Form 169 (07.21) ©SOR Inc. 

1/12

This instruction provides information for mounting, electrical 
connection, process connection, and calibration of SOR

®

 

Temperature Switches.

The SOR Temperature Switch consists of a pressure switch 
with a sealed temperature sensing bulb attached directly to the 
pressure port. (An optional remote temperature sensing bulb may 
be connected to the pressure port with an armor-clad capillary.) The 
temperature sensing system is pressure filled with a volatile fluid. 
Process temperature changes cause proportional vapor pressure 
changes in the temperature sensing bulb that act on the diaphragm/
piston assembly to actuate and deactuate a snap-action electrical 
switching element at discrete process temperatures. The 
instrument’s 
behavior is 
determined by vapor pressure 
(105 range model fill media is inert gas).

NOTE: If you suspect that a product 
is defective, contact the factory 
or the SOR Representative 
in your area for a return 
authorization number (RMA). 
This product should only be 
installed by trained and 
competent personnel.

ent at discrete process temperatures. The 

vapor pressure 

del fill media is inert gas).

spect that a product 

ntact the factory 

resentative 

a return 

umber (RMA). 

ould only be 

ned and 

onnel.

Design and 

specifications are 

subject to change 

without notice. 

For latest revision, go to 

SORInc.com

Table of Contents

Installation .......................................2
SIL Installation ..................................3 
Process Connection ............................3
Electrical Connection ...........................4
Calibration .......................................5
Special Conditions ..............................5
Probe Dimensions ..............................6
ATEX/IECEx Marking Information .............8
Declaration of Conformity ................... 10

Temperature 

Switches

Registered Quality System to ISO 9001

General Instructions

Summary of Contents for GI169

Page 1: ...ocess temperatures The instrument s behavior is determined by vapor pressure 105 range model fill media is inert gas NOTE If you suspect that a product is defective contact the factory or the SOR Repr...

Page 2: ...6 35 mm bolts o Mounting by electrical conduit connection is NOT recommended p Suggested mounting orientation is electrical conduit connection at 3 or 9 o clock and sensing body at 6 o clock However t...

Page 3: ...A thermowell filled with thermal transfer media reduces lag Safety Integrity Level SIL Installation Requirements The SOR pressure switches have been evaluated as Type A safety related hardware To meet...

Page 4: ...movement or replacement in the field will degrade performance and could render the device inoperative unless factory authorized procedures are followed Housing Type Conduit Connection Contact Termina...

Page 5: ...Use 3 4 inch open end wrench to turn hex adjusting nut clockwise in to increase set point and counterclockwise out to decrease set point Approximate set point can be obtained by sighting across top of...

Page 6: ...r all Others 263 4 Max 10 37 308 3 12 06 Approximate Range of Adjustment Remote Mount Probe Dimensions Linear mm inches Drawings are for reference only Contact the factory for certified drawings for a...

Page 7: ...25 mm 107 2 112 0 112 0 112 0 112 0 in 4 22 4 41 4 41 4 41 4 41 C 235 125 115 mm 128 3 135 to 396 147 to 409 185 to 447 216 to 480 in 5 05 5 3 to 15 6 5 8 to 16 1 7 3 to 17 6 8 5 to 18 9 105 mm 170 to...

Page 8: ...f clause 6 3 12 EN 60079 11 2007 The unit is capable of withstanding a 500 Vrms isolation test between circuit and enclosure ATEX IECEx Marking Information For Mini Hermet ATEX IEXEx Certified Models...

Page 9: ...for use in Potentially Explosive Atmospheres EN 60079 0 2012 A11 2013 IEC 60079 0 2011 EN 60079 1 2014 IEC 60079 1 2014 06 II 2 G Ex db IIC T6 T5 Gb T6 40 C Ta 60 C T5 40 C Ta 75 C EC Type Examination...

Page 10: ...amination Certi cate Baseefa11ATEX0125 Issued February 16 2012 IECEx BAS 15 0150 Issued April 19 2016 SGS Fimko Oy Noti ed Body No 0598 Takomotie 8 Helsinki 00380 Finland Michael J Bequette VP of Engi...

Page 11: ...Form 169 07 21 SOR Inc 11 12...

Page 12: ...12 12 Form 169 07 21 SOR Inc 14685 W 105th St Lenexa KS 66215 913 888 2630 800 676 6794 USA SORInc Registered Quality System to ISO 9001...

Reviews: