Installing the Temperature Sensors
The controller operates with Pt1000 temperature sensors which are accurate to 1 °C, ensuring optimal control of system func-
tions.
If desired, the sensor cables can be extended to a maximum of 30 m using a cable with a cross-section of at least
0.75 mm². Ensure there is no contact resistance! Position the sensor precisely in the area to be measured! Only use
immersion, pipe-mounted or flat-mounted sensors suitable for the specific area of application with the appropriate
permissible temperature range.
Low-voltage cables such as temperature sensor cables must be routed separately from mains voltage cables. Feed
temperature sensor cables only into the left-hand side of the unit, and mains voltage cables only into the right-hand
side.
Temperature Resistance Table for Pt1000 Sensors
°C
-20
-10
0
10
20
30
40
50
60
70
80
90
100
Ω
922
961
1000
1039
1077
1116
1155
1194
1232
1270
1308
1347
1385