                SM1882B    Us er Ma nual                   

http://www.sonbus.com/ 

Sha nghai Son

best Industrial Co., Ltd                                                                             Page4

 

needs to change the query command of the software at the same time.   

        4 Read and Modify Baud Rate 
        (1) Read baud rate 

        The device default factory baud rate is 9600. If you need to change it, you can change it according to 

the following table and the corresponding communication protocol. For example, read the current device's 

baud rate ID, the command is:01 03 00 67 00 01 35 D5 , its format is parsed as follows.  

Device ID 

Function id 

Start Address 

Data Length 

CRC16 

01 

  03 

00 67 

00 01 

35 D5 

        Read the baud rate encoding of the current device. Baud rate encoding: 1 is 2400; 2 is 4800; 3 is 9600; 

4 is 19200; 5 is 38400; 6 is 115200. 

        For the correct query command, the device will respond, for example the response data is: 01 03 02 

00 03 F8 45, the format of which is as shown in the following table: 

Device ID 

Function id 

Data Length 

Rate ID 

CRC16 

01 

  03 

02 

00 03 

F8 45 

        coded according to baud rate, 03 is 9600, ie the current device has a baud rate of 9600.  

        (2)Change the baud rate 

        For example, changing the baud rate from 9600 to 38 400, ie changing the code from 3 to 5, the 

command is: 01 06 00 67 00 05 F8 1601 03 00 66 00 01 64 15 .  

Device ID 

Function id 

Start Address 

Target Baud Rate 

CRC16 

01 

03 

00 66 

00 01 

64 15 

        Change the baud rate from 9600 to 38400, changing the code from 3 to 5. The new baud rate will take 

effect immediately, at which point the device will lose its response and the baud rate of the device should 

be queried accordingly. Modified. 

        5 Read Correction Value 
        (1) Read Correction Value 

        When there is an error between the data and the reference standard, we can reduce the display error 

by adjusting the correction value. The correction difference can be modified to be plus or minus 1000, t hat 

is, the value range is 0-1000 or 64535 -65535. For example, when the display value is too small, we can 

correct it by adding 100. The command is: 01 03 00 6B 00 01 F5 D6 . In the command 100 is hex 0x64 If 

you need to reduce, you can set a negative value, such as -100, corresponding to the hexadecimal value of 

FF 9C, which is calculated as 100-65535=65435, and then converted to hexadecimal to 0x FF 9C. The 

correction value starts from 00 6B. We take the first parameter as an example. The correction valu e is read 

and modified in the same way for multiple parameters. 

Device ID 

Function id 

Start Address 

Data Length 

CRC16 

01 

03 

00 6B 

00 01 

F5 D6 

        For the correct query command, the device will respond, for example the response data is: 01 03 02 

00 64 B9 AF, the format of which is as shown in the following table: 

Device ID 

Function id 

Data Length 

Data value 

CRC16 

01 

  03 

02 

00 64 

B9 AF 

        In the response data, the first byte 01 indicates the real address of the current device, and 00 6B is the 

first state quantity correction value register. If the device has multiple parameters, other parameters 

operate in this way. The same, the general temperature, humidity have this parameter, the light generally 

does not have this item. 

        (2)Change correction value 

Summary of Contents for SM1882B

Page 1: ...us MODBUS RTU protocol easy access to PLC DCS and other instruments or systems for monitoring atmospheric pressure state quantities The internal use of high precision sensing core and related devices to ensure high reliability and excellent long term stability can be customized RS232 RS485 CAN 4 20mA DC0 5V 10V ZIGBEE Lora WIFI GPRS and other output methods Technical Parameters Technical parameter...

Page 2: ...the correctness and then use it again ID Core color Identification Note 1 Red V Power 2 Green V Power 3 Yellow A RS485 A 4 Blue B RS485 B In the case of broken wires wire the wires as shown in the figure If the product itself has no leads the core color is for reference Communication Protocol The product uses RS485 MODBUS RTU standard protocol format all operation or reply commands are hexadecimal...

Page 3: ... Length CRC16 FA 03 00 64 00 02 90 5F FA is 250 for the general address When you don t know the address you can use 250 to get the real device address 00 64 is the device model register For the correct query command the device will respond for example the response data is 01 03 02 07 12 3A 79 the format of which is as shown in the following table Device ID Function id Start Address Model Code CRC1...

Page 4: ... point the device will lose its response and the baud rate of the device should be queried accordingly Modified 5 Read Correction Value 1 Read Correction Value When there is an error between the data and the reference standard we can reduce the display error by adjusting the correction value The correction difference can be modified to be plus or minus 1000 t hat is the value range is 0 1000 or 64...

Page 5: ...s or imply and prohibits any other means of granting any intellectual property rights such as the statement of sales terms and conditions of this product other issues No liability is assumed Furthermore our company makes no warranties express or implied regarding the sale and use of this product including the suitability for the specific use of the product the marketability or the infringement lia...

Reviews: