background image

1. Access the Initial Setup mode by pressing and holding the

;

button for three seconds. Press the

'

button repeatedly until the parameter

Ctrl

appears. Use the

,

and

.

buttons to select

onof

for ON

/ OFF control and press the

;

button to save the selected value. Press the

'

button to access the param-

eter

s-hC

. Use the

.

button to select

h2C1

for controlling a cooling / heating loop. This parameter sets

the cooling control to output #1 and the heating control to output #2. Press the

;

button twice to save the

value and return to the controller main screen.
2. Press the

'

button to access the parameter

r-s

. Verify that the default value

run

is selected. Press

the

;

button to return to the controller main screen.

3. Press the

;

button for less than three seconds to access the

parameter

hts

. Use the

,

and

.

buttons to enter hysteresis

for output #2, the heating control. This is the amount the PV must go

below the SV before the controller output turns on. Press the

;

button to save the selected value. Press the

'

button to access the

parameter

Cts

. Use the

,

and

.

buttons to enter hysteresis

for output #1, the cooling control. This is the amount the PV must go

above the SV before the controller output turns on. Press the

;

button twice to save the selected value and return to the controller

main screen.
4. Optional regulation parameters can be programmed for additional dual loop control. If this is desired, access

the regulation mode again by pressing the

;

button for less than three seconds. Press the

'

button

repeatedly until the parameter

dead

appears. Use the

,

and

.

buttons to enter a deadband zone value

around the setpoint where the output is not on. The PV must go beyond the deadband range in order for either

the heating or cooling output to turn on. Press the

;

button twice to save the selected value and return to the

controller main screen.

Dual Cooling / Heating Loop with ON / OFF Control

12-9

OFF

PV

Set point

ON

Heating

Dead band

Heating hysteresis 

Cooling hysteresis 

Cooling

hts

Cts

dead

Dual loop ON / OFF control

output operation

Manual Control

1. Access the Initial Setup mode by pressing and holding the

;

button for three seconds. Press the

'

button repeatedly until the parameter

Ctrl

appears. Use the

,

and

.

buttons to select

manu

for

manual control. Press the

;

button twice to save the selected value and return to the controller main screen.

2. Press the

'

button to access the parameter

out1

. Use the

,

and

.

buttons to set a value

between

)0

and

10)0

to control output #1 directly. If the controller has a discrete output, a value of

2)0

turns the output on 20% of the time. A value of

10)0

would turn the output on 100% of the time. A manually

controlled analog output value is a percentage of the analog signal. For example, if the controller has a 4-20mA

current output, a setting of

)0

would mean that the output would be 4mA. The output would be 20mA with a

setting of

10)0

. Both types of manually controlled outputs are off with a value of

00

. Press the

;

button

to save the selected value. For dual output control, press the

'

button to access the parameter

out2

. Use

the

,

and

.

buttons to set a value between

)0

and

10)0

to control output #2 directly. Press the

;

button twice to save the selected value and return to the controller main screen.

12-11

Dual Cooling / Heating Loop with PID Control

1. Access the Initial Setup mode by pressing and holding the

;

button for three seconds. Press the

'

button repeatedly until the parameter

Ctrl

appears. Confirm the default value

Pid

is selected for PID

control. Press the

'

button to access the parameter

s-hC

. Use the

.

button to select

h2C1

for

controlling a dual cooling / heating loop. This parameter sets the cooling control to output #1 and the heating

control to output #2. Press the

;

button twice to save the value and return to the controller main screen.

2. Press the

'

button to access the parameter

r-s

. Verify that the default value

run

is selected. Press

the

;

button to return to the controller main screen.

3. Refer to Section 12-1 of this Quick Start Guide to set up the PID control parameters.
4. If the temperature controller’s output #1 is discrete, access the regulation mode again by pressing the

;

button for less than three seconds. Press the

'

button repeatedly until the parameter

Clpd

appears. Use

the

,

and

.

buttons to set the time period in seconds for the cooling output. Press the

;

button to save

the value. If the temperature controller’s output #2 is discrete, press the

'

button repeatedly until the param-

eter

hCpd

appears. Use the

,

and

.

buttons to enter the cycle period for output #2, the heating output.

Press the

;

button twice to save the value and return to the controller main screen.

5. Optional regulation parameters can be programmed for additional dual

loop control. If this is desired, access the regulation mode again by

pressing the

;

button for less than three seconds. Press the

'

button repeatedly until the parameter

Coef

appears. This value allows

the heating control to have a different proportional setting than the cooling

loop. The cooling loop proportional band setting is multiplied by the

Coef

value to create a proportional band setting for the heating loop

control. Use the

,

and

.

buttons to change this value if desired.

Press the

;

button to save the selected value. Press the

'

button to

access the parameter

dead

. Use the

,

and

.

buttons to enter a

deadband zone value around the setpoint where the output is not effected

by the proportional control value. As long as the PV remains within the

deadband zone the output is not affected by the proportional control. The

integral and derivative controls ignore the deadband setting and may

cause the output to be on within the deadband zone. Press the

;

button

twice to save the value and return to the controller main screen.

12-8

PV

0

Output

Dead band: dead

band width=positive

Set point

Heating

Cooling

dead

PV

0

Output

Dead band: dead

band width=negative

Set point

Heating

Cooling

dead

Dual loop PID control

positive deadband

Dual loop PID control

negative deadband

Alarm Output

Note: ALnH represents AL1H. ALnL represents AL1L.

13

Ramp / Soak Control

1. Access the Initial Setup mode by pressing and holding the

;

button for three seconds. Press the

'

button repeatedly until the parameter

Ctrl

appears. Use the

,

and

.

buttons to select

pro6

for

Ramp / Soak control. Press the

;

button to save the selected value. Press the

'

button to access the

parameter

Patn

. Eight different Ramp / Soak patterns are possible with the Solo Temperature Controller. Use

the

,

and

.

buttons to select pattern number 0 through 7 for programming. Press the

;

button to save

the selected value.
2. The chart below illustrates an example of a seven step Ramp / Soak pattern (Pattern 0). Press the

'

button

to access the parameter

SP00

. Use the

,

and

.

buttons to select a setting value temperature for step

00 and press the

;

button to save the value. Press the

'

button to access the parameter

ti00

. Use the

,

and

.

buttons to enter a time in hours / minutes for step 00. Follow this procedure until the desired

number of temperature and time parameters are completed. Press the

'

button to access the parameter

psx0

. Use the

,

and

.

buttons to select the last step to be completed by the Ramp /Soak pattern. For

example, if

psx0

is set to

4

, steps 00 through 04 will be executed in the pattern.

3. Press the

'

button to access the parameter

CYC0

. Use the

,

and

.

buttons to select the number

of additional times the Ramp / Soak pattern will be executed. For example, if

CyC0

is set to

3

, the Ramp /

Soak pattern will execute a total of four times. Press the

;

button to save the selected value. Press the

'

button to access the parameter

lin0

. Use the

,

and

.

buttons to choose a Ramp / Soak pattern to

execute after the completion of Pattern 0. If set to

off

, the temperature of the last step in Pattern 0 will be held.

Press the

;

button twice to save the selected value and return to the controller main screen.

100

°

70

°

50

°

30

°

Ramp

03.00

02.00

08.00

Soak

POS0 POS1

POS2

POS3

POS4

POS5

POS6

05.00

03.00

05.00

03.00

Step00 = 50°

Time00 = 3 hrs 00 min.

Step01 = 70°

Time01 = 2 hrs 00 min.

Step02 = 70°

Time02 = 5 hrs 00 min.

SP00

ti00

SP01

ti01

SP02

ti02

Step03 = 100°

Time03 = 3 hrs 00 min.

Step04 = 100°

Time04 = 8 hrs 00 min.

Step05 = 30°

Time05 = 5 hrs 00 min.

SP03

ti03

SP04

ti04

SP05

ti05

Step06 = 30°

Time06 = 3 hrs 00 min.

Process Step = 6

Cycle times = 0

Link = OFF

SP06

ti06

psx0

CyCO

lin0

12-10

Set Value

Alarm Type

Alarm Output Operation

0

Alarm function disabled

Output is OFF

1

Deviation upper and lower limit:

This alarm output activates when the PV value is higher than the setting value

SV + ALnH or lower than the setting value SV - ALnL.

ON

OFF

SV - ALnL

SV

SV + ALnH

2

Deviation upper-limit:

This alarm output activates when the PV value is higher than the setting value

SV + ALnH.

ON

OFF

SV

SV+ALnH

3

Deviation lower limit:

This alarm output activates when the PV value is lower than the setting value

SV - ALnL.

ON

OFF

SV

SV - ALnL

4

Reverse deviation upper and lower limit:

This alarm output activates when the PV value is in the range of the setting value

SV+ ALnH and the setting value SV - ALnL.

ON

OFF

SV

SV - ALnL

SV + ALnH

5

Absolute value upper and lower limit:

This alarm output activates when the PV value is higher than the setting value ALnH

or lower than the setting value ALnL.

ON

OFF

ALnL

ALnH

6

Absolute value upper-limit:

This alarm output activates when the PV value is higher than the setting value ALnH

ON

OFF

ALnH

7

Absolute value lower limit:

This alarm output activates when the PV value is lower than the setting value ALnL

ON

OFF

ALnL

8

Deviation upper and lower limit with standby sequence:

This alarm output activates when the PV value reaches the set point (SV value) and

the reached value is higher than the setting value SV + ALnH or lower than the setting

value SV - ALnL.

ON

OFF

SV

SV - ALnL

SV + ALnH

9

Deviation upper limit with standby sequence:

This alarm output activates when the PV value reaches the set point (SV value) and

the reached value is higher than the setting value SV+ ALnH.

SV + ALnH

ON

OFF

SV

10

Deviation lower limit with standby sequence:

This alarm output activates when the PV value reaches the set point (SV value) and

the reached value is lower than the setting value SV - ALnL.

SV - ALnL

ON

OFF

SV

11

Hysteresis upper-limit alarm output:

This alarm output activates when the PV value is higher than the setting value

SV + ALnH. This alarm output is OFF when the PV value is lower than the setting

value SV + ALnL.

ON

OFF

SV + ALnL

SV

SV + ALnH

12

Hysteresis lower-limit alarm output:

This alarm output activates when the PV value is lower than the setting value

SV- ALnH. This alarm output is OFF when the PV value is higher than the setting

value SV - ALnL.

ON

OFF

SV - ALnH

SV

SV - ALnL

13

N/A

Ramp / Soak Program Alarms

14

This alarm activates when the Ramp / Soak program has ended.

15

This alarm activates while the program is in RAMP UP status.

16

This alarm activates while the program is in RAMP DOWN status.

17

This alarm activates while the program is in SOAK status.

18

This alarm activates while the program is in RUN status.

Error Display Information

14

The chart below shows the possible error displays on the Solo temperature controller.

Controller Error Display

Display Position

Display

Meaning

Cause

Corrective Action

PV

b160

Cr

Initialization

PV = Firmware version

SV = Module type

The controller is in

the initialization

process.

The Solo controller displays this information for a few sec-

onds after power up. If the controller continues

displaying this information, check the input wiring. If the
problem still exists, replace the sensor or the controller.

SV

PV

no

Cont

No sensor input

The input terminals

are open.

Check the input wiring. If the problem still exists, replace the

sensor or the controller.

SV

PV

Err

Inpt

Input error

The controller cannot

read the input value

Check the sensor and the input wiring. If the problem still

exists, replace the sensor or the controller.

SV

PV

Err

Prom

EEPROM error

There is an error with

the EEPROM

Cycle the power to the Solo controller. If the problem still

exists, replace the controller.

SV

PV

Flashing PV

PV out of range

The PV is out of

range

Check the PV range. The parameters

tp-h

and

tp-l

define the range. Refer to section 12-1, 12-2 or 12-3 for

directions on how to access these parameters.

SV

The SL4824 series temperature controller has one alarm output, ALA1. Alarm group ALA1 can be programmed

for one of seventeen different alarm types. To set up the alarm output, press the

;

button for three seconds.

Press the

'

button repeatedly until the parameter

ALA1

appears. Use the

.

button to choose the set

value for the desired alarm type. Refer to the chart below for alarm type information. Press the

;

button to

save the selected value. Press the

;

button repeatedly until the controller returns to the main screen.

The alarm output limits are controlled by the parameters

Al

n

h

and

Al

n

l

, where “n” corresponds to the alarm

output group chosen. After setting the alarm type for ALA1, press the

'

button repeatedly until the parameter

Al

n

h

and/or

Al

n

l

appears. Use the

.

and

,

buttons to enter the high and/or low values for alarm

group ALA1. Press the

;

button to save each selected value. Press the

;

button again to return to the

controller main screen.
ALA1 is a SPST resistive load 3A @ 250 VAC, normally open relay output.

Summary of Contents for SL4824 Series

Page 1: ...pe unit and must be placed in an enclosure away from high temperature humidity dripping water corrosive materials airborne dust and electric shock or vibration 12 Make sure power cables and signals from instruments are all installed properly before energizing the controller otherwise serious damage may occur 13 To prevent electric shock do not touch the terminals in the controller or try to repair...

Page 2: ...To display the process value or parameter type SV Display To display the set point parameter operation read value manipulated variable or set value of the parameter AT Auto tuning LED flashes when the Auto tuning operation is ON OUT1 OUT2 Output LED lights when the output is ON ALM Alarm output LED lights when one of the alarms is on C F Temperature unit LED C Celsius F Fahrenheit Set Button Press...

Page 3: ...e to save the value and return to the controller main screen 2 Press the button to access the parameter r s Verify that the default value run is selected Press the button to return to the controller main screen 3 Press the button for less than three seconds to access the parameter Cts Use the and buttons to enter hysteresis This is the amount the PV must go above the SV before the controller outpu...

Page 4: ...or programming Press the button to save the selected value 2 The chart below illustrates an example of a seven step Ramp Soak pattern Pattern 0 Press the button to access the parameter SP00 Use the and buttons to select a setting value temperature for step 00 and press the button to save the value Press the button to access the parameter ti00 Use the and buttons to enter a time in hours minutes fo...

Reviews: