cover the maximum expected level. See the illustration below for the default configuration.
EXAMPLE
In the default configuration the parameter
is set to
0
and
to
10'000 mm
, as illustrated below. If the USH-9 is moun-
ted at a lower height, it is recommended to keep this setting.
13.4.2 IOUT 2
The measured air temperature or a status as configured in
in can be returned as an ana-
log 4…20 mA signal on pin 7 of the MAIN connector.
If the air temperature is selected as output, the span is set to 100 °C and the offset to -40°C as
default.
If one of the status options is selected and the conditions specified in
are satisfied, the
output is set to high (20 mA) and otherwise to low (0 mA). The following status options are available:
ID
Option
Description
1
off (default)
IOUT2 is inactive.
2
value, tem-
perature
The air temperature is returned.
3
status, level
limit
If the level exceeds the limit specified in
, 20 mA is applied, oth-
erwise 0 mA.
1
3
A
n
al
o
g
o
u
tp
u
t
Manual
97