background image

© 2007-2017, SOMFY ACTIVITÉS SA, Société Anonyme. ALL RIGHTS RESERVERD. REF. 5057571C - 2017/12/05

 

WTT animeo IB+/IB • REF. 5057571C - 

4/4

A.   This installation test tool offers the following 

possibilities

1.   Sending of animeo IB+ telegrams for examination of the C and 

IB+ ( 

) wires on the 4 wire bus as well as the correct rota-

tion direction of the motors.

2.   Sending of animeo IB up/down orders for examination of the C, 

Up and Down (

st

) wires of the IB bus.

3.   Short circuit detection between the C and IB+ ( 

) wires of 

the animeo 4 wire bus.

4.   Programming of the Motor Controller local switch allocation to 

the motor outputs, individual or grouped.

B.  Preliminary conditions

1.   All blinds within the tested zone should be in the upper end limit position (completely up). 

Check the position of the blinds from the outside of the building!

2.   Examine whether wind conditions allow to drive the blinds.

3.   Connections of the local switches between Motor Controller of different zones are not allowed 

without using the switch zone splitter.

4.   Battery test of the WTT (3 V battery type CR 2430). A “low bat tery“ is indicated by 4 simultane-

ously flashing LEDs on the WTT after pressing one of the buttons on the device. Be sure that the 
device is not yet connected to the system. If the “low battery“ indication appears, replace it 
before continuing! The life span of the battery amounts to approx. 2000 send instructions.

5.   Remove the bus connection from the Building Controller to the Motor Controller zone and at-

tach the WTT to the Motor Controller zone.

UP

STOP

DOWN

MODE

E.  Grouping of the local switches on the Motor Controller

1.   Identify the Motor Controllers to program and disconnect them from the IB+ bus. Connect the 

WTT to the Motor Controller(s) which have to be programmed. 

Attention: This order is transfered to all connected Motor Controllers. 

2.   Enable the function by pushing the button on the back of the WTT at least  

3 seconds. On = 2 x outside-inside running light on the WTT.

3.   Choose the wanted switch configuration with the Up-button on the WTT. 

You have 8 possibilities to choose from. The choice will be displayed with  

the 4 LEDs on the WTT. 

Red = Motor 1, Orange = Motor 2, Yellow = Motor 3, Green = Motor 4.

Example:  All 4 LEDs on the WTT blink one by one = Each switch controls 1 motor

4.   By pressing the Stop button on the WTT, the current chosen combination can be visualised.

5.  

Send the order by pushing the mode button. Again, your choice is indicated by the LEDs on the WTT.

6.   Test via the local switch if your configuration succeeded.

7.   Disable the grouping function by pushing the button on the back for 3 seconds. 

Off = 2 x inside-outside running light on the WTT.

F. Battery

1.   Unloose screws and remove cover of Wiring Test Tool.

2.   Remove used battery and insert new one (Type CR 2430).

3.  Proper disposal of used battery.

m  

Batteries or accumulators have to be separated from other type 

of waste and must be recycled through your local treatment and 

recycling system.

min. 3 s.

WTT animeo IB+/IB 

W

iring 

T

est

 T

ool

Installation guide

50 Avenue du Nouveau Monde, 74300 Cluses, France

somfy.com/projects 

somfy.com/ce

©2007-2017, SOM

FY

 A

CTIVITÉS SA

 - Sociét

é 

Anon

yme - c

apit

al 35.000.000 €, R

CS 

ANNE

CY

 303.970.230. 

AL

L RIGHTS RESER

VED

. REF

. 5057571C

 – 2017/12/05 100 % r

ec

ycled p

aper

Reviews: