Space Pak LAHP48 Installation, Operation & Maintenance Manual Download Page 5

– 5 –

Model 

LAHP48

 Air to Water Heat Pump — Installation, Operation & Maintenance Manual

LAHP Controller

The LAHP controller allows the adjustment of heating & cooling setpoints, differentials, and defrosting parameters. 
The following chart depicts the factory default values for the most commonly adjusted parameters.
Certain read only parameters are available to evaluate performance or troubleshoot faults. These are accessed through the same 

parameter menu and are listed below. 

DISPLAY DESCRIPTION

MIN MAX UOM DEFAULT MEANING

PASSWORD

A01 Low Temp Alarm

A07 A04

°F

32.0 Water temperature below which the Low Temp alarm A1 will activate

22

A02 Alarm differential

0.3 122.0

°F

4.0

Alarm A1 turns off at A01 + A02

22

A04 Aux heater setpoint

A01 r16

°F

34.0 Water temperature below which the pump and electric heater, if present, engage.

22

A05 Differential for aux heater

0.3 50.0

°F

4.0

Pump and heater turns off at A04+A05

22

A07 Antifreeze alarm set point limit

-40.0 176.0

°F

32.0 Minimum temperature that A01 can be set to

66

A08 Auxiliary heater set point in heating mode

A01 r15

°F

90.0 Water temperature below which the electric heater, if present, engages in heating mode

22

A09 Auxiliary heater differential in heating mode

0.3 50.0

°F

5.0

Electric heater turns off at A08 + A09 in heating.

22

b00 Default display value

0

10

Flag

0

b00 = 0 Displays return water temperature b00 = 01 displays supply water temperature

22

b01 Probe B1 reading

-

-

°F

-

Read only, real time return water temperature

00

b02 Probe B2 reading

-

-

°F

-

Read only, real time supply water temperature

00

b03 Probe B3 reading

-

-

°F

-

Read only, real time OS coil surface temperature

00

b04 Probe B4 reading

-

-

Bar

-

Read only, real time OS coil refrigerant pressure

00

b08 Probe B8 reading

-

-

°F

-

Read only, real time ambient air temperature

00

c10

Accumulated compressor hours

-

- hrs x 100

-

Value x 100 is the accumulated compressor run time in hours

00

C15 Accumulated pump hours

-

- hrs x 100

-

Value x 100 is the accumulated pump run time in hours

00

d01 Defrost cycle

0

1

Flag

1

Defrost feature enabled

22

d02 Defrost logic

0

2

Flag

2

Start on pressure, end on temperature

22

d03 Start defrosting pressure

0.0 d04

Bar

3.2

Suction pressure below which Defrost initiates (1 bar = 14.5 PSIG)

22

d04 End defrosting temperature

0.0 176.0

°F

45

End defrost temperature, coil surface

22

d06 Min. duration of a defrosting cycle

0

150 Second

60

Minimum defrost duration even if all conditions are satisfied.

22

d07 Max. duration of a defrosting cycle

1

150 Minute

7

Maximum allowable defrost duration. Will display dF1 error code if exceeded

22

d08 Delay between 2 defrost cycles

10 150 Minute

45

Minimum time betgween two successive defrost cycles even if conditions call for it

22

d16 Forced ventilation time at the end of the defrosting

0

360 Second

45

Duration of fan operation at full speed to clear water from coil

66

d17 Defrost with compressors OFF

0 80.0

°F

55.0 Temperature above which defrost occurs with fans only.

66

F02 Fan operating logic

0

2

Flag

02

0 = Fans on full speed whenever unit is on

1 = Fans on when compressor is running

2 = Fans modulating according to F03 through F10

66

F03 Min. voltage threshold for Triac

0

F04

%

10

Establishes low end of fan modulation signal (See Fig 3 & Fig 6)

66

F04 Max. voltage threshold for Triac

F03 100

%

100

Establishes high end of fan modulation signal (See Fig 3 & Fig 6)

66

F05 Pressure value for min. speed Cooling

0.0 42.0

Bar

20.0 Discharge pressure, bar,  below which fans remain on at minimum speed (1 Bar = 14.5 PSIG) (See Fig 3)

22

F06 Pressure differential for max. speed Cooling

0.0 42.0

Bar

6.0

Fans reach max speed at F05 + F06 (See Fig 3)

22

F07 Pressure differential for fan shut-down in Cooling mode 0.0 F5

Bar

2.0

Fans shut down at F05 - F07 (See Fig 3)

22

F08 Pressure value for min speed in Heating mode

0.0 42.0

Bar

10.0 Discharge pressure, bar,  above which fans operate at minimum speed (See Fig 4)

22

F09 Pressure differential for max speed in Heating

0.0 F08

bar

5.5

Fans reach maximum speed at F08 - F09 (See Fig 4)

22

F10 Pressure differential for fan shut-down in Cooling mode 0

F08

Bar

1.0

Fans shut down at F08 + F10 (See Fig 4)

22

F11

Fan starting time

0

120 Second

15

Fans start at maximum speed and remain for this duration before modulating

22

r01

Cooling set point

r13 r14

°F

47.0 Primary cooling setpoint (See Fig 5)

00

r02

Cooling differential

0.3 50.0

°F

8.0

Cooling differential/hysteresis

00

r03

Heating set point

r15 r16

°F

120.0 Primary heating setpoint (See Fig 6)

00

r04

Heating differential

0.3 50.0

°F

8.0

Heating differential/hysteresis

00

r06

Compressor control logic

0

4

Flag

00

00 = Proportional control on return water temperature

02 = Proportional control on supply water temperature

66

r13

Min. Cooling set point

-40.0 r14

°F

42

Minimum allowable cooling setpoint

22

r14

Max. Cooling set point

r13 176.0

°F

65

Maximum allowable cooling setpoint

22

r15

Min. Heating set point

-40 -40.0

°F

80.0 Minimum allowable Heating setpoint

22

r16

Max. Heating set point

r15 176.0

°F

140.0 Maximum allowable Heating setpoint

22

r17

Cooling compensation constant

-5.0 +5.0

°F

0.0

Slope of Outdoor reset curve, Deg water temp/Deg ambient temp. Cooling mode (See Fig 5)

22

r18

Maximum distance from the set point

0.3 20.0

°F

8.0

Maximum deviation from setpoint that can be achieved by outdoor reset (See Fig 5 & Fig 6)

22

r19

Start compensation temperature in cooling mode

-40.0 176.0

°F

85.0 Ambient air temp above which Outdoor Reset is active in Cooling (See Fig 5)

22

r20

Start compensation temperature in heating mode

-40.0 176.0

°F

30.0 Ambient air temp below which Outdoor Reset is active in Heating (See Fig 6)

22

r31

Heating compensation constant

-5.0 +5.0

°F

0

Slope of Outdoor reset curve, Deg water temp/Deg ambient temp. Heating mode (See Fig 6)

22

Summary of Contents for LAHP48

Page 1: ...PIPING 13 SECTION 7 GLYCOL WATER SYSTEM Glycol Water System Design Installation 14 15 SECTION 8 START UP AND TEST Preparing for Start Up 15 BEFORE Starting the Unit 16 Start the SpacePak Low Ambient...

Page 2: ...t capacity under extreme cold conditions and uses that heat energy to increase the compression and therefore usable heat produced by the compressor A generously sized outside coil to absorb heat in he...

Page 3: ...3 Model LAHP48 Air to Water Heat Pump Installation Operation Maintenance Manual Figure 1 LAHP Controller Section 2 LAHP Field Adjustable Parameters...

Page 4: ...main menu Note a The parameters that have been modified without being confirmed using the sel button return to the previous value b If no operations are performed on the keypad for 60 seconds the con...

Page 5: ...osting 0 360 Second 45 Duration of fan operation at full speed to clear water from coil 66 d17 Defrost with compressors OFF 0 80 0 F 55 0 Temperature above which defrost occurs with fans only 66 F02 F...

Page 6: ...Heating F03 F05 OUTSIDE COIL PRESSURE BAR FAN SPEED PERCENTAGE SOLSTICE EXTREME FAN SPEED CONTROL COOLING F04 F06 F07 OFF r01 r19 r17 0 AS SHOWN r18 OUTDOOR AMBIENT TEMPERATURE F WATER TEMPERATURE SP...

Page 7: ...mp sized to provide the minimum ow rates speci ed in this manual Pump selection must consider the pressure loss through the system and its components plus the pressure loss through the LAHP s heat exc...

Page 8: ...min Pressure drop at recommended flow 17 1 ft 7 4 PSI 35 8 kPa Heating current 31A Cooling Current 23 5A Noise level at max fan speed Heating or Cooling 62 dB A Compressor EVI Scroll Installed weight...

Page 9: ...l LAHP48 Cooling Performance 0 0 1 0 2 0 3 0 4 0 24 000 28 000 32 000 36 000 40 000 44 000 48 000 65 70 75 80 85 90 95 100 COOLING CAPACITY BTU hr OUTDOOR AMBIENT TEMPERATURE F 42 44 47 Coefficientof...

Page 10: ...00 40 000 48 000 56 000 64 000 72 000 80 000 10 5 0 5 10 15 20 25 30 35 40 45 50 H H E E A A T T I I N N G G C C A A P P A A C C I I T T Y Y B B T T U U h h r r O OU UT TD DO OO OR R A AM MB BI IE EN...

Page 11: ...11 Model LAHP48 Air to Water Heat Pump Installation Operation Maintenance Manual Figure 9 Model LAHP Dimensions all dimensions in inches Section 4 Dimensions...

Page 12: ...ted where the cables cross with sufficient padding such as multiple layers or corrugated cardboard Use caution when handling The unit is heavy and could cause severe injury or damage if dropped or han...

Page 13: ...Make sure no other equipment located in the space will be affected by the units air flow All clearances must be maintained to ensure free air ow into and out of the enclosure Make sure no other equipm...

Page 14: ...plier Heating 1 34 1 46 1 5 Minimum Expansion Volume System Volume Heating and Cooling 1 gallon expansion per 15 gallons system volume Heating only HP only 1 gallon expansion per 20 gallons system vol...

Page 15: ...re Calculate the system volume 2 See Figure 13 for required glycol concentration for the mini mum expected outside temperature 3 Obtain the required volume inhibited glycol water solution premixed or...

Page 16: ...efrigeration system will initiate and the numeral 1 will begin ashing on display 7 After 1 to 2 minutes the 1 numeral will change to constant the compressor symbol will turn on and the compressor will...

Page 17: ...17 Model LAHP48 Air to Water Heat Pump Installation Operation Maintenance Manual Figure 15 SpacePak LAHP Pictorial Wiring Diagram Section 9 Electrical Diagrams...

Page 18: ...18 Model LAHP48 Air to Water Heat Pump Installation Operation Maintenance Manual Figure 16 SpacePak LAHP Electrical Ladder Diagram Section 9 Electrical Diagrams continued...

Page 19: ...19 Model LAHP48 Air to Water Heat Pump Installation Operation Maintenance Manual Figure 17 Field Connections Section 9 Electrical Diagrams continued...

Page 20: ...20 Model LAHP48 Air to Water Heat Pump Installation Operation Maintenance Manual Figure 18 Wiring Diagram Section 9 Electrical Diagrams continued...

Page 21: ...Stop E3 OS coil temp sensor fail Automatic None None None None E4 Refrigerant pressure sensor fail Automatic Stop None Stop None E8 Ambient temp sensor fail Automatic None None None None ESP Lost com...

Page 22: ...cooling operation i e 55 F If low ambient cooling is desired contact Technical Support for procedure to modify fan operating parameters Compressor will not run Power supply failure Supply correct pow...

Page 23: ...aks immediately Close the isolation valves on either side of the y strainer at the SpacePak heat pump return connection Remove the screen and inspect for sediment Clean if necessary NOTE If the strain...

Page 24: ...0 430048 Fan Speed Controller 17 45R2000 3202 Sensor 5k 18 45R20000 120100 Plate Heat Exchanger EVI 19 45R20000 140027 Filter 20 45R20000 140194 EVI Solenoid Valve 21 45R20000 140234 Electronic Expans...

Page 25: ...or parts thereof c To any workmanship of the installer of the Product This limited warranty is conditional upon a Shipment to the Manufacturer of that part of the Product thought to be defective Goods...