9
C.2 Electrical
connection
Installation
Danger
Before working on the unit, switch off the power supply and secure
it against being switched on again! Check for the absence of power!
Electrical connections may only be made by a specialist and in
compliance with the applicable regulations.
Do not use the controller if the housing shows visible damage.
Caution
Low-voltage cables such as temperature sensor cables must be routed
separately from mains voltage cables. Feed temperature sensor cables
only into the left-hand side of the unit, and mains voltage cables only
into the right-hand side.
Caution
The customer must provide an all-pole disconnecting device, e.g. a
heating emergency switch.
Caution
The cables being connected to the unit must not be stripped by more
than 55mm, and the cable jacket must reach into the housing just to the
other side of the strain relief.
With hydraulic variant D1 „Solar+storage“ relays R1 and R2 are
switched on simultaneously to allow the connection of another load at
R2.
Caution