20
5.4. - Circulation
Mode of circulation
Set the mode of circulation in this menu.
In mode
“Off”
a circulation pump is not part of the design (see 2.5 Fig.1).
When the mode
“Request”
is active, the circulation pump is switched on after a correspond-
ing withdrawal of water has occured (see 5.5 to 5.8 for instructions to the necessary settings).
In mode “
Periods
” the circulation pump is enabled in the set periods (see 5.5 to 5.9 for instruc-
tions to the necessary settings)
Settings range: Off, Request, Periods / Default: Request
When mode “Periods” or “Request” is active, additional menu items are available in
the “Settings” menu.
Caution
Settings
5.5. - Circ. purging time
Operating time of the circulation pump
The circulation pump is switched off after this period of time even if the set temperature is not
reached at sensor 2. This is to prevent the pump from unnecessary running, e.g. when the
storage buffer is too cold.
Settings range: 1 Min. to 20 Min. / Default: 2 Min.
5.6. - Circ. pause time
Circulation pump pause time
To prevent the pump from frequently switching on and off, this sets the minimum time the pump
is not switched on again after being switched off.
Settings range: 1 Min. to 20 Min. / Default: 15 Min.