C.  Detectable errors 

Error 1:   Motor Controller without supply
Error 2:   Missing IB+ transmission to the Motor Controller
Error 3:   Short circuit in the IB+ bus, between the C and IB+ wire (a short circuit  

is indicated by 4 simultaneously flashing LEDs on the wiring test tool)

Error 4:   Inverted up/down motor connection
Error 5:   Broken fuse for the corresponding motor output
Error 6:   Broken motor or missing connections
Error 7:   Inverted up/down wires or short circuit on the IB bus. Start to look for the error from the 

Motor Controller which is closest to the Building Controller

Error 8:   Wiring mistake on the local switches

Remark:  When running long test sequences the thermal protection of the mo-

tors could be activated. In this case wait 30 minutes before continuing.

D.  Wiring test sequence

1.  Testmode on

 by pressing  

(1 sec) the button on the back 

of the tool.

Testmode on = orange LED blinks  

3 x. Running light on all connected 

Motor Control lers. During the 

test mode, all local switches are 

disabled!

Error 1

Error 2

Error 3

After correc-

tion,  

repeat this 

step until the 

running light is 

enabled on all 

Motor Control-

lers

 

 

4.  Test mode off

 by pressing  

(1 sec) the button on the back of 

the tool.

Test mode off = yellow LED blinks 3 x. The running light on the 

Motor Controller stops. All local switches are enabled again!

 

2a.  IB+ Down order. 

Order 

indicated on WTT by blinking of 

the red and the green LED.

Visual check of all blinds in the zone. 

All blinds move down for approx. 

10 sec.

Wrong running  

direction

Error 4

Does not move

Error 5

Error 6

After correction,  

repeat step 2a 

and 2b until 

o.k.

2b.  IB+ Up order. 

Order indi-

cated on WTT by blinking of the 

red and the green LED.

Visual check of all blinds in the zone. 

All blinds move up for approx. 10 sec.

3a. Switching to IB mode 

in order to test the C, up and down (

st

) wires of the IB bus.

(You may switch from IB to IB+ by pushing the mode button for 3 sec)

3b.  IB Down order. 

Order 

indicated on WTT by blin king of 

the red and the yellow LED.

Visual check of all blinds in the zone. 

All blinds move down to the lower 

end limit.

Error 7

After correction,  

repeat step 3b 

and 3c until o.k.

3c.  IB Up order. 

Order  indi cated 

on WTT by blinking of the red 

and the orange LED.

Visual check of all blinds in the zone. 

All blinds move up to the upper end 

limit.

WTT Command

Reaction

Possible error

WTT order

Reaction

Possible error

5.  

Check each of the local switches in the building individually!

Error 8