Menu Operation Illustration

Under user menu status       
1. Press 

SET

 key more than 5 seconds to enter user menu; if the user password is set, it will pop up the password input box, enter the correct 

password to enter the user menu, and then set the parameters.
2. If the current display is the first class, press 

SET

 key to enter next class display. Press           to change other parameters.

3. If the current display is second or third class , press 

ESC

 key to return to previous class display.

4. If the current display is third class , press            key to flash digit, press key      to shift place. Keep pressing            to change value . Press 

SET 

key to save value. If press 

ESC

 key, do not save the set value and return to second class.

5. After modifying the parameters , press 

SET

 key more than 5 seconds or press 

ESC 

key, to exit user menu, return to measuring status.

Menu Structure and Function Description

No.

class 1

class 2

class 3

description

System 

Setting

Clear Energy

User password

backlight 

delay time

page shift time

software version

Input net

Volt transform  

Volt transform  

Current 

transform

Current 

transform

signal input

Communication

parameter

Switch signal

setting

Address

baud rate

Data sequence   

Alarm mode  

Alarm unit 

Alarm value  

Alarm hysteresis

value  

alarm relay

setting

alarm start

 delay

alarm finish

delay

Alarm mode  

Alarm unit 

Alarm value  

Alarm hysteresis

value  

alarm relay

setting

alarm start

 delay

alarm finish

delay

Input “ 1111” to clear energy.  Input 2222 to clear maximum demand.

input 1234 to reset to factory setting

Change user password

backlight delay time , unit is second . If set as  0 , mean keep on

 lighting all the time.

measurement page shift delay time , unit  is second . If set as  0, no 

page shift.

software version 

Select the input network of the measured signal

Primary coil voltage , unit kV

Secondary coil voltage , unit V

Primary coil current , unit A

Secondary coil current ,unit A

meter address range

Baud rate: 4k8 means 4800, 9k6 means 9600

Data sequence: high digit in front or low digit in front

When the value is 0 , it is for remote control mode, otherwise

it is for alarm mode. Please refer to table 1.

1: means international standard unit,  K: means 1000 times of 

international standard unit,    M: means1000000 

times of international standard unit. 

1st alarm value setting

1st alarm hysteresis value setting

1st alarm relay output setting

alarm start delay time , unit : second

alarm finish delay time , unit : second

When the value is 0 , it is for remote control mode, otherwise

it is for alarm mode. Please refer to table 1.

1: means international standard unit,  K: means 1000 times of 

international standard unit,    M: means1000000 

times of international standard unit. 

2nd alarm value setting

2nd alarm hysteresis value setting

2nd alarm relay output setting

alarm start delay time , unit : second

alarm finish delay time , unit : second

Summary of Contents for EW9L C Series

Page 1: ...demand statistics function Optional harmonic analysis funtion including the total harmonic EW9L C EW9L S EW9L F EW9L H No No No 4 20mA No No No No No No Yes Yes 1 loop RS485 1 loop RS485 1 loop RS485...

Page 2: ...DI connection Pulse output connection DC 2000V Input output power supply to Meter cover 5M Symbol Meaning voltage current power Frequency No symbol Name Function Set Key Check measuring value and wor...

Page 3: ...percentage Total voltage harmonics percentage A Phase parameters B Phase parameters C Phase parameters Measuring Status Menu Operation press SET more than 5 seconds First class Second class Third cla...

Page 4: ...eters Meter s address range Baud Rate Data format 1st Alarm mode 1st Alarm unit 1st alarm value setting 1st alarm Hysteresis value setting 1st alarm relay output choice 1st alarm start delay 1st alarm...

Page 5: ...lash flash flash flash flash flash flash 1st transmition high limit value 1st transmition low limit value year Month Day Hour Minute Second Period 1 tarrif rate Period 2 tarrif rate Period 12 tarrif r...

Page 6: ...delay Alarm mode Alarm unit Alarm value Alarm hysteresis value alarm relay setting alarm start delay alarm finish delay Input 1111 to clear energy Input 2222 to clear maximum demand input 1234 to res...

Page 7: ...ut AP RP and RS485 interface for the transmit of energy data The energy pulse of optical couple relay with open collector enables the long distance transmit of active energy AP reactive energy RP Remo...

Page 8: ...dress function code error code and check area When the high bit position of function code area is 1 it means the present data frame is abnormal response Below table illustrates the meaning of abnormal...

Page 9: ...st send read 01 address meter read the current value data started from 400C A phase current register Hexadecimal code of 100 000 is 000186A0 hexadecimal code of 200 000 is 00030D40 hexadecimal code of...

Page 10: ...Data byte length low bit Data byte length Data 1 high bit Data 1 low bit CRC code low bit CRC code high bit Meter address Function code Start address high 8 bit Start address low 8 bit Data byte lengt...

Page 11: ...122 2 long long Note Note Note Note No decimal point active power maximum demand reactive power demand reactive power maximum demand A phase voltage harmonic content B phase voltage harmonic content C...

Page 12: ...transmit mode refer to table 1 1st transmit unit note note Link mode extend note note note note note Communication address Baud rate Data format switch output switch input remote input extend No deci...

Page 13: ...demand happen time day reactive power maxi demand happen time hour reactive power maxi demand happen time minute reactive power maxi demand happen time second no decimal point Reference table 1 Refer...

Page 14: ...ion value Menu display Communication value D7 D6 D5 D4 D3 D2 D1 D0 AL1 status 0 No alarm 1 Alarm AL2 status 0 No alarm 1 Alarm Note Measure Satus Indication switch output S1 status 0 close 2 disconnec...

Page 15: ...r than 5A If some other meters are connected with the same CT the connection should be serial for all meters C Please make sure that the input voltage is corresponding to the input current they should...

Reviews: