Form 169 (07.21) ©SOR Inc.
1/12
This instruction provides information for mounting, electrical
connection, process connection, and calibration of SOR
®
Temperature Switches.
The SOR Temperature Switch consists of a pressure switch
with a sealed temperature sensing bulb attached directly to the
pressure port. (An optional remote temperature sensing bulb may
be connected to the pressure port with an armor-clad capillary.) The
temperature sensing system is pressure filled with a volatile fluid.
Process temperature changes cause proportional vapor pressure
changes in the temperature sensing bulb that act on the diaphragm/
piston assembly to actuate and deactuate a snap-action electrical
switching element at discrete process temperatures. The
instrument’s
behavior is
determined by vapor pressure
(105 range model fill media is inert gas).
NOTE: If you suspect that a product
is defective, contact the factory
or the SOR Representative
in your area for a return
authorization number (RMA).
This product should only be
installed by trained and
competent personnel.
ent at discrete process temperatures. The
vapor pressure
del fill media is inert gas).
spect that a product
ntact the factory
resentative
a return
umber (RMA).
ould only be
ned and
onnel.
Design and
specifications are
subject to change
without notice.
For latest revision, go to
SORInc.com
Table of Contents
Installation .......................................2
SIL Installation ..................................3
Process Connection ............................3
Electrical Connection ...........................4
Calibration .......................................5
Special Conditions ..............................5
Probe Dimensions ..............................6
ATEX/IECEx Marking Information .............8
Declaration of Conformity ................... 10
Temperature
Switches
Registered Quality System to ISO 9001
General Instructions