Room Controller
This value is used to appoint the amount of influence the room temperature has on the reference flow temperature, as a per-
centage. For each degree deviation between room temperature and set point temperature, the percentage set here is added
from the calculated set flow temperature to the set flow temperature or subtracted from it until the min. or max flow values.
Example: Reference room temp.: e.g. 25 °C; room temp.: e.g. 20 °C ±5 °C. Calculated reference temp.: e.g. 40 °C: room con-
troller: 10 %= 4 °C 5 X 4 °C= 20 °C. Accordingly, 20 °C are added to the reference flow temperature, giving 60 °C. If the value is
higher than the one set in max. flow temp, the resulting temperature is the one set in max. flow temp.
Room Reference (Day)
The desired room temperature for day mode. As long as this temperature is not reached, the reference flow temperature is
raised and/or lowered according to the percent setting in ‚room controller‘. If ‚room controller‘ is set to 0 %, this function is deac-
tivated.
Room Reference (Night)
The desired room temperature for night mode. As long as this temperature is not reached, the reference flow temperature is
raised and/or lowered according to the percent setting in ‚room controller‘. If ‚room controller‘ is set to 0 %, this function is deac-
tivated.
In the modes ‚Set point‘ and ‚Set point program, the room controller has no influence.
Thermostat (X)
The room controller is selected here. If no room controller is connected and a room controller is connected via the CAN Bus,
another room controller can be selected here.
The CAN bus ID of a controller is shown in the respective controller menu under 7.7.4. special functions - network. In °CALEON
see the CAN Bus ID in the expert menu under Network. Choose the Room Controller with the CAN Bus ID of the corresponding
controller.
Eco Display Mode
In Eco Display Mode the backlight of the display is switched off if no buttons are pushed for 2 minutes.
If a message exists, the backlight does not switch off until the message has been scanned by the user.
Network
If applicable, the network settings of the connected data logger have to be adjusted
Access Control
This menu lets you give up to 4 users access to the data logger. The users that are registered then have access to the controller
or respectively the data logger.
To add a user in the list, select <add user>. Leave the now visible menu open und connect to the address of the connector or
respectively the data logger. Your user name is going to appear in this menu and can be selected and confirmed with ‘OK’.
Note
You can find the address of the connector or respectively the data logger on the address sticker on the outside of the casing.
Pointers and help on how to establish a connection you can find in the enclosed SOREL connect instructions or the instructions
of the data logger.
Select a user with ‘OK’ to grant access.
To revoke access again, choose one of the users from your list and choose <remove user>.
Ethernet
The data logger‘s Ethernet connection settings can be set using this menu.
MAC Address
Displays the individual MAC address of the data logger.
Auto-Configuration (DHCP)
If auto-configuration is activated, the data logger requests IP addresses and network parameters from a DHCP server that
assigns an IP address, subnet mask, gateway IP and DNS server IP.
If you deactivate the auto configuration (DCHP), you will
have to make the required network settings manually!
IP-Address
Please refer to the router configuration for the IP address to be set.
Subnetz
Please refer to the router configuration for the subnetz to be set.
20