10. Specifications
10. Specifications
Dimensions (W*H*D)
Weight
84kg
Max. DC input voltage (Volts)
MPPT voltage range (Volts)
Max. input current (Amps)
MPPT number/Max input strings number
Rated grid voltage (Volts)
Rated grid output current (Amps)
Power Factor (at rated output power)
Max.efficiency
EU efficiency
Model
Topology
Self consumption (night)
Operating ambient temperature range
Relative humidity
Ingress protection
Cooling concept
Max.operation altitude
1100
6*32
6*50
6/12
50/60
98.5%
98.1%
Transformerless
-25
℃...
+60
℃
0~100%
IP66
4000m
Rated output power (Watts)
Max. output power (Watts)
Max. apparent output power (VA)
450
50000
55000
55000
131.2
144.3
THDi (at rated output power)
<3%
Start-up voltage (Volts)
Max short circuit input current (Amps)
Rated DC voltage (Volts)
Rated grid frequency (Hertz)
180...1000
195
S5-GC50K-LV
Max. output current (Amps)
AC connection
Grid connection standard
DC connection
Display
Communication connections
Warranty
MC4 connector
OT Terminal (max 185 mm²)
LCD, 2×20 Z
RS485, Optional: Wifi, GPRS , PLC
5 years (extand to 20 years)
Safty/EMC standard
Operating frequency range (Hertz)
45...55 or 55...65
<
2W
>
0.99(Adjustable from 0.8leading...0.8lagging)
Noise emission (typical)
≤
65 dBA
Intelligent redundant cooling
IEC 61727, IEC 62116, C10/11,
VDE 4105, IEEE 1547
Dimensions (W*H*D)
Weight
84kg
Max. DC input voltage (Volts)
MPPT voltage range (Volts)
Max. input current (Amps)
MPPT number/Max input strings number
Rated grid voltage (Volts)
Rated grid output current (Amps)
Power Factor (at rated output power)
Max.efficiency
EU efficiency
Model
Topology
Self consumption (night)
Operating ambient temperature range
Relative humidity
Ingress protection
Max.operation altitude
1100
8*32
8*50
8/16
>
0.99(Adjustable from 0.8leading...0.8lagging)
50/60
98.5%
98.1%
Transformerless
-25
℃...
+60
℃
0~100%
IP66
4000m
Rated output power (Watts)
Max. output power (Watts)
Max. apparent output power (VA)
450
60000
66000
66000
157.5
173.2
THDi (at rated output power)
<3%
Start-up voltage (Volts)
Max short circuit input current (Amps)
Rated DC voltage (Volts)
Rated grid frequency (Hertz)
180...1000
195
S5-GC60K-LV
Max. output current (Amps)
AC connection
Grid connection standard
DC connection
Display
Communication connections
Warranty
MC4 connector
OT Terminal (max 185 mm²)
LCD, 2×20 Z
RS485, Optional: Wifi, GPRS , PLC
5 years (extand to 20 years)
IEC 61727, IEC 62116, C10/11,
VDE 4105, IEEE 1547
Safty/EMC standard
<
2W
Operating frequency range (Hertz)
45...55 or 55...65
Cooling concept
Noise emission (typical)
≤
65 dBA
Intelligent redundant cooling
.62.
.63.
3/(N)/PE, 220
3/(N)/PE, 220
1065*567*344.5mm
1065*567*344.5mm
IEC/EN 62109-1/-2, IEC/EN 61000-6-1/-2/-3/-4