9. Specifications

Max. input voltage

Start-up voltage

MPPT voltage range

MPPT number/Max input strings number

Max. input current

Battery Voltage range

Maximum Charging Power

Rated output power

Max. apparent output power

Back-up switch time

Rated output voltage

Rated frequency

Rated output current

THDv(@linear load)

Recommended max. PV power

Maximum Charge/discharge current

Communication 

Technical Data

S5-EH1P3K-L

4800W

120V

90-520V

2/2

15.0A/15.0A

3kW

62.5A

CAN

3kW

1/N/PE, 220 V/230 V

50Hz/60Hz

14.0 A/13.5 A

<

2%

600V

42 - 58V

Battery Type

Li-ion / Lead-acid

Battery Capacity 

50 - 2000Ah

4.5 kVA, 10SEC

S5-EH1P3.6K-L

Input DC (PV side)  

Rated voltage

330V

Full load MPPT voltage range

100-520V

120-520V

Max. short circuit current

22.5A/22.5A

Battery  

Output AC(Back-up)     

Input AC (Grid side)   

Input voltage range

Frequency range

187-265V

20.5 A/20.0 A

45-55 Hz/ 55-65Hz

Max. input current

<

20ms

5700W

25.0 A/23.5 A

8. Troubleshooting

NOTE: 

If the inverter displays any alarm message as listed in Table 8.1; please 
turn off the inverter and wait for 5 minutes before restarting it . 
If the failure persists, please contact your local distributor or the service 
center. 

1.  Serial number of Solis Single Phase Inverter;

2.  The distributor/dealer of Solis Single Phase Inverter (if available);

3.  Installation date.

4.  The description of problem (i.e. the alarm message displayed on the LCD and the status 

    of the LED status indicator lights. Other readings obtained from the Information 

  

submenu (refer to Section 6.2) will also be helpful.);

5. The PV array configuration (e.g. number of panels, capacity of  panels, number of 

  

strings, etc.);

6. Your contact details.

Please keep ready with you the following information before contacting us.

.85.

.86.

OV-ILLC
(1052 DATA:0000)

LLC hardware overcurrent

1. Check whether the backup load is overloaded.
2. Restart the system, confirm that the fault 
    continues.

DSP-B-FAULT
(1036 DATA:0000)

AFCI-Check
(1040 DATA:0000)

ARC- FAULT
(1041 DATA:0000)

The master-slave DSP 
communication is abnormal

AFCI self-test failure

AFCI failure

INI-FAULT
(1031 DATA:0000)

AD zero drift overlink

1. Restart the system, confirm that the fault 

 

    continues.

1. Verify connections are tight within your PV 

system.  Arc fault settings can be changed in 

advanced settings if further adjustment is 

necessary.

Table 8.1 Fault message and description

Message Name

Information Description

Troubleshooting Suggestion

Summary of Contents for S5-EH1P-L

Page 1: ...712 P R China Tel 86 0 574 6578 1806 Fax 86 0 574 6578 1606 If you encounter any problem on the inverter please find out the inverter S N and contact us we will try to respond to your question ASAP Ve...

Page 2: ...ion 4 6 AC Cable Installation 4 7 Communication Cable Installation 6 Operation 6 1 Initial Display 6 3 Information 6 4 Settings 6 5 Advanced Info 03 56 6 6 Advanced Settings Technicians Only 2 3 Notic...

Page 3: ...ttery Cable x2 Connector x1 Terminal cover x1 Rs485 Meter cable x1 For Eastron Meter The Solis S5 EH1P L Series is designed for residential hybrid systems which can work with batteries to optimize sel...

Page 4: ...sconnecting all power sources service technician only Warranty may be voided if the cover is removed without authorization CAUTION The surface temperature of the inverter can reach up to 75 167 F To a...

Page 5: ...to the instructions stated in this manual 4 The inverter must be installed according to the correct technical specifications 05 06 Figure 3 3 Front Panel Display WARNING Please refer to the specifica...

Page 6: ...heating always make sure the flow of air around the inverter is not blocked A minimum clearance of 300mm should be kept between inverters or objects and 500mm clearance between the bottom of the machi...

Page 7: ...ft up the inverter be careful to avoid injury and align the back bracket on the inverter with the convex section of the mounting bracket Hang the inverter on the mounting bracket and make sure the inv...

Page 8: ...make sure the PV array open circuit voltage is within the limit of the inverter Before connection please make sure the polarity of the output voltage of PV array matches the DC and DC symbols Please...

Page 9: ...eard to prove the connection is correct CAUTION If DC inputs are accidently reversely connected or inverter is faulty or not working properly it is NOT allowed to turn off the DC switch Otherwise it m...

Page 10: ...please carefully read the user manual of the battery and perform the installation exactly as the battery manufacturer requests Figure 4 16 Figure 4 17 A Connector Body A 1 Barrel sealing Not included...

Page 11: ...imping tool Manual hydraulic crimping Die 25 mm 18 17 Grommet Back shell Correct direction The chamfer in the rear position Wrong direction The chamfer at the front position When 16mm cable apply asse...

Page 12: ...0 14mm 6 8mm 9mm Traverse cross sectional area Exposure Length Numerical value There are two AC terminals and the assembly steps for both are the same Take out the AC connector parts from the packagin...

Page 13: ...normal hybrid control logics 1 Optional To realize Demand Response or Logic interface function this function may be required in UK and Australia 1 Optional Used for Solis Data Logger Connection 2 Opt...

Page 14: ...the positive or negative pole of the battery module 4 7 3 2 Compatible Smart Meter RS485 Connection Compatible Smart Meter Model SDM120CT Default Pin 9 RS485B Pin 10 RS485A Pin 9 RS485B Pin 10 RS485A...

Page 15: ...s Data Logger Installation 1 Remove the watertight cap from the COM port 2 Insert the Solis Data Logger to the COM port to match the joint NOTE Solis hybrid inverter is designed to provide 12V power f...

Page 16: ...1 section describes the connection diagram of 1ph meter Eastron SDM120CT and Acrel ACR10R D16TE Below 4 8 2 section describes the connection diagram of 3ph meter Eastron SDM630MCT and Acrel ACR10R D16...

Page 17: ...PV strings CB Battery CB PV strings CB Battery CB S5 EH1P L Back up L N PE L N PE Grid L N PE CB CB N L S5 EH1P L Distribution box RS485 Meter COM Critical Load RCD RCD PE N L Load_a CT L N PE GRID R...

Page 18: ...H1P L Back up L N PE La N PE Grid Distribution box RCD RCD RS485 PE N L Load_a L N PE PE N La Load_b Lb Lc PE N Lc Load_c RCD RCD GRID RS485 Lc Lb La N PE CTc CTb CTa N La Lc Lb La N Meter 1 2 3 4 131...

Page 19: ...ure all the devices are accessible for operation maintenance and service Check and confirm that the inverter is firmly installed Space for ventilation is sufficient for one inverter or multiple invert...

Page 20: ...DK2 EN50438L C10 11 NRS097 CEI 021 RD1699 EN50549 G98 G99 G98NI G99NI EN50549IE Belgium South Africa Italy Spain Applicable in some European countries UK UK North Ireland North Ireland Ireland France...

Page 21: ...n Discharge Limitation 000 0A 000 0A Equalizing Charge 055 0V 000 0V 056 4V 046 0V SET ENT DONE ESC Voltage Droop Disable Step 3 7 Select the battery option and set battery SOC The default setting for...

Page 22: ...rge Time Discharge Time Discharge Time Discharge Time HH MM HH MM 10 00 00 00 00 00 14 00 00 00 00 00 Total Time Total Time Total Time Total Time Total Time Total Time HH MM NEXT ENT DONE ESC Stop Set...

Page 23: ...te RS485 ON OFF Step 1 Settings Storage Energy Set 2015 02 23 19 35 Control Parameter Battery Select Storage Mode Select Battery Wakeup Meter Set Step 2 Settings Meter Set 2015 02 23 19 35 Meter Selec...

Page 24: ...ay When powering up the inverter for the first time it is required to set the language Press ENT to select Figure 6 2 Set Language Settings Set Language 2015 02 23 19 35 English YES ENT NO ESC ESC UP...

Page 25: ...cal Loads Loads connected to the AC Backup port which will be supported by battery and solar even if the grid is in malfunction Grid The arrow and value indicate the export import power of the hybrid...

Page 26: ...indicates discharging NOTE Information for PV Inverter Meter is only available when two Eastron meters are used and Meter Placement is selected as Grid PV Meter Details please consult Solis service d...

Page 27: ...yield calculation If Solis monitoring system is used must set the correct time zone of the system otherwise datalogger will update the inverter time based on the time zone of the system Press UP and D...

Page 28: ...Version and Software Version Battery Enable Disable 6 5 Advanced Information Detailed information can be viewed in this section 1 Alarm Message 2 Running Message 3 Version 4 Communication Data 5 Dail...

Page 29: ...ly Energy Figure 6 18 Daily Energy Daily Energy 2015 02 23 19 35 2015 23 02 00 10 20 30 40 50 60 D a i l y E n e r g y k W 00 00 03 00 06 00 09 00 12 00 15 00 18 00 21 00 00 00 ESC UP DOWN ENT The scr...

Page 30: ...arning Message 2015 02 23 19 35 Message Date Time Data NO message ESC UP DOWN ENT 6 5 9 Warning Message Figure 6 22 Warning Message Settings 6 5 8 Total Energy The screen shows the inverter total ener...

Page 31: ...erter which are subject to change It is for your reference only If customer has any doubts or uncertainty please consult Solis service department for confirmation Detailed protection limits can be vie...

Page 32: ...Reset Password Calibrate 2015 02 23 19 35 Total Energy Power Parameter 6 6 3 Calibrate By using our data monitoring hardware the data on monitoring website can automatically synchronize with the pres...

Page 33: ...when the ForceCharge SOC is reached inverter will charge the battery using the power from either PV or Grid ForceChg Limit 0A 100A default 100A Determine the battery charge current limit when inverter...

Page 34: ...Force Charg Voltage Define the voltage that forces to charge the battery to prevent a dead battery 7 ForceChg Limit Define the battery charge current limit in force charge status 8 I_Max Discharge De...

Page 35: ...Meter Model Acrel 3ph meter With CT ACR10R D16TE4 Optional Eastron 1ph meter Direct Insert SDM120M Optional Eastron 1ph meter With CT SDM120CT Eastron 3ph meter Direct Insert SDM630 Optional Eastron...

Page 36: ...HH MM HH MM 10 00 00 00 00 00 14 00 00 00 00 00 Total Time Total Time Total Time Total Time Total Time Total Time HH MM NEXT ENT DONE ESC Stop Charging from gird self use Path Advanced Settings Storag...

Page 37: ...es from PV If Charging From Grid is allowed it can also come from Grid If Time of Use is Run the logic will follow the charging discharging settings and time settings as defined in Time of Use For tho...

Page 38: ...g 1 3 are only valid when Setting 2 is set to ON ON OFF is to enable disable the export power control function Backflow Power is to set the max allowed export power at the meter location Failsafe ON O...

Page 39: ...tdown once it loses communication with the meter in case of any backflow power exceeding the limit 6 6 8 HMI Update This function is used to update HMI software Values are for reference only Figure 6...

Page 40: ...23 19 35 AFCI Set EPS Mode YES ENT NO ESC 6 6 11 1 AFCI Set Inverters have the built in AFCI function which can detect the arc fault on the DC circuit and shut down the inverter to prevent a fire disa...

Page 41: ...S switching box to achieve ATS switching function When grid is available only the Grid Port is enabled and load is supported through NPS box by the grid When grid is lost Grid Port will be disabled an...

Page 42: ...rter has been subjected to several test to ensure its optimal operation and reliability In case of a failure the LCD screen will display an alarm message In this case the inverter may stop feeding ene...

Page 43: ...it OV G F01 UN G F01 G PHASE G F GLU NO Grid OV G V02 OV G V03 IGFOL F OV G V05 OV G V04 UN G V02 OV G F02 UN G F02 NO Battery Grid frequency exceeds the upper frequency range Grid frequency exceeds t...

Page 44: ...ATA 0000 UN TEM 103A DATA 0000 PV ISO PRO01 1033 DATA 0001 PV ISO PRO02 1033 DATA 0002 12Power FAULT 1038 DATA 0000 ILeak PRO01 1034 DATA 0001 ILeak PRO02 1034 DATA 0002 ILeak PRO03 1034 DATA 0003 ILe...

Page 45: ...sists please contact your local distributor or the service center 1 Serial number of Solis Single Phase Inverter 2 The distributor dealer of Solis Single Phase Inverter if available 3 Installation dat...

Page 46: ...leading 0 8 lagging 96 5 Max output current 15 0 A 14 5 A 18 5 A 17 5 A THDi 2 Efficiency AC grid frequency range Rated grid output current 13 7 A 13 1 A 45 55 Hz 55 65 Hz 16 4 A 15 7 A The grid volta...

Page 47: ...ange Frequency range 187 265V 31 5 A 30 0 A 45 55 Hz 55 65Hz Max input current 20ms Rated output power 5kW 4 6kW Max apparent output power 4 6kVA Output AC Grid side Power Factor Max efficiency EU eff...

Page 48: ...ms Li ion Lead acid 100A 5kW Features Quick connection plug AC connection Communication Warranty RS485 Optional Wi Fi GPRS 5 years standard extand to 20 years Display 7 0 LCD color screen display Grid...

Page 49: ...NE 206007 1 CEI 0 21 C10 11 NRS 097 2 1 TOR EIFS 2018 2 IEC 62116 IEC 61727 IEC 60068 IEC 61683 EN 50530 MEA PEA Safty EMC standard IEC EN 62109 1 2 EN 61000 6 2 3 3000m Max operation altitude MC4 con...