Energy Storage System “IJ1001SNBT”
54
Set the connecting box and conduit
Remarks
The field-wiring terminals shall be connected using the following wire types:
AC connections:
18 in./lbs. - 22 in./lbs. tightening torque
#10 AWG - #14 AWG
wire type – rated 90C
Copper
Equipment Electrode Terminal:
75 in./lbs. – 88 in./lbs. tightening torque
#8 AWG - #10 AWG
wire type – rated 90C
Copper
Limits of accuracy of frequency measurement (+ 0.1 Hz)
Limits of accuracy of Voltage measurement (+ 6 V)
For conduit hubs, use only UL Listed rain tight for entry into the enclosure.
AC output / neutral is not bonded to ground.
The AC input and AC output circuits are isolated from the enclosure and that system grounding,
if required by Section 250 of the National Electrical Code, ANSI/NFPA 70, is the responsibility of the installer.
The National Electrical Code, ANSI/NFPA 70 wiring methods are to be used.
use if needed
The following pressure terminal connectors / component terminal assemblies are allowed / provided for
field installation with this unit.
Manufacturer : OSADA Co., Ltd (E121961)
Model #Type : OK-147-3P Acceptable wire gauges : 16-10 AWG