Spark modern fires 59N Owner'S Operation And Installation Manual Download Page 15

1

5

INSTALLATION

Continued

  WARNING:  Never  connect 

natural gas fireplace to private 

(non-utility)  gas  wells.  This 

gas  is  commonly  known  as 

wellhead gas. 

Installation Items Needed

Before installing fireplace, make sure you have 

the items listed below.
•  external  regulator  for  propane/LP  unit  only 

(supplied by installer)

•  piping (check local codes)
•  sealant (resistant to propane/LP gas)
•  equipment shutoff valve *
•  test gauge connection *
•  sediment trap (optional)
•  tee joint
•  pipe wrench
•  approved flexible gas line with gas connector 

(if allowed by local codes) (not provided)

as shown in Figure 

5

. Pointing the vent down 

protects it from freezing rain or sleet. 

* Purchase  the  optional  CSA  design-certified 

equipment shutoff valve from your dealer.  

** Minimum inlet pressure for purpose of input 

adjustment.

Figure 

 6

 - Gas Connection

Sediment Trap

CSA Design-Certified 
Equipment Shutoff Valve 
With 1/8" NPT Tap*

3" Minimum

Cap     Pipe    Tee

 Nipple   Joint

  CAUTION:  Use  only  new, 

black  iron  or  steel  pipe.  Inter-

nally-tinned copper tubing may 

be used in certain areas. Check 

your  local  codes.  Use  pipe  of 

1/2" diameter or greater to allow 

proper gas volume to fireplace. 

If pipe is too small, undue loss 

of volume will occur.

Installation must include an equipment shutoff 

valve, union and plugged 1/8" NPT tap. Locate 

NPT  tap  within  reach  for  test  gauge  hook  up. 

NPT tap must be upstream from fireplace

.

 

IMPORTANT:

 

Install  equipment  shutoff  valv

 

e

in an accessible location. The equipment shutoff 
valve is for turning on or shutting off the gas to 
the appliance.
Check  your  building  codes  for  any  special  re-
quirements for locating equipment shutoff valve 
to fireplaces

.

Apply  pipe  joint  sealant  lightly  to  male  NPT 

threads. This  will  prevent  excess  sealant  from 

going into pipe. Excess sealant in pipe could result 

in clogged fireplace valves. Never use sealant on 

flare threads. 

Propane/LP 
Supply Tank

External 
Regulator

Figure 

 5

 - External Regulator With Vent 

Pointing Down

Vent 
Pointing 
Down

SHUTOFF VALVE

A CSA design-certified equipment shutoff valve 

with 

1/8" NPT tap is an acceptable alternative to 

test gauge connection. Purchase the optional CSA 

design-certified equipment shutoff valve from your 

dealer. 

For propa

ne/LP units, the installer must supply 

an external regulator. The external regulator will 

reduce incoming gas pressure. You must reduce 

incoming gas pressure to between 11 and 1

3

 inches 

of water. If you do not reduce incoming gas pres-

sure, heater regulator damage could occur. Install 

ex

ternal regulator with the vent pointing down 

Natural Gas

From Gas Meter 
(5" W.C.** to 10.5" 
W.C. Pressure)

Propane/LP

 

From External 
Regulator 
 (11" W.C.** to 1

3

"

     W.C. Pressure)

Summary of Contents for 59N

Page 1: ...This appliance may be installed in an aftermarket permanently located manu factured mobile home where not prohib ited by local codes This appliance is only for use with the type of gas indicated on t...

Page 2: ...liance be kept clean 7 2 217 176 Safety Information 3 Local Codes Specifications 4 Locating Firebox 5 Product Specifications 5 Air For Combustion and Ventilation 6 Installation 8 Framing 10 Operating...

Page 3: ...be present even though no odor exists Make certain you read and understand all warnings Keep this manual for reference It is your guide to safe and proper operation of this heater WARNING Any change...

Page 4: ...er dusty conditions 10 Do not use this replace to cook food or burn paper or other objects SAFETY INFORMATION Continued 11 Do not use fireplace if any part has been exposed to or under water Immediate...

Page 5: ...ombustion and ventilation PRODUCT SPECIFICATIONS RIGHT SIDE VIEW 60 48 28 75 8 15 25 75 28 75 FRONT VIEW TOP VIEW GAS LINE ACCESS BOTH SIDES 25 75 13 75 18 Maximum 10 5 Minimum 5 0 Ignition Electronic...

Page 6: ...gs of unusually tight construction you must provide additional fresh air Unusually tight construction is de ned as construction where a walls and ceilings exposed to the out side atmosphere have a con...

Page 7: ...vent gas appliances Di rect vent draws combustion air from the outdoors and vents to the outdoors Example Gas water heater __________ Btu Hr Vent free replace ________ Btu Hr Total ________ Btu Hr 4...

Page 8: ...ts IMPORTANT Do not provide openings for inlet or outlet air into attic if attic has a thermostat controlled power vent Heated air entering the attic will activate the power vent Figure 2 Ventilation...

Page 9: ...n page 6 IMPORTANT Make sure the replace is level If replace is not level it will not work properly CHECK GAS TYPE Use the correct gas type natural or propane LP for your replace If your gas supply is...

Page 10: ...an external regulator notsupplied Installtheexternal regulator between the replace and propane LP supply VENT FREE FIRE RIBBON FRAMING DIMENSIONS 26 61 E S U N I S B A T G N I N E T S A F 0 625 29 0 5...

Page 11: ...LEAVE MINIMUM 1 2 X 26 SLOT CLEAR FOR THE LOUVER AREA ON BOTH FACES Figure 4 1 Installation of facing materials Case 1 IE DUROCK CEMENT BOARD GRANITE MARBLE STONE OF NON COMBUSTIBLE MATERIAL OPTION 1...

Page 12: ...6 Figure 4 2 Installation of facing materials Case 2 COVER WITH SECOND LAYER OF FACE MATERIAL SECOND LAYER LEAVE THE LOUVER AREA CLEAR WITH FIRST LAYER OF FACE MATERIAL FIRST LAYER SIDE VIEW ALLOW AIR...

Page 13: ...COMBUSTIBLE FACING MATERIAL ALLOWING AIR FLOW FROM BEHIND SURROUND VIEW FROM BACK OF SURROUND NOTCH OUT BACK OF FACE MATERIAL TO ALLOW MINIMUM 13 SQUARE INCHES OF AIR FLOW ALLOW AIRFLOW NON COMBUSTIB...

Page 14: ...7V AC DC adapter which is required to operate Remote Control However during power outage situation its electronic system DFC board can be temporary powered with 9V DC batery and main valve can be oper...

Page 15: ...quipment shutoff valve union and plugged 1 8 NPT tap Locate NPT tap within reach for test gauge hook up NPT tap must be upstream from replace IMPORTANT Install equipment shutoff valve in an accessible...

Page 16: ...equipment shutoff valve to fireplace Route flexible gas supply line through one of the access holes 3 Attach the flexible gas line to gas supply as per Figure 7 Check tightness of flexible gas line a...

Page 17: ...5 Correct all leaks at once 6 Reconnect replace and equipment shutoff valve to gas supply Check reconnected ttings for leaks INSTALLATION Continued Figure 8 Equipment Shutoff Valve Open Closed Equipm...

Page 18: ...ION 1 Locate optional media tray OPTIONAL MEDIA TRAY PLACEMENT 2 Place media tray on the support brackets as shown 3 Fill the tray with media supplied Do not place media on burner or block air flow be...

Page 19: ...applying any power supply to the DFC board please verify that the electrical connections illustrated parts list or mounted in adjacent wall Make sure that the remote receiver switch is in REMOTE midd...

Page 20: ...s into the receiver batter bay Note the polarity of the batteries and insert into the battery bay as indicated on the battery covel 2 Place the 3 posilion slider switch in the REMOTE position 3 Insert...

Page 21: ...the room thermostat is ON and the set temperature is now displayed see Figure 14 2 Adjust the set temperature by pressing the up or down arrow keys until the desired set temperature is displayed on th...

Page 22: ...are low no beep will sound from the receiver when a transmitter command is sent Replace batteries when this happens Transmitter The life span of the transmitter batteries depends upon various factors...

Page 23: ...shows a correct pilot ame pilot ame pattern pattern Figure 18 shows an incorrect Figure 17 Correct Pilot Flame Pattern Figure 18 Inorrect Pilot Flame Pattern If pilot ame pattern is incorrect as show...

Page 24: ...um cleaner in the blow position If using com pressed air in a can please follow the directions on the can If you don t follow directions on the can you could damage the pilot assembly 1 Shut off the u...

Page 25: ...5 Gas regulator setting is not correct 2 Free ignitor cable if pinched by any metal or tubing Keep ignitor cable dry 3 Replace ignitor cable 4 Call for service 5 Replace pilot assembly 6 Replace pilo...

Page 26: ...e Cleaning and Maintenance caused by one or both of page 24 or replace ODSI 3 Flame sensor connection 3 Hand tighten until snug loose at control valve then tighten 1 4 turn more 2 Burner orifice clogg...

Page 27: ...n burner see Cleaning and Maintenance page 24 Moisture condensation no 1 Not enough combustion I Refer to Airfor Combustion ticed on windows ventilation air and Vcntilation require Heater produces a w...

Page 28: ...and Maintenance 1 Foreign matter between 1 Take apart gas tubing and control valve and burner remove foreign matter Fireplace produces a clicking ticking noise just after burners are lit or shut off F...

Page 29: ...NPUT 7 Volt DC STABILIZED SUPPLY OUTPUT MOTOR RECEIVER DC SUPPLY SPLIT FLOW ON OFF TPTH TH DFC SUPPLY DC SUPPLY GROUND 885 PROFLAME Orange Green 11 29 17 18 4 20 19 16 21 This diagram shows replaceabl...

Page 30: ...ILLUSTRATED PARTS BREAKDOWN 1 2 3 4 5 6 7 8 9 10 30 1 9 1 7 2 0 21 4 1 22 11 13 for references see page 31...

Page 31: ...CTOR 1 This list contains replaceable parts used in your rebox All replacement parts should be ordered from your installer or from Spark Modern Fires at 1 8669 383 846 or on line at www sparkfires com...

Page 32: ...reinstallation or transportation of defective parts on the appliance or 3 indentical or consequential damage All service work must be performed by an authorized service representative This warranty i...

Reviews: