Enable and Verify a DIMM
c.
Gently press the DIMM into the slot until the ejector tabs lock the DIMM in
place.
Repeat these steps until each DIMM has been installed.
4.
Return the server to operation.
a.
Install the top cover.
See
“Replace the Top Cover” on page 152
.
b.
Return the server to the normal operating position.
See
“Return the Server to the Normal Operating Position” on page 153
.
c.
Reinstall the power cords to the power supplies and power on the server.
See
“Returning the Server to Operation” on page 149
Related Information
■
“DIMM Configuration” on page 93
■
■
“Enable and Verify a DIMM” on page 100
Enable and Verify a DIMM
1.
Access the Oracle ILOM prompt.
2.
Use the
show faulty
command to determine how to clear the fault.
■
If the output indicates a POST-detected fault, go to
■
If the output displays a UUID, which indicates a host-detected fault, go to
.
3.
Use the
set
command to enable the DIMM that was disabled by POST.
In most cases, replacement of a faulty DIMM is detected when the service processor is power
cycled. In those cases, the fault is automatically cleared from the server. If
show faulty
still
displays the fault, the
set
command will clear it.
->
set /SYS/MB/CMP1/MCU0/CH1/D0 requested_config_state=Enabled
100
SPARC S7-2L Server Service Manual • March 2017
Summary of Contents for S7-2L
Page 1: ...SPARC S7 2L Server Service Manual Part No E73201 04 March 2017...
Page 2: ......
Page 10: ...10 SPARC S7 2L Server Service Manual March 2017...
Page 26: ...26 SPARC S7 2L Server Service Manual March 2017...
Page 44: ...44 SPARC S7 2L Server Service Manual March 2017...
Page 61: ...Remove the Fan Cover Use a T6 Torx screwdriver Preparing for Service 61...
Page 64: ...64 SPARC S7 2L Server Service Manual March 2017...
Page 76: ...76 SPARC S7 2L Server Service Manual March 2017...
Page 86: ...86 SPARC S7 2L Server Service Manual March 2017...
Page 156: ...156 SPARC S7 2L Server Service Manual March 2017...