fig 1b...

Page 6: ...11 Mini Z1h H2O XL Fig 1c 12 Varia 1V H2O Fig 1d...

Page 7: ...13 Varia 1Vh H2O Fig 1e 14 Varia 1V H2O XL Fig 1f...

Page 8: ...15 Varia 1Vh H2O XL Fig 1g 16 Varia 1V H2O XXL Fig 1h...

Page 9: ...17 Varia 1Vh H2O XXL Fig 1i 18 Varia 2Lh 2Rh H2O Fig 1j...

Page 10: ...19 Varia Ah H2O Fig 1k 20 1 Abgaskuppel 2 separater Verbrennungsluftstutzen 150 mm 3 Luftstellhebel 4 T r klappbar 5 T r hochschiebbar Varia A FDh H2O Fig 1l...

Page 11: ...nstallations must be checked for leaks by means of a pressure test For this purpose the H2O fireplace insert must be aligned horizontally by adjusting the height of the fireplace insert feet or provid...

Page 12: ...any All the work must be carried out according to the VDE Regulations e g VDE 0105 VDE 0116 VDE 0100 etc and the technical connection require ments of the local power supply company 2 3 H2O fireplace...

Page 13: ...ve G feed of overheat discharge valve H rear bleed valve I return J inspection opening Fig 2a 26 Varia 1V H2O Varia 1Vh H2O To facilitate access to the water connections of the Varia 1V H2O an inspect...

Page 14: ...l sensor D bleed valve E return F feed of overheat discharge valve G discharge of overheat discharge valve Fig 2c 28 Varia 2Lh 2Rh H2O For access to the water connections of the Varia 2Lh 2Rh H2O an i...

Page 15: ...connections are clearly marked and must not be used for any other purpose The integral safety device safety heat exchanger must not be used to heat water We recommend the use of straight or angled rad...

Page 16: ...1V H2O Varia 1Vh H2O Varia 1V H2O XL Varia 1Vh H2O XL Varia 1V H2O XXL Varia 1Vh H2O XXL 600 cm 750 cm Varia 2Lh 2Rh H2O 600 cm 750 cm Varia Ah H2O 440 cm 400 cm Varia A FDh H2O 220 cm 200 cm Generall...

Page 17: ...safety device from operating Furthermore all the required safety devices must be integrated throughout the system in such a manner as to ensure non hazardous operation A separate safety valve must sti...

Page 18: ...ks at any time The discharge of the overheat discharge valve must be executed in such a manner that a test may be carried out at any time e g via an outlet with siphon 36 2 9 Thermal pump control syst...

Page 19: ...cted phase L blue wire 2 10 Incorporation into a heating system Please note The H2O fireplace insert may only be installed in a complete system after detailed planning for the entire heating system ac...

Page 20: ...ire storage tank takes just under 2 hours On very cold winter days the fireplace system may be in operation for as much as 12 hours or so The thermal energy produced in such a case is then theoretical...

Page 21: ...for the thermostat switch C feed D safety valve 3 bar E bleed valve F pump thermostat switch e g JUMO heatTHERM G Load unit H load unit fittings e g ESBE type LTC 141 I circulating pump J filling and...

Page 22: ...sor for the thermostat switch D safety valve 3 bar E return F pump thermostat switch eg JUMO heatTHERM G return H load unit fittings e g ESBE type LTC 141 I circulating pump J filling and drain fittin...

Page 23: ...valve B temperature sensor for the thermostat switch C safety valve 3 bar D bleed valve E pump thermostat switch eg JUMO heatTHERM F return G load unit fittings e g ESBE type LTC 141 H circulating pum...

Page 24: ...D return E discharge from overheat discharge valve F supply to overheat discharge valve G safety valve 3bar H bleed valve I pump thermostat switch eg JUMBO heatTHERM J return K load unit fittings e g...

Page 25: ...ermal safety heat exchanger discharge F Thermal safety heat exchanger feed G bleed valve 3 8 H safety valve I bleed valve 3 8 J pump thermostat switch e g JUMO heatTHERM K heating system connection L...

Page 26: ...valve I bleed valve 3 8 J pump thermostat switch e g JUMO heatTHERM K heating system connection L load unit M return N load unit fittings e g Thermoventiler AB type Laddomat 21 O circulating pump P fi...

Page 27: ...ening height is reduced by 50 mm If the opening height is to be further reduced reduction in opening height by 100 mm or increased maximum opening the stops on both sides of the door must be converted...

Page 28: ...and the vermiculite are slowly tempered and the moisture from any storage transport etc slowly evaporated off If this is not done the area between the glass panes may be contaminated and the fireclay...

Page 29: ...s opera tion of the latter When the flue gas temperature is sufficiently high approx 150 C the flue gas valve closes automatically This de flects the flue gas flow through the heat exchanger When the...

Page 30: ...and if our recommendations are followed the cleaning intervals can be significantly extended After the end of the heating season thorough cleaning of all the components is required The heat exchanger...

Page 31: ...nt them in the commission ing log In the event of a claim evidence of the maintenance work carried out must be submitted to the service personnel 62 6 Troubleshooting Note The fireplace must not be us...

Page 32: ...ween the manufacturer Spartherm Feuerungstechnik GmbH and the dealer intermediary They are not the same as the contract and warranty terms and conditions which the dealer intermediary passes on or may...

Page 33: ...ur or other aspects due to thermal stress improper transport and or incorrect storage 66 improper handling of fragile components such as glass and ceramics improper handling and or use lack of mainten...

Page 34: ...em bled Yes No Working pressure checked Yes No System tested for leaks Yes No All safety devices overheat discharge valve safety valve diaphragm expansion vesssel tested Yes No Please enter temperatur...

Reviews: