TELKAN 4 GSM 3G
Telephonic Control Via GSM Code:19.095
Manual of installation and use
DESCRIPTION
LED´s
SIM card
Input for external battery
External input for a sealed lead battery of 12V and a
capacity of 1.2 to 20Ah.
Input for temperature probes
r1, r2, r3, r4
(Relays)
External antenna connector
Connection for external antenna with magnetic base
Contact closure alarms
When open / close contact for more than 5 seconds generates an alarm
a1, a2, a3
(Alarms)
t1, t2, t3
(Probes)
b1
(Battery)
PWR
(Power supply)
GSM
(Signal)
SIM
(Card)
Input for transducer 4a20mA
Has the same procedure that input for probes.
on
Z
in value alarm
off
Z
without value alarm
blinking
Z
Connection error
c1
(Input 4a20mA)
Before giving the power to the control, remove the SIM card PIN and insert it into the TELKAN
START UP
3
3
1
1
- Wiring type: H05VV-F or H05RR-F
- Environment: Temperature
Z
0°C to 45°C / Humidity
Z
20% to 85%
- Software classe A - Action type 1.B
- Free-voltage contact relay
- Independent dispositive
- According normative:
EN 60730 / EN 301511 / EN 301489-1 / EN 301489-7
- Power supply: 230V~ +10% -15% 50/60Hz max. 2VA
- Measures: Rail-DIN box 6 modules (90x105x58 mm)
2
2
- Minimum section for cable of: Relay
Z
2,5 mm Power supply
Z
1 mm
- Contamination degree: clean environment
TECHNICAL SPECIFICATIONS
Electrical drawing:
4
4
BAT
PWR GSM
SIM
BAT
PWR GSM
SIM
BAT
PWR GSM
SIM
5
5
IP20
If the installation was successful should light the LEDs:
PWR
,
SIM
and
GSM
Buttons ON / OFF
Connect /disconnect the relays manually without sending message.
Application
(relays
r2, r3
)
5A 250V~ SPST.
Relays with free voltage-contact (operation as a
switch)
T3
+
-
Battery
B1
5A
R3
C
NO
C
NO
NO
NO
R1
NC
C
L
230V~
N
SIM
ANTENNA
+
-
4a20mA
L
N
Contact Alarms
Temperature Probes PTC2000
C1
T1
T2
A1
A2
R2
NC
C
230V~
16A
16A
1 Input for external battery
: When detecting a change of power (battery passes network or vice versa) sends
SMS warning of network failure and SMS of service restoration. (Battery not supplied, code: 7.190)
SIM:
Works with prepaid card or contract of any company, it is recommended the prepaid for save money. Before
purchasing the SIM, verify what company has the better coverage in the area. (SIM not included)
4 Relays (2x5A + 2x12A):
: You can activate/deactivate manually or by SMS, activate /deactivate timed and query
the status of the relay.
3 Inputs for T Probes
: Allows receive warnings of a temperature alarm, the relay can be linked to temperature
alarm and view the history of temperatures for the last 4 hours via SMS. (Probes not supplied, code: 4.343)
1 Input for 4a20mA:
Has the same procedure that input for probes.
1 Alarms contact
: When open / close contact for more than 5 seconds will generate an alarm.
IP65 Box
: Box for surface mounting. (Box not supplied, code: 7.118)
Remote control via GSM that works by sending and receiving SMS (configurable in 2 languages, Spanish /
English). Ability to operate powered 12V ideal photovoltaic installations.
Connection for temperature probe PTC2000 (-40°C ... + 140°C).
When the probe detects that the temperature has crossed the
threshold defined by the user, the controller sends an SMS alarm
only to phone No function has been activated. (F. MEET, can
activate the desired relay).
Cardholder to insert a Mini-SIM that is operational and any
company. Does not work with Mini-SIM card or the phone number
doubled.
Do not insert or remove the SIM card with the Sondertel
powered.
2 - Check with a mobile phone the SIM (which has no access PIN code, the credit,
sending and receiving SMS).
1 - Install the control away from contactors, motors ... etc. It may be the case with
some contactor with strong electromagnetic peaks need to install a relay between
the output of
TELKAN
and the contactor coil.
3 - Insert SIM in
TELKAN
.
4 - make the rest of connections.
5 - Connect the control to the power supply 230V~
A3
R4
on
Z
in alarm
off
Z
Without alarm
on
Z
relay connected
off
Z
realy disconnected
on
Z
in temperature alarm
off
Z
without temperature alarm
blinking
Z
Connection error
on
Z
power supply by battery
off
Z
power supply by 230V~
on
Z
powered supply
off
Z
without power supply
on
Z
wiht signal GSM
off
Z
without signal GSM
blinking
Z
sending dates or
SMS received
on
Z
inserted and operational
off
Z
without card SIM
blinking
Z
the card has PIN
(take out of TELKAN & disabled the PIN)
Cod.:7955 INGVØ ENE19
OPERATING TEMPERATURE ALARM
30°C
31°C
29°C
Temperature
Device is
out
of alarm
Device is
inside
the alarm
First off set the temperature for alarm for example 30°C ± 1°C (differential of activation) may also indicate the time that has to remain above or below to consider that is in alarm.
You can define two different values or the same for the delay time (Delay). Factory goes to 0 and alerts at the same time the temperature goes from temp alarm ± 1°C.
Delays are very useful to discriminate when a temperature alarm of a product load in cold rooms where there are short peaks and temperature are controlled.
5 min.
Actives the alarm in case of being more than 5 minutes (time delay) above 31°C
(temperature alarm + differential) and does not disable the alarm until it is below of
29°C over 5 minutes (temperature alarm - differential)
0000 alarm t1 30
delays 5 minutes for activation and deactivation
Temperature for alarm: 30°C + fixed Dif.: ± 1°C
0000 delay t1 5
SMS
For the rest of general conditions visit our web.
- Apparatus modified without the consent of the manufacturer.
deleted or modified.
according to the instructions accompanying the appliance.
- Devices whose deterioration is the result of impact or liquid
Reserved the right to change without prior notice.
or gaseous emanations.
- Devices whose connection or use has not been executed
- Equipment whose serial number has been damaged,
We decline any responsibility for damaged equipment result
of poor handling. Not included in the warranty:
This device has 3 year warranty according to the date of manufacture,
it is limited to replacement of faulty part. Transport not included.
CONDITIONS OF GUARANTEE
SONDER
delay for activation 5 and 10 minutes for deactivation
0000 delay t1 5 10
Example:
Very important:
Device designed for a situation of pollution
clean.
Control device for DIN rail mounting and
connection via fixed pipeline.
When installing control ensure you have good
coverage away from contactors and other
signals that may interfere.
This control is not a safety device, and can not be
used as such, it is the installer responsibility
incorporate adequate protection to every type
of installation (
HOMOLOGATED
)
Must comply with 2 factors: Tempe Time Set
IN CASE OF:
SMS received
- The
TELKAN
saves the last 5 phone numbers that have given a correct order and if they make a lost call, the TELKAN sends an SMS of state, but the SMS that an alarm has
occurred only is sent to the numbers set in INFORM function.
• If the control is configured with the function PROMO in off, is deleted.
- If the SMS received by the
TELKAN
not start with numeric digits and comes from an unknown telephone is interpreted as a message from the phone company:
• If the control is configured with the function PROMO in on, the SMS is forwarding to all phones set in Function Inofrm
- Send an wrong SMS to the
TELKAN
from a phone that had
previously made valid orders.
- The temperature exceeds the limit set by the user
Alarm: T1
T1: 33.5C
A1: off
B1: MAIN
ERROR: invalid language. 0-Castellano, 1-English.
- If a request to change languages includes an invalid number
T1: 26.8C
A1: off
B1: MAIN
- Message received periodically according to set time with
the function
Alive
activated
pwrd +
on - relay on
off - relay off
inform on - receive alarm
test - status
pass xxxx - change password
Probe set for alarm
Reading probe alarm
Disconnected alarm contact
Main power supply
Temperature read by probe T1
Alarm 1 off
Main power supply
- Make a call to
TELKAN
from a phone that had previously
made valid orders.
R1: on
R2: off
T1: 26.8C
T2: 35C
A1: off
B1: BATT (11.799V)
Password (set from factory to 0000) + followed by the command:
order - (meaning that order)
SMS
Status query
:
State relays
Current temperature read by probes
Alarm status
battery connected (value of charge)
Warning! The volatge of
the battery is very low.
BATT (9.112V)
- Message received when the control detects that the
battery power is low.
Warning low battery with charge value
Sonder Regulación, S.A.
Avda. La Llana, 93
08191 RUBÍ
(Barcelona) Spain
www.sonder.es
230V~ +10% -15% 50Hz máx. 2VA
Power supply
Application
(relays
r1
,
r2
)
12A 250V~ SPDT.
Relays
with free voltage-contact
(operation as a switch)