PV Grid Tie Inverter

Solis-1P6K3-4G, Solis-1P7K-4G, Solis-1P8K-4G, Solis-1P9K-4G, Solis-1P10K-4G

Solis 4G Single Phase Inverter

Ver 1.7

Installation and Operation Manual

Ginlong Technologies Co., Ltd.

No. 57 Jintong Road, Binhai Industrial Park, Xiangshan, Ningbo, 

Zhejiang, 315712, P.R.China.

Tel: +86 (0)574 6578 1806

Fax: +86 (0)574 6578 1606

If you encounter any problem on the inverter, please find out the inverter S/N 

and contact us, we will try to respond to your question ASAP. 

Please adhere to the actual products in case of any discrepancies in this user manual. 

Summary of Contents for Solis-1P10K-4G

Page 1: ... Manual Ginlong Technologies Co Ltd No 57 Jintong Road Binhai Industrial Park Xiangshan Ningbo Zhejiang 315712 P R China Tel 86 0 574 6578 1806 Fax 86 0 574 6578 1606 If you encounter any problem on the inverter please find out the inverter S N and contact us we will try to respond to your question ASAP Please adhere to the actual products in case of any discrepancies in this user manual ...

Page 2: ...ter 4 3 Electrical Connections Contents 3 5 5 5 6 7 7 7 8 8 9 9 11 13 6 Operation 20 5 Start Stop 5 1 Start the Inverter 5 2 Stop the Inverter 19 19 19 1 1 Product Description 3 1 2 Packaging 4 4 3 1 Connect PV side of inverter 13 4 3 2 Connect grid side of inverter 16 18 4 3 3 Max overcurrent protection device OCPD 18 4 3 4 Inverter monitoring connection 6 2 1 Lock screen 22 6 2 Information 20 6 ...

Page 3: ...nergy 6 4 5 Monthly Energy and Yearly Energy 24 24 24 6 4 2 Running Message 24 6 4 6 Daily Record 6 4 7 Communication Data 25 25 6 4 8 Warning Message 25 6 5 Advanced Settings 6 5 1 Select Standard 6 5 2 Grid ON OFF 25 26 27 28 6 5 3 Clear Energy 6 5 4 Reset Password 27 27 6 5 5 Power Control 6 5 6 Calibrate Energy 27 28 6 5 7 Special Settings 6 5 8 STD Mode Settings 28 29 29 7 Maintenance 8 Troub...

Page 4: ... important safety instructions which if not correctly followed could result in serious injury or death Improper use may result in potential electric shock hazards or burns This manual contains important instructions that should be followed during installation and maintenance Please read these instructions carefully before use and keep them for future reference WARNING Please don t connect PV array...

Page 5: ...ifications 5 To startup the inverter the Grid Supply Main Switch AC must be switched on before the solar panel s DC isolator shall be switched on To stop the inverter the Grid Supply Main Switch AC must be switched off before the solar panel s DC isolator shall be switched off 6 CAUTION The PV array Solar panels supplies a DC voltage when they are exposed to sunlight CAUTION Risk of electric shock...

Page 6: ...ut power limiting Ginlong recommends inverter installed to avoid direct sunlight or raining WARNING Risk of fire Despite careful construction electrical devices can cause fires Do not install the inverter in areas containing highly flammable materials or gases Do not install the inverter in potentially explosive atmospheres Figure 4 1 Recommended installation position 3 3 Keypad 3 4 LCD There are ...

Page 7: ... 5 If the mounted inverter is tilted to an angle greater than the maximum noted heat dissipation can be inhibited and may result in less than expected output power 4 Installation 4 Installation 11 Dimensions of mounting bracket Figure 4 4 Inverter wall mounting Please see Figure 4 4 and Figure 4 5 for instruction on mounting the inverter to a wall or pillar Figure 4 3 Inverter wall mounting 4 2 Mo...

Page 8: ...G The inverter must be mounted vertically 3 Use the suitable screws to fix the bracket to the wall 4 Lift up the inverter be careful to avoid body strain and align the back bracket on the inverter with the convex section of the mounting bracket Hang the inverter on the mounting bracket and make sure the inverter is secure see Figure 4 6 Figure 4 6 Wall Mount Bracket 5 Use screws to fix the bottom ...

Page 9: ...ssemble the Connector Cap nut Figure 4 11 Insert the Wire into the Connector Cap nut and contact pin 4 Installation Figure 4 8 DC Connector Figure 4 9 DC Connector Please use approved DC cable for PV system Cable type 4 0 6 0 Cross section Range Industry generic PV cable model PV1 F Recommended value 4 0 12AWG 12 10AWG 15 14 Table 4 1 DC cable Figure 4 13 Connector with Cap nut Screwed on Crimping...

Page 10: ...he 3 cables into AC terminal and use the slotted screwdriver to tight the screws The torque is 2 2 5Nm as shown in figure 4 17 Figure 4 17 Connect cable to AC terminal WARNING Please do not put the insulating layer of the cable in to the terminal when tight the screws otherwise it will cause poor contact D Push the AC terminals along the rail to the inside of the inverter then tighten the screw un...

Page 11: ... 45 5 43 5 Solis 1P6K3 4G 40 5 1 Start the Inverter To start up the Inverter it is important that the following steps are strictly followed 1 Switch the grid supply main Switch AC ON first 2 Switch the DC switch ON If the voltage of PV arrays are higher than start up voltage the inverter will turn on The red LED power will light 3 When both the DC and the AC sides supply to the inverter it will be...

Page 12: ...n also be scrolled manually by pressing the UP and DOWN keys Press the ENTER key to access to the Main Menu V_DC1 350 8V I_DC1 5 1A V_DC3 350 8V I_DC3 5 1A V_Grid 230 4V I_Grid 8 1A Status Generating Power 1488W Grid Frequency F_Grid 60 06Hz Total Energy 0258458 kwh This Month 0123kwh Last Month 0123kwh Today 15 1kwh Yesterday 13 5kwh 10 sec 10 sec 10 sec 10 sec 10 sec 10 sec 10 sec 10 sec V_DC1 S...

Page 13: ...sword the Main Menu will display a screen and be able to access to the following information 1 Alarm Message 2 Running Message 3 Version 4 Daily Energy 5 Monthly Energy 6 Yearly Energy 7 Daily Record 8 Communication Data 9 Warning Message The screen can be scrolled manually by pressing the UP DOWN keys Pressing the ENTER key gives access to a submenu Press the ESC key to return to the Main Menu 6 ...

Page 14: ...creen shows the internal data of the Inverter see Figure 6 14 which is for service technicians only 01 05 01 25 E4 9D AA 06 10 C2 B5 E4 9D 55 Figure 6 14 Communication Data Press DOWN key to move the cursor press UP key to change the digit Press Enter after the month year is fixed 2015 02 0510kWh 2015 01 0610kWh Press UP DOWN key to move one date from another 2015 0017513kWh 2014 0165879kWh Figure...

Page 15: ...e set as different according to local requirements If there is any doubt please consult Solis service technicians for details 6 5 2 Grid ON OFF This function is used to start up or stop the power generation of Solis Single Phase Inverter see Figure 6 18 Grid ON Grid OFF Figure 6 18 Set Grid ON OFF Screens can be scrolled manually by pressing the UP DOWN keys Press the ENTER key to save the setting...

Page 16: ... Restore Settings Are you sure YES ENT NO ESC Press the Enter key to save the setting after setting grid off Press the ESC key to return the previous mean Restore setting could set all item in 6 5 7 special setting to default 6 5 10 HMI Update This function is used for update the LCD program This function is applicable by maintenance personnel only wrong operation will prevent the inverter from re...

Page 17: ...veral tests to ensure its optimal operation and reliability In case of failure the LCD screen will display an alarm message In this case the inverter may stop feeding into the grid The failure descriptions and their corresponding alarm messages are listed in Table 8 1 Solis Single Phase 4G Inverter does not require any regular maintenance However cleaning the dust on heat sink will help the invert...

Page 18: ...I IGBT OV I Over IGBT current 12Power FAULT 12V power supply fault 1 Restart inverter or contact installer IG AD Grid current sampling fail DSP B FAULT Comm failure between main and slave DSP PV ISO PRO 01 02 PV isolation protection 1 Check the polarity of AC connector Reverse DC Reverse DC polarity 1 Check the polarity of DC connector NOTE If the inverter displays any alarm message as listed in T...

Page 19: ...z Rated DC voltage Volts Rated grid frequency Hertz 34 35 0 99 0 8 leading 0 8 lagging 1 45 55 or 55 65 0 99 0 8 leading 0 8 lagging 45 55 or 55 65 Operating ambient temperature range Ingress protection Noise emission typical Cooling concept Max operation altitude Grid connection standard IP65 30 dBA Natural convection 4000m Display Communication connections Warranty Terms LCD 2 20 Z 5 Years Exten...

Page 20: ...Rated DC voltage Volts Rated grid frequency Hertz 36 37 0 99 0 8 leading 0 8 lagging 1 0 99 0 8 leading 0 8 lagging 1 45 55 or 55 65 45 55 or 55 65 Operating ambient temperature range Ingress protection Noise emission typical Cooling concept Max operation altitude Grid connection standard IP65 30 dBA Natural convection 4000m Display Communication connections Warranty Terms LCD 2 20 Z 5 Years Exten...

Page 21: ...d grid frequency Hertz 0 8leading 0 8lagging 1 1 For Brazil products the certificated PF range is 0 9 leading 0 9 lagging but the actual range is 0 8 leading 0 8lagging Operating ambient temperature range Ingress protection Noise emission typical Cooling concept Max operation altitude Grid connection standard IP65 30 dBA Natural convection 4000m Display Communication connections Warranty Terms LCD...