10

Information on servicing (Continued)
9.  Checks to electrical devices

 

Repair and maintenance to electrical components shall 
include initial safety checks and component inspection 
procedures. If a fault exists that could compromise 
safety, then no electrical supply shall be connected to 
the circuit until it is satisfactorily dealt with. If the fault 
cannot be corrected immediately but it is necessary to 
continue operation, an adequate temporary solution 
shall be used. This shall be reported to the owner of the 
equipment so all parties are advised. 
Initial safety checks shall include: 
That capacitors are discharged: this shall be done in a 
safe manner to avoid possibility of sparking;  
That there no live electrical components and wiring 
are exposed while charging, recovering or purging the 
system; That there is continuity of earth bonding.

10. Repairs to sealed components

•  During repairs to sealed components, all electrical 

supplies shall be disconnected from the equipment 
being worked upon prior to any removal of sealed 
covers, etc. If it is absolutely necessary to have an 
electrical supply to equipment during servicing, then 
a permanently operating form of leak detection shall 
be located at the most critical point to warn of a 
potentially hazardous situation.

•  Particular attention shall be paid to the following to 

ensure that by working on electrical components, the 
casing is not altered in such a way that the level of 
protection is affected. This shall include damage to 
cables, excessive number of connections, terminals 
not made to original specification, damage to seals, 
incorrect fitting of glands, etc. Ensure that apparatus 
is mounted securely. Ensure that seals or sealing 
materials have not degraded such that they no 
longer serve the purpose of preventing the ingress of 
flammable atmospheres. Replacement parts shall be in 
accordance with the manufacturer’s specifications. 

NOTE:

 The use of silicon sealant may inhibit the 

effectiveness of some types of leak detection 
equipment. Intrinsically safe components do not have 
to be isolated prior to working on them.

11.  Repair to intrinsically safe components

 

Do not apply any permanent inductive or capacitance 
loads to the circuit without ensuring that this will 
not exceed the permissible voltage and current 
permitted for the equipment in use. Intrinsically safe 
components are the only types that can be worked on 
while live in the presence of a flammable atmosphere. 
The test apparatus shall be at the correct rating. 
Replace components only with parts specified by the 
manufacturer. Other parts may result in the ignition of 
refrigerant in the atmosphere from a leak.

12. Cabling

 

Check that cabling will not be subject to wear, corrosion, 
excessive pressure, vibration, sharp edges or any other 
adverse environmental effects. The check shall also take 
into account the effects of aging or continual vibration 
from sources such as compressors or fans.

13. Detection of flammable refrigerants

 

Under no circumstances shall potential sources of 
ignition be used in the searching for or detection of 
refrigerant leaks. A halide torch (or any other detector 
using a naked flame) shall not be used.

14. Leak detection methods

 

The following leak detection methods are deemed 
acceptable for systems containing flammable 
refrigerants. Electronic leak detectors shall be used 
to detect flammable refrigerants, but the sensitivity 
may not be adequate, or may need re-calibration. 
(Detection equipment shall be calibrated in a 
refrigerant-free area.) Ensure that the detector is not 
a potential source of ignition and is suitable for the 
refrigerant used. Leak detection equipment shall be 
set at a percentage of the LFL of the refrigerant and 
shall be calibrated to the refrigerant employed and 
the appropriate percentage of gas (25 % maximum) 
is confirmed. Leak detection fluids are suitable for 
use with most refrigerants but the use of detergents 
containing chlorine shall be avoided as the chlorine 
may react with the refrigerant and corrode the copper 
pipe-work. If a leak is suspected, all naked flames shall 
be removed/ extinguished. If a leakage of refrigerant 
is found which requires brazing, all of the refrigerant 
shall be recovered from the system, or isolated (by 
means of shut off valves) in a part of the system 
remote from the leak. Oxygen free nitrogen (OFN) shall 
then be purged through the system both before and 
during the brazing process.

15. Removal and evacuation

 

When breaking into the refrigerant circuit to make 
repairs or for any other purpose conventional 
procedures shall be used. However, it is important 
that best practice is followed since flammability is 
a consideration. The following procedure shall be 
adhered to:  
Remove refrigerant; Purge the circuit with inert gas; 
Evacuate; Purge again with inert gas; Open the circuit 
by cutting or brazing. 
The refrigerant charge shall be recovered into the 
correct recovery cylinders. The system shall be flushed 
with OFN to render the unit safe. This process may 
need to be repeated several times. Compressed air or 
oxygen shall not be used for this task. Flushing shall be 
achieved by breaking the vacuum in the system with 
OFN and continuing to fill until the working pressure is 
achieved, then venting to atmosphere, and

General Safety Instructions (Continued)

Summary of Contents for GGSAD16W

Page 1: ...E S S E N T I A L S F O R L I F E User Manual MODEL GGSAD16W Dehumidifier...

Page 2: ...he following information which can be found on the rating plate and the date of purchase which can be found on your sales invoice STORE DETAILS STORE NAME ADDRESS TELEPHONE PURCHASE DATE PRODUCT DETAI...

Page 3: ...es and importantly taking care of your appliance when cleaning our Support Team are here to help You can use our online Support Centre at anytime by visiting http support residentiagroup com au or you...

Page 4: ...4 This page is intentionally left blank...

Page 5: ...ide 19 Other Useful Information 20 Technical Specifications 22 Warranty Information S lt recommends the use of original spare parts When contacting our customer service team please ensure that you hav...

Page 6: ...unplugging it from the wall socket Disconnect Turn off the unit first and then unplug it when it is not in use and before maintenance or cleaning but do not unplug it when it is in operation as this c...

Page 7: ...with relevant safety and performance standards An electrical specialist must carry out all repairs Contact our after sales support line for advice on service INSTALLATION Proper installation Install...

Page 8: ...he equipment manuf and repair requiring the assistance of other skilled personnel shall be carried of the person competent in the use of flammable refrigerants The appliance shall be stored in a room...

Page 9: ...inguisher adjacent to the charging area 6 No ignition sources No person carrying out work in relation to a refrigeration system which involves exposing any pipe work that contains or has contained fla...

Page 10: ...d by the manufacturer Other parts may result in the ignition of refrigerant in the atmosphere from a leak 12 Cabling Check that cabling will not be subject to wear corrosion excessive pressure vibrati...

Page 11: ...volume liquid charge i Do not exceed the maximum working pressure of the cylinder even temporarily j When the cylinders have been filled correctly and the process completed make sure that the cylinder...

Page 12: ...er level indicator window 6 Drain hose outlet 7 Caster wheels 8 Power cord plug 9 Air intake grill 10 Air filter located behind the grill 11 Power cord storage Note The above diagrams are for explanat...

Page 13: ...after sales support line for advice Read the manual to familiarise yourself with all parts and operating principles Pay particular attention to the safety instructions on the previous pages WARNING EL...

Page 14: ...rcentage and conversely for damper air set a higher relative humidity level 5 Turbo button Fan Speed Use this button to select the fan speed Press to select either High or Normal fan speed setting Not...

Page 15: ...FEATURES Water tank full FULL This indicator light will illuminate when the water tank is full and ready to be emptied This light will also illuminate when the water tank has not been fitted correctl...

Page 16: ...ng the Timer setting to 0 0 will cancel the Auto Start or Auto Stop functions If the LED display window is showing the error code P2 the Auto Start or Stop function will also be cancelled Dryer Mode Y...

Page 17: ...he FULL indicator light will also flash and the digital display will show P2 Slowly and carefully remove the water tank Grip the left and right handles securely and carefully pull the tank straight ou...

Page 18: ...ing warm air in Close all windows and doors Have you allowed enough time for the appliance to work Is the room you are using the appliance in too large Room temperature is too low below 5 C The air fi...

Page 19: ...low the filter to completely dry before refitting it WARNING Never put the filter in a dishwasher or washing machine This will cause damage IMPORTANT Never operate the appliance without the air filter...

Page 20: ...20 RATING LABEL Technical Specifications...

Page 21: ...to the relevant label on the unit itself 2 Installation service maintenance and repair of this unit must be performed by a certified technician 3 Product uninstallation and recycling must be performe...

Page 22: ...epair an Appliance during the Warranty Period g Warranty Period means i where the Appliance is used for personal domestic or household use i e normal single family use as set out in the instruction ma...

Page 23: ...nce was serviced or repaired by anyone other than Residentia Group an authorised repairer or ASR 8 This warranty the contract to which it relates and the relationship between you and Residentia Group...

Page 24: ...C COM This a 6033 RESP At th prod of ina of it a facili T 1300 11 4357 E support residentiagroup com au E S S E N T I A L S F O R L I F E An initiative by Residentia Group www solt house...

Reviews: