Soyal AR-888H Manual Download Page 7

V221012

- 7 -

   

Flush-Mounted Series

Flush-Mount Backlight Multi-Function Controller / Flush Mount Illuminated Access Reader 

[e.g.] The anti-pass-back function of User Address 00154 has been enabled. After presenting the card to get in, the user doesn’t present the card to 

leave. When s/he tries to present the card to get in again, since the in-in sequence violates the anti-pass-back rule, s/he will be rejected. To solve this 

problem, you can reset it as follows. Enter program mode

 → 

26     00154     00154     2     

 → 

Reset

[e.g.] Enable the anti-pass-back function of User Address from 00152 to 00684:

 

26     00152     00684     0

Enable card

Enter program mode

 → 

26     SSSSS     EEEEE     N      

[SSSSS= Starting User Address; EEEEE= Ending User Address; N=0(control)/ 1(Not control)/ 2(reset)]

Enable controller

Enter program mode

 → 

20     DDD       [128= Anti-pass-back(0=Disable; 1=Enable)/ 064=Entrance/Exit(0=Exit; 1=Entrance).]

         Enter program mode

 → 

20     128      (Please refer to function default value for details.)

[e.g.] Enable Anti-pass-back, and set to Exit door= (128 x 1) + (064 x 0) = 128

Usually, anti-pass-back is commonly applied to parking areas in order to prevent from multi-entry with one card at a time, or to locations that 

need entry and exit control.

F. Anti-pass-back (M4/M8)

M4/M8: Private PIN

Card or PIN:

 

Enter program mode

 → 

12     UUUUU     PPPP       [e.g. User Address: 00001 and pass code: 1234, input 12     00001     1234     ]

Card and PIN:

 

Enter program mode

 → 

13     UUUUU     PPPP       [e.g. User Address: 00001 and pass code: 1234, input 13     00001     1234     ]

M6: Public PIN
Card or PIN:

 

Enter program mode

 → 

15     PPPP       [Input 4-digit PIN, default value: 4321; PPPP=0000: cancel the function of simply inputting PIN to get access]

Card and PIN:

 

Enter program mode

 → 

17     PPPP       [Input 4-digit PIN, default value: 1234; PPPP=0000: access mode will be "Card Only"]

D. Set up the password

Enter program mode

 → 

28     064       [064= Double Door Control]

Controller with a reader to perform the "Double Door Control".

E. Double Door Control (M4/M8)

Operation process

Enable/Disable auto-open time zone

Enter program mode

 → 

20     004       [004= enable Auto-Open Time Zone; 000= disable Auto-Open Time Zone]

Enable/Disable auto open door without presenting one valid card

Enter program mode

 → 

24     001       [001=enable auto-open door without presenting one valid card

000=disable auto-open door without presenting 

one valid card]

N: 2 sets of auto-open zone (N=0=1st set; N=1=2nd set)
HHMMhhmm=Staring time to ending time (e.g. 08301200=08:30 to 12:00)
7123456H= 7 days of a week (Sun/Mon/Tue/Wed/Thu/Fri/Sat) + Holiday (H= 0: disable; 1: enable);  Holidays can be set via 701Client software.

Set up auto-open time zone

Enter program mode

 → 

08     N     HHMMhhmm     7123456H

[e.g.] To set the second time zone as 9:30 AM to 4:20 PM, Monday, Wednesday and Friday: 08     1     09301620     01010100      

 → 

Done

Door will remain open after flashing one valid card. There are 2 time zones supported when Standalone, and 63 time zones when connected to AR-716-E.

Please refer to paragraph 

Function Default Value

 below to ensure command 20      DDD       /   24     DDD      will not reset the functions that already had 

been changed.

G. Auto-Open Time Zone

Summary of Contents for AR-888H

Page 1: ...e Application Pin Color Description 3 PIN Connector 1 Black GND 2 White Duress 3 Purple Arming Security trigger signal 888 K U 125kHz 13 56MHz Cable CN5 Cable CN4 Wire Application Pin Color 888 H Desc...

Page 2: ...ttach C to B at lower position of B Push C up to make the cogging hooked completely Use the Allen key and screws to assemble the body C onto the mounting plate B Attach the Back Cover D to C Hands off...

Page 3: ...CN1 CN1 CN1 CN5 P T Exit Flush Mounted Series Flush Mount Backlight Multi Function Controller Flush Mount Illuminated Access Reader Request To Exit Request To Exit Request To Exit Electric Bolt AR 12...

Page 4: ...s to 1 3 5 7 floor 21 00001 0 01010101 POWER DC12 24V POWER DC12 24V POWER AC18V AR 821RB AR 821RB Controller Traditional Electronic Door Lock Traditional Electronic Door Lock Controller Controller po...

Page 5: ...ng 17 command to set Arming PWD as 0000 2 Card and PIN 4 digitpublicPIN ArmingPWD 3 Card or PIN 4 digitpublicPIN Duresscode 1 Card only 2 Card and PIN 4 digitPrivatePIN 3 Card or PIN 4 digit Private P...

Page 6: ...g Add User Address 00100 Enter program mode 11 00100 00100 OK e g Add a batch of user with sequential Card Number of user address 12058 until 12559 total 50 tags Enter program mode 11 012058 012599 OK...

Page 7: ...01 and pass code 1234 input 13 00001 1234 M6 Public PIN Card or PIN Enter program mode 15 PPPP Input 4 digit PIN default value 4321 PPPP 0000 cancel the function of simply inputting PIN to get access...

Page 8: ...g door is forced openg door is forced openg In the security management of access control system the controller or reader status is divided into Standby Mode or Disarming Mode and Arming Mode The condi...

Page 9: ...s of egress button RTE Reserved Keep beeing while arming is enabled Door relay connected to AR 721RB suited to models without relay built in Arm relay connected to AR 721RB suited to models with relay...

Page 10: ...d code UUUUU User Address QQQQQ Card quantity 00001 for adding a single card or a batch of random numbering cards N 0 Delete tag N 1 Add tag After enabling Door Open For Any Tag all cards in same freq...

Page 11: ...s function ex AR 725 H UUUUU User Address S 4 sets of lift control 0 3 FFFFFFFF 8 assigned floor F 0 Disable 1 Enable NNN site number TTT relay time 000 600 1 600 sec UUUUU User Address FF Floor 01 32...