6
LIGHT LEVEL TEST TABLE
The green LED will blink according to the energy produced by the solar cell
blinks
lux foot candles
time to fully charge
discharge time
0,1
< 15 < 1.4
below operating level
n/a
2
15-50 1.4 - 4.6
min operating level
n/a
3
50-100 4.6 - 9.3
24 hours to full charge
100 hours
4
100-200 9.3 - 18.6
12 hours to full charge
150 hours
5
200-400 18.6 - 37.2
6 hours to full charge
200 hours
The time to fully charge is based on the storage capacitor charging from
a non-operational condition. Discharge time indicates how long a fully
charged sensor will operate in the dark. The test will repeat every 2 sec-
onds and run for a duration of 100 seconds. You may quit the test at any
time by pressing the test button for 6 seconds.
Range Confirmation Test:
provides visual feedback of the sensors signal
strength by a linked receiver with range confirmation capability (only “F
series” controllers have range confirmation ability). One and only one re
-
ceiver can be linked to the sensor for proper operation of the test. (disable
repeaters in range for proper test operation).
1.
To enter Range Confirmation Test mode, press and hold the occupan
-
cy/test button for 6 seconds. The green led will begin to blink.
2.
A quick press and release of the button at this point will allow you to
select between light level test (green LED) and range confirmation test
(amber). When the amber LED is blinking, go to step 3.
(If the 3 LEDs
fail to blink during this test, insert a battery or place under a lamp with
at least 100 fc (1000 lux) for 1 hour before retrying.)
3.
Press and hold the test button again for 6 seconds to select Range
Confirmation Test.
All three LED’s can blink in this test mode when the sensor transmits or
receives a Range Confirmation Telegram. The sensor will display the signal
strength status for 5 seconds, see table below.
RANGE CONFIRMATION TEST TABLE
LED
Signal Strength
Green
> -70 dbm
Amber
> -80 dbm
Red
< -80 dbm
The test will repeat every 10 seconds and run for a duration of 3 min
-
utes. You may quit the test at any time by pressing the occupancy/test
button for 6 seconds.