5.Connecting Drawing

6.Dimension

KKEL8E01-3

1

2

3

5

6

Illustration

INP

Ad1

AL1

Ad2

AL2

rH

rL

Add

bAd

LCK

4

7

8

9

Ct

PS

10

11

12

13
14

Hy1

Hy2

Voltage input connecting drawing

P o w e r   O N

Enter measuring 

status setting

SET

SET

SET

SET

SET

SET

SET

SET

SET

SET

SET

SET

SET

SET

SET

Add:Meter communication address

IN1

IN3

H

001
9.6

000

1.000

1.000
1.000

0.000

L

H or L

H or L

-1999

9999

-1999

9999

-1999

9999

-1999

9999

-1999

9999

-1999

9999

-1999

9999

0

9999

0

255

0

255

4.8 or 9.6

AL,HY,Ct,PS,
rH,rL have the
same unit as 
their range 

20

19

18

17

16

15

14

13

12

11

100~240V
  AC/DC

IN2 IN1

IN3

10

9

8

7

6

5

4

3

2

1

-

+

4~20mA

AL2

AL1

RXD TXD COM

GND

96

48

±0.1

+0.5
-0

+0.5
-0

±0.1

30

20

19

18

17

16

15

14

13

12

11

100~240V
  AC/DC

IN2

IN1

COM2

10

9

8

7

6

5

4

3

2

1

-

+

4~20mA

AL2

AL1

RXD TXD COM

COM1

94

 

 

45

6

45

25

91

Panel size

Side-face size

Mounting size

Self-check after power on

All LED are on

Measuring state operation setting

Input Channel Selection:

"IN1

IN3"

Chosen from

The first alarm mode

H: High

L: Low

The first alarm value setting

The first alarm hysteresis. For 

example, if Ad1 is H, AL1=50,HY1=5,

when measuring value≥50(AL1), alarm 

is active; when it is≤45(AL1-HY1),

alarm is not active.

The second alarm mode:

It is similar to Ad1

The second alarm value setting:

It is similar to AL1

The second alarm hysteresis:

It is similar to HY1. 

Current Transforming: It is only for

5A range or 75mV spliter current input.

It is the external CT or spliter value.

For example,if you buy a meter with 

range of 20A,it should be set as 4.000

(20/5=4.000).If the range is 30A,it 

should be set as 6.000(30/5=6.000).

Correction value,displaying value =

measuring value +PS.

factory setting: PS=0  

High limit of analog setting : when measuring

value=rH,correspondingly , analog output = 20mA

Low limit of analog setting : when measuring

value=rL, correspondingly , analog output = 4mA

Communication baud rate:
4.8kbps

,

9.6kbps for option. 

Lock key

Lock=000,read and write

Lock=010,read only

Number

Paremeter code

Setting range

  

  

  

Factory setting  value

  

  

When the range is A1000,

default is IN1, for other range,

default is IN3.

90%  of measuring range

10%  of measuring range

minimum of the range

maximum of the range

Current input connecting drawing

Note:please subject to the diagram on the product if any changes.

(unit:mm)