background image

17

CLAMP BAND

CLAMP 
BAND

RETURN AIR BOX

FLEXIBLE RETURN
DUCT (90° BEND) 

SPACE-PAK FAN

COIL UNIT

48" MIN.

FIGURE 2.23: RETURN AIR DUCT INSTALLATION

AAAAA

AAAAA

AAAAA

AAAA

AAAAA

AAAAA

AAAAA

ROOM 
TERMINATOR

WINTER
SUPPLY
SHUT-OFF

FIGURE 2.24: WINTER SUPPLY SHUT-OFF

AAAAAAAA

AAAAAAAA

AAAAAAAAAAA

AAAAAAAAAAA

AAAAAAAAAAA

AAAAAAAAAA

AAAAAAAAAAA

AAAAAAAAAAA

AAAAAAAAAAA

AAAAAAAAAAA

RETURN AIR
BOX

RETURN AIR
FILTER GRILL

AAAAA

AAAAA

AAAAA

FIGURE 2.22: RETURN AIR BOx INSTALLATION

Winter Supply Shut-Off Installation

Simply  insert  winter  supply  shut-offs  into  the  room 

terminator openings (see Figure 2.24). Wrap the return

air filter in a plastic bag and reinstall it to block the return

air opening. Winter supply shut-offs prevent moisture

from collecting in ductwork during winter months. Be sure

to remove the plastic bag and all winter supply shut-offs

before operating the system.

Return Air Box & Duct Installation

Remove the return air grill from the return air box and

remove the air filter from the return air grill.

Insert the return box from below for ceiling installation 

(or from the front for wall installations) and fasten with

four screws through holes provided on the long side of

the box. (see Figure 2.22).

Then,  insert  return  air  grill  into  box  (see  Figure  2.22) 

and  fasten  with  the  four  screws  provided  through  the

holes on both sides. Open return air grill (turn the 

1

4

turn

latches) and insert filter. Close the return air grill. Slide 

a clamp band (provided with return air box) over one end

of the return air duct. Place that end over the elliptical

flange on the fan coil unit (see Figure 2.23). Move the

clamp over the flange and tighten so the clamp holds the

return air duct securely to the flange.
Follow the same procedures to attach the return air duct

to the return air box (see Figure 2.23).

Step 9: B & C Series Unit Retrofits

For retrofitting an ESP-J series unit to an existing ESP-

B or C series, some modifications will need to be made

to  the  current  system.  The  necessary  changes  are

below and the extent of the changes is dependent upon

the  model  of  the  unit.  (Refer  to  Figures  2.25  /  2.26  /

2.27)

ESP-2430 Retrofits

The 7" duct can still be utilized with a transition kit (Part

No.  BM-6918)  available  from  SpacePak.  This  kit  will

reduce the main plenum from 9" to 7" to adapt to the

existing 7" duct.  

ESP-3642/4860 Retrofits

The existing plenum duct, which is typically 7", will need

to be replaced with 8" X 8" duct board or field supplied

9" round duct. The return duct and return grille will also

have  to  be  replaced  with  the  proper  parts  for  the

replacement model. The reason for this change is the

amount of air supplied by current models is 30% higher

than the B & C Series models. The existing 7" duct work

will  reduce  the  air  flow  and  cause  excessive  static

pressures  resulting  in  lack  of  performance  and  could

possibly  freeze  up  the  coil  which  will  result  in

compressor failure due to short cycling.

NOTICE FOR ALL RETROFITS

It may be necessary to add outlets to the system. The

number of additional outlets will be dependent upon the

external static pressure which should be measured with

a  manometer.  This  measurement  should  be  between

1.2-1.5" WC. For more details on this test procedure and

location for the test, refer to the System Start Up and

Adjustment section in this installation manual.

Summary of Contents for WCSP-2430J

Page 1: ...ies Retrofits 17 19 SECTION 3 START UP OPERATION Sequence Of Operation 19 Prior To Start Up 19 System Start Up Adjustments 19 Operating Setpoints 21 23 Factors Affecting the Balance of the System 24 S...

Page 2: ...ur as a result of overflow from the equipment drain pan or stoppage in the condensate drain piping from a cooling or an evaporator coil AIR DISTRIBUTION SYSTEM COMPONENT REQUIREMENTS Air distribution...

Page 3: ...tains a specified amount of sound attenuating tubes kwik connects terminator plates incl spring clips screws winter supply air shut offs and a balancing orifice set to complete installation of room ou...

Page 4: ...3 not more than 30 of the total number of system outlets should be attached to the perpendicular branch of the tee The larger system capacities WCSP 3642 4860 are affected more by higher system static...

Page 5: ...bration isolation pads a condensate trap assembly and a factory installed primary float switch AA AA ROOM TERMINATOR FIGURE 1 4 TERMINATOR IN SOFFIT AREA AA AAAAA AAA AAA AAAAA AAAAA AAAA SUPPLY TUBIN...

Page 6: ...J WCSP 4860J 2 2 1 2 3 3 1 2 4 5 440 550 3 4 3 4 3 4 5 6 2 8 7 6 4 10 6 5 4 6 6 6 2 4 105 123 144 660 850 880 1150 2 4 2 4 Coil Wheel Dia 115V 230V and Width 10 x 6 10 x 6 10 x 6 Bottom Top FIGURE 2 2...

Page 7: ...5 0 50 0 55 0 60 0 65 0 70 0 75 0 80 0 85 0 90 0 4 0 5 0 6 0 7 0 8 0 9 0 Water Flow Rate GPM Heating Capacity MBH 160 EWT 140 EWT 120 EWT WCSP 3642 850 cfm Heating Capacity 30 0 35 0 40 0 45 0 50 0 55...

Page 8: ...box should fit between successive joists Where joists run in the opposite direction or to properly center the return it may be necessary to cut joists and install headers For all wall return applicat...

Page 9: ...attic A HORIZONTAL DISCHARGE Refer to Figure 2 7 and duct installation instruc tions supplied with fan coil unit 14 5 16 FIGURE 2 6 RETURN AIR BOx FRAME DIMENSIONS Measure return air box dimension A t...

Page 10: ...ides for servicing For installations with a return air box and return air duct set fan coil unit on the platform with the elliptical opening facing in the direction of the return air opening The suppl...

Page 11: ...ndensate line to a closed drain system Step 6 Installing the Condensate Trap Line ITEM 1 2 3 4 5 6 MALE ADAPTER 3 4 DESCRIPTION ELBOW 45 3 4 1 2 PLUG 3 4 X 1 2 BUSHING TEE 3 4 P TRAP 3 4 3 4 P TRAP AS...

Page 12: ...12 FIGURE 2 11 MODEL WCSP J 230V STANDARD WIRING SCHEMATIC For 115V conversion instructions see conversion kit supplied separately with the unit...

Page 13: ...F Heating Water Coil Present Heating Water Coil Settings Switch 2 No Heating Water Coil Present Energized in Cooling Mode Changeover Valve Settings Switch 4 Energized in Heating Mode ON Fan Circulatio...

Page 14: ...S WITH THICKER WALL 3 16 GAP FOR APPLICATIONS WITH THICKER WALLBOARD 3 16 GAP FOR APPLICATIONS WITH THICKER WALLBOARD 3 16 GAP FOR APPLICATIONS WITH THICKER WALLBOARD 3 16 GAP FOR APPLICATIONS WITH TH...

Page 15: ...tube Third thread kwik connect into the inner core until snug Fourth pull the insulation and cover for ward and tuck it into the deep groove on the back side of the kwik connect Fifth wrap the connect...

Page 16: ...19 TAKE OFF INSTALLATION PLENUM FASTENER GASKET PLENUM TAKE OFF GASKET PLENUM TAKE OFF PLENUM FASTENER 1 HAND INSERT FASTENER INTO PLENUM TAKE OFF 2 WITH PLIERS SNAP FASTENER INTO PLACE UNTIL IT LOCKS...

Page 17: ...tical flange on the fan coil unit see Figure 2 23 Move the clamp over the flange and tighten so the clamp holds the return air duct securely to the flange Follow the same procedures to attach the retu...

Page 18: ...HOE LAYOUT Spacepak Air Handler 9 RND 7 RND w 60 or 50 of Total Outlets A B F G A Minimum distance from the air handler outlet to rst tee or elbow is 18 B No outlets in the rst 18 of straight pipe o o...

Page 19: ...if the drain pan is full of water condensate and not draining The fan coil unit will continue to operate when the water level in the drain pan drops the system will continue normal operation PRIOR TO...

Page 20: ...o that the end is approximately flush with the inside wall of the plenum and perpendicular to the direction of airflow 3 System static pressure should be between 1 2 and 1 5 WC a If the pressure is hi...

Page 21: ...5VDC 2 0VDC 1 7VDC 1 4VDC 1 0VDC SystemCurves Nominal operating point 550 CFM at 1 2 ESP 5 0V 4 5V 4 0V 3 5V 3 0V 2 5V 2 0V 1 5V 1 0V 2 2 475 380 2 0 638 547 455 260 1 8 680 640 600 485 370 1 6 830 7...

Page 22: ...t 850 CFM at 1 2 ESP Curves 5 0V 4 5V 4 0V 3 5V 3 0V 2 5V 2 0V 1 5V 1 0V 2 2 520 2 0 730 635 540 460 380 1 8 860 795 730 640 550 410 1 6 970 910 850 800 695 550 360 1 5 1 020 965 910 830 740 610 430 1...

Page 23: ...ingpoint 1 150 CFM at1 2 ESP 5 0V 4 5V 4 0V 3 5V 3 0V 2 5V 2 0V 1 5V 1 0V 2 2 520 2 0 760 728 695 625 1 8 920 885 850 800 630 1 6 1 040 1 005 970 900 760 585 1 5 1 100 1 060 1 020 950 810 650 400 1 4...

Page 24: ...ATION 5 65 85 1 00 1 15 1 30 1 50 1 65 1 70 1 80 1 85 1 95 1 5 1 35 1 15 1 1 5 1 35 2 35 1 35 1 15 or 1 1 5 or 3 5 1 1 35 or 2 5 1 35 2 15 2 35 1 5 1 1 15 3 35 2 00 2 For a room with more than two 2 t...

Page 25: ...th 2 Check fan coil unit Turn off unit power disconnect switch and remove service access panels a Inspect coil and blower wheel for build up of dust and dirt Clean with solvent and or water as necessa...

Page 26: ...of coil WG SpacePak Motor Amps measured Amps Voltage measured Volts Air Temperatures Return indoor ambient FDB FWB Condensing unit outdoor ambient F AHU read 3 ft from fan discharge F last supply outl...

Page 27: ...s W09RWG0422 01 8 Electrical Control Box Cover All Sizes 462RWG0529 J1 9 Side Access Panel Coil Side All Sizes 462RWG0527 01 10 Primary Float Switch All Sizes 455RWG0543 02 11 Cable Connector Ground A...

Page 28: ...o the Manufacturer of that part of the Product thought to be defective Goods can only be returned with prior written approval from the Manufacturer All returns must be freight prepaid b determination...

Reviews: