                SM3691B    Us er Ma nual                   

http://www.sonbus.com/ 

Sha nghai Son

best Industrial Co., Ltd                                                                             Page3

 

        (2)Change device address 

        For example, if the current device address is 1, we want to change to 02, the command is:01 06 00 66 

00 02 E8 14 . 

Device ID 

Function id 

Start Address 

Destination 

CRC16 

01 

06 

00 66 

00 02 

E8 14 

        After the change is successful, the device will return information: 02 06 00 66 00 02 E8 27 , its format 

is parsed as shown in the following table: 

Device ID 

Function id 

Start Address 

Destination 

CRC16 

01 

  06 

00 66 

00 02 

E8 27 

        Response should be in the data, after the modification is successful, the first byte is the new device 

address. After the general device address is changed, it will take effect immediately. At this time, the user 

needs to change the query command of the software at the same time.   

        4 Read and Modify Baud Rate 
        (1) Read baud rate 

        The device default factory baud rate is 9600. If you need to change it, you can change it according to 

the following table and the corresponding communication protocol. For example, read the current device's 

baud rate ID, the command is:01 03 00 67 00 01 35 D5 , its format is parsed as follows.  

Device ID 

Function id 

Start Address 

Data Length 

CRC16 

01 

  03 

00 67 

00 01 

35 D5 

        Read the baud rate encoding of the current device. Baud rate encoding: 1 is 2400; 2 is 4800; 3 is 9600; 

4 is 19200; 5 is 38400; 6 is 115200. 

        For the correct query command, the device will respond, for example the response data is: 01 03 02 

00 03 F8 45, the format of which is as shown in the followin g table: 

Device ID 

Function id 

Data Length 

Rate ID 

CRC16 

01 

  03 

02 

00 03 

F8 45 

        coded according to baud rate, 03 is 9600, ie the current device has a baud rate of 9600.  

        (2)Change the baud rate 

        For example, changing the baud rate from 9600 to 38400, ie changing the code from 3 to 5, the 
command is: 01 06 00 67 00 05 F8 1601 03 00 66 00 01 64 15 .  

Device ID 

Function id 

Start Address 

Target Baud Rate 

CRC16 

01 

03 

00 66 

00 01 

64 15 

        Change the baud rate from 9600 to 38400, changing the code from 3 to 5. The new baud rate will take 

effect immediately, at which point the device will lose its response and the baud rate of the device should 
be queried accordingly. Modified. 

        5 Read Correction Value 
        (1) Read Correction Value 

        When there is an error between the data and the reference standard, we can reduce the display error 

by adjusting the correction value. The correction difference can be modified to be plus or minus 1000, that 
is, the value range is 0-1000 or 64535 -65535. For example, when the display value is too small, we can 

correct it by adding 100. The command is: 01 03 00 6B 00 01 F5 D6 . In the command 100 is hex 0x64 If 

you need to reduce, you can set a negative value, such as -100, corresponding to the hexadecimal value of 

FF 9C, which is calculated as 100-65535=65435, and then converted to hexadecimal to 0x FF 9C. The 

correction value starts from 00 6B. We take the first parameter as an example. The correction value is read 
and modified in the same way for multiple parameters. 

Summary of Contents for SM3691B

Page 1: ...echnical Parameters Technical parameter Parameter value Brand SONBEST Moisture Temperature range 30 80 Moisture Temperature accuracy 0 5 25 Temperature measuring range 30 80 Temperature measuring accuracy 0 5 25 Humidity measuring range 0 100 RH Humidity accuracy 3 RH 25 Communication Interface RS485 Default baud rate 9600 8 n 1 Power DC9 24V 1A Running temperature 40 80 C Working humidity 5 RH 90...

Page 2: ...rt Address Description Data type Value range 40001 00 00 soil temperature Read Only 0 65535 40002 00 01 temperature Read Only 0 65535 40003 00 02 humidity Read Only 0 65535 40101 00 64 model code read write 0 65535 40102 00 65 total points read write 1 20 40103 00 66 Device ID read write 1 249 40104 00 67 baud rate read write 0 6 40105 00 68 mode read write 1 4 40106 00 69 protocol read write 1 10...

Page 3: ...will respond for example the response data is 01 03 02 00 03 F8 45 the format of which is as shown in the following table Device ID Function id Data Length Rate ID CRC16 01 03 02 00 03 F8 45 coded according to baud rate 03 is 9600 ie the current device has a baud rate of 9600 2 Change the baud rate For example changing the baud rate from 9600 to 38400 ie changing the code from 3 to 5 the command i...

Page 4: ...ss Destination CRC16 01 06 00 6B 00 64 F9 FD After the operation is successful the device will return information 01 06 00 6B 00 64 F9 FD the parameters take effect immediately after successful change Disclaimer This document provides all information about the product does not grant any license to intellectual property does not express or imply and prohibits any other means of granting any intelle...

Reviews: