SIM Inverter Monobloc Air-to-Water Heat Pump
SIM Error Codes
Error Code Description
Cause
Solution
---
Heat pump will not start when called
upon for Heating, Cooling or DHW
Various errors will not immediately appear
on Home Screen until multiple re-start
attempts have been exhausted.
Refer to Section 5 to navigate to Fault Log.
Check for faults and identify below.
P01
Inlet Water Temp Sensor
Sensor failed open or shorted. Wiring fault Correct wiring or replace 5k sensor T1
P02
Outlet Water Temp Sensor
Sensor failed open or shorted. Wiring fault Correct wiring or replace 5k sensor T2
P04
Ambient Air Temp Sensor
Sensor failed open or shorted. Wiring fault Correct wiring or replace 5k sensor T6
P07
Suction Line Temp Sensor
Sensor failed open or shorted. Wiring fault Correct wiring or replace 5k sensor T4
P08
Discharge Line Temp Sensor
Sensor failed open or shorted. Wiring fault Correct wiring or replace 50k sensor T3
PP1
Discharge Pressure Sensor Fault
Sensor failed open or shorted. Wiring fault Correct wiring or replace pressure sensor X1
PP2
Suction Pressure Sensor Fault
Sensor failed open or shorted. Wiring fault Correct wiring or replace pressure sensor X2
E01
High Pressure Dischare Pressure
Excessive refrigerant discharge pressue.
If in Heating, high water temperature
or insufficient water flow. If in Cooling,
restricted airlow, dirty coil or high ambient
temperature.
Correct water or air flow, clean coil or lower
water temperature.
E02
Low Pressure Dischare Pressure
Excessive refrigerant discharge pressue.
If in Cooling, insufficient water flow. If in
Heatinging, restricted airlow or dirty coil.
Correct water or air flow, clean coil or lower
water temperature.
E03
Flow error
Undersized pump, excessive plumbing
restriction, pump not receiving signal
Ensure pump is adequate to maintain
specified flow at actual head loss, check
wiring to confirm voltage is supplied to pump
when called for by the heat pump.
E07
Antifreeze Protection
Insufficient water flow in Cooling
Verify Pump as flow error above
E08
Communication fault with Compressor
Inveter Board
Check internal RS485 wiring between
control board and Inverter Board
Correct wiring or check fault codes indicating
faulty Inverter Board
E19
Primary Freeze Protection
Inlet Water Temperature between 32° and
36°F and Ambient T is below 32°F
Check water temperature. If it is over 36°F,
check or replace 5k sensors T6 or T7
E29
Secondary Freeze Protection
Inlet Water Temperature below 32° and
Ambient T is below 32°F
Check water temperature. If it is over 36°F,
check or replace 5k sensors T6 or T7
P181
Refrigerant discharge temperature
exceeds 239°F
Excessive suction superheat due to
refrigerant undercharge.
Determine loss of refrigerant, evacuate and
recharge system by weight on Data Label
E21
Power supply undervoltage
Input power falls below 220V under load
Ensure power supply is adequate to supply
220-240V under maximum load.
E22
Input overcurrent
High amp draw due to high compressor
load or low voltage
Address discharge pressure per PP2 above,
or check input voltage.
Summary of Contents for CSOLSTICE SIM-036
Page 51: ...51 SIM Inverter Monobloc Air to Water Heat Pump SECTION 8 REPLACEMENT PARTS SIM036...
Page 52: ...52 SIM Inverter Monobloc Air to Water Heat Pump Replacement Parts SIM036...
Page 53: ...53 SIM Inverter Monobloc Air to Water Heat Pump Replacement Parts SIM060...
Page 54: ...54 SIM Inverter Monobloc Air to Water Heat Pump Replacement Parts SIM060...
Page 59: ...59 SIM Inverter Monobloc Air to Water Heat Pump...