– 21 –
Model
LAHP48
Air to Water Heat Pump — Installation, Operation & Maintenance Manual
Section 10: Fault Codes
Figure 19
Fault Codes
Alarm
Display
Alarm type
Reset Logic
Compressor
Response
Pump
Response
Fans
Response
Heater
Response
A1
Freeze error
Automatic
Stop
None
Stop
Enable
Aht
High water temp at startup
Automatic
Stop
None
Stop
None
dF1
Defrost error, cycle time exceeded
Automatic
None
None
None
None
E1
Return water temp sensor fail
Automatic
Stop
None
Stop
Stop
E2
Supply water temp sensor fail
Automatic
Stop
None
Stop
Stop
E3
OS coil temp sensor fail
Automatic
None
None
None
None
E4
Refrigerant pressure sensor fail
Automatic
Stop
None
Stop
None
E8
Ambient temp sensor fail
Automatic
None
None
None
None
ESP
Lost com. with expansion module
Automatic
Stop
Stop
Stop
Stop
FL
Water system low flow
Automatic
Stop
Stop
Stop
Stop
Hc1
Service hours notification
Automatic
None
None
None
None
HP1
Refrigerant High Pressure fault
Auto x3, then Manual
Stop
None
Run 60 sec
None
Ht
High water temp
Automatic
None
None
None
None
LHt
Low Water temp at startup
Automatic
Stop
None
Stop
None
LP1
Refrigerant Low Pressure fault
Auto x3, then Manual
Stop
None
Run 60 sec
None
tC1
Compressor over current or delivered water too cold
Automatic
Stop
Stop
Stop
Stop