4
EN
Copyright © 2006-2017 SOMFY ACTIVITES SA, Société Anonyme. All rights reserved. Images are not contractually binding.
2.3. COMMISSIONING
These instructions describe commissioning using a local Somfy io-homecontrol
®
control
point.
2.3.1. Identifying the type of roller blind setting
Connect the motor to the mains; only switch on one
motor at a time.
• If the blind moves briefly, the end limits are set,
and the local control is not programmed, see
2.3.2.
• If the blind does not move, press the
up
button;
if the blind is raised fully, the end limits are set
and the local control is programmed. Move onto
the next blind.
-
If the blind does move, the end limits are not
set and the local control is not programmed, see
2.3.3
.
2.3.2. Memorising the transmitter
-
Simultaneously press the
Up
and
Down
buttons
on the transmitter to be programmed: the blind
moves briefly.
-
Briefly press the
“PROG”
button on the transmitter
to be programmed: the blind moves briefly; the
transmitter is memorised.
2.3.3. Determining the blind types
• [1]
Stops and rigid links: see
2.3.4. Adjusting
the automatic upper and lower end limits
.
• [2]
Flexible links and no stops: see
2.3.5.
Adjusting the manual upper and lower end
limits
.
• [3]
Flexible links and stops: see
2.3.6. Adjusting
the manual lower and automatic upper end
limits.
• [4]
Rigid links and no stops: see
2.3.6. Adjusting
the manual upper and automatic lower end
limits
.
2.3.4. Adjusting the automatic upper and lower end limits
1)
Simultaneously press the
Up
and
Down
buttons:
the blind moves briefly.
2.3.2.
2.3.3.
[1]
[3]
[4]
[2]
2.3.4.
2.3.5.
2.3.6.
2.3.7.
1)
[1]
Summary of Contents for Oximo io
Page 1: ...Oximo io Ref 5015164C R 0 4C0 EN Instructions ES Manual PT Instru es EL www somfy com...
Page 2: ......
Page 39: ......