SIG-5450 User Manual Ver. 1.1
- 14 -
connection is terminated. The unit is seconds and can be set between 0 and
3600. Default value is 0.
3.2.3
Modbus
⚫
Modbus Type
This item is to set the Modbus type. Set it to Slave when using this product
with an HMI program including ModMap. It can be set to Master only when it is
used an Internet Switch. The default value is Slave.
3.2.4
Digital Output
⚫
Fail Safe Mode
This item is to set whether to enable the Fail-Safe function. If you enable
the Fail-Safe function to a specific output port, the state of the port is
initialized when the TCP connection with the counterpart is lost. If there are
multiple sessions connected, Fail Safe Mode is run only if all sessions are
disconnected.
⚫
Delay (Unit: ms)
This item is to set the output delay time. When the product receives an output
control frame from the master, it delays the output by the time set in this
item. The setting unit is milliseconds. The range is 0 to 30000 and the
default value is 0.
⚫
Pulse Mode
This item selects whether to use the pulse output mode. If this value is set
to Enable, output in the form of a pulse or a pulse train is available.
⚫
Pulse: Width (Unit: ms)
This item is to set the time to output ON signal in pulse output mode. The
setting unit is milliseconds. The range is 100 to 30,000 and the default value
is 1,000.
⚫
Pulse: Interval (Unit: ms)
This item is to set the time interval between two pulse signals when the
Number is set to a value more than 2. The setting unit is milliseconds. The
range is 100 to 30,000 and the default value is 1,000.
⚫
Pulse Mode: Repeat Count
This item sets the number of pulses to be output in pulse output mode. The
range is 1 to 32 and the default value is 1.