25
Instruction for use | Supercal 739
Qn
Threaded
connection
*EAS
Mounting
length
*EAS
Mat
PN
Maximal
flow
qs
Minimal
flow
qi
Low flow
threshold
value
(50°C)
Threaded
hole for
sensor
Total
Meter
Weight
Kvs value
(20°C)
Pressure
loss at
qp
m
3
/h
G''
DN
mm
bar
m
3
/h
l/h
l/h
Kg
m
3
/h
bar
(
EN
ISO
228-1)
0.6
3/4 ''
(15)
110
Brass
16
1.2
12
8
yes
0.6
1.7
0.08
1.5
3/4''
(15)
110
Brass
16
3.0
15
10
yes
0.6
3.4
0.19
1.5
1''
(20)
130
Brass
16
3.0
15
10
yes
0.6
3.4
0.19
2.5
1''
(20)
130
Brass
16
5.0
25
17
yes
0.7
5.9
0.18
13.2 Coaxial multi jet meter with G2'' connection
*EAS = base 16 bar = 1.6 MPa
Mounting
The Supercal 739 should not be mounted on the side where the continuous operating temperature of
the liquid exceeds 90°C or is below 5°C.
Length of straight section fitted upstream/downstream of each flow meter (EN1434): U0 / D0 for:
L=110mm and L=130mm
qp
1.
5
qp
0.
6
qp
2.
5
0.01
0.1
1
0.1
1
10
100
Pr
essu
re
lo
ss
[b
ar
] =
=>
Flow [m3/h] ==>
Pressure loss
Sontex Supercal 739
log-log
Pressure loss curve