5.Connecting Drawing
6.Dimension
KKEL8E01-3
1
2
3
5
6
Illustration
INP
Ad1
AL1
Ad2
AL2
rH
rL
Add
bAd
LCK
4
7
8
9
Ct
PS
10
11
12
13
14
Hy1
Hy2
Voltage input connecting drawing
P o w e r O N
Enter measuring
status setting
SET
SET
SET
SET
SET
SET
SET
→
SET
SET
SET
SET
SET
SET
SET
SET
Add:Meter communication address
IN1
~
IN3
H
001
9.6
000
1.000
1.000
1.000
0.000
L
H or L
H or L
-1999
~
9999
-1999
~
9999
-1999
~
9999
-1999
~
9999
-1999
~
9999
-1999
~
9999
-1999
~
9999
0
~
9999
0
~
255
0
~
255
4.8 or 9.6
AL,HY,Ct,PS,
rH,rL have the
same unit as
their range
20
19
18
17
16
15
14
13
12
11
100~240V
AC/DC
←
←
←
←
IN2 IN1
IN3
10
9
8
7
6
5
4
3
2
1
←
←
←
←
-
+
4~20mA
AL2
AL1
←
←
RXD TXD COM
GND
96
48
±0.1
+0.5
-0
+0.5
-0
±0.1
30
20
19
18
17
16
15
14
13
12
11
100~240V
AC/DC
←
←
←
←
IN2
IN1
COM2
10
9
8
7
6
5
4
3
2
1
←
←
←
←
-
+
4~20mA
AL2
AL1
←
←
RXD TXD COM
COM1
94
←
←
45
←
6
45
25
91
Panel size
Side-face size
Mounting size
Self-check after power on
All LED are on
Measuring state operation setting
Input Channel Selection:
"IN1
~
IN3"
Chosen from
The first alarm mode
H: High
;
L: Low
The first alarm value setting
The first alarm hysteresis. For
example, if Ad1 is H, AL1=50,HY1=5,
when measuring value≥50(AL1), alarm
is active; when it is≤45(AL1-HY1),
alarm is not active.
The second alarm mode:
It is similar to Ad1
The second alarm value setting:
It is similar to AL1
The second alarm hysteresis:
It is similar to HY1.
Current Transforming: It is only for
5A range or 75mV spliter current input.
It is the external CT or spliter value.
For example,if you buy a meter with
range of 20A,it should be set as 4.000
(20/5=4.000).If the range is 30A,it
should be set as 6.000(30/5=6.000).
Correction value,displaying value =
measuring value +PS.
factory setting: PS=0
High limit of analog setting : when measuring
value=rH,correspondingly , analog output = 20mA
Low limit of analog setting : when measuring
value=rL, correspondingly , analog output = 4mA
Communication baud rate:
4.8kbps
,
9.6kbps for option.
Lock key
Lock=000,read and write
Lock=010,read only
Number
Paremeter code
Setting range
Factory setting value
When the range is A1000,
default is IN1, for other range,
default is IN3.
90% of measuring range
10% of measuring range
minimum of the range
maximum of the range
Current input connecting drawing
Note:please subject to the diagram on the product if any changes.
(unit:mm)