9. Specifications
Max. input voltage
Start-up voltage
MPPT voltage range
MPPT number/Max input strings number
Max. input current
Battery Voltage range
Maximum Charging Power
Rated output power
Max. apparent output power
Back-up switch time
Rated output voltage
Rated frequency
Rated output current
THDv(@linear load)
Recommended max. PV power
Maximum Charge/discharge current
Communication
Technical Data
S5-EH1P3K-L
4800W
120V
90-520V
2/2
15.0A/15.0A
3kW
62.5A
CAN
3kW
1/N/PE, 220 V/230 V
50Hz/60Hz
14.0 A/13.5 A
<
2%
600V
42 - 58V
Battery Type
Li-ion / Lead-acid
Battery Capacity
50 - 2000Ah
4.5 kVA, 10SEC
S5-EH1P3.6K-L
Input DC (PV side)
Rated voltage
330V
Full load MPPT voltage range
100-520V
120-520V
Max. short circuit current
22.5A/22.5A
Battery
Output AC(Back-up)
Input AC (Grid side)
Input voltage range
Frequency range
187-265V
20.5 A/20.0 A
45-55 Hz/ 55-65Hz
Max. input current
<
20ms
5700W
25.0 A/23.5 A
8. Troubleshooting
NOTE:
If the inverter displays any alarm message as listed in Table 8.1; please
turn off the inverter and wait for 5 minutes before restarting it .
If the failure persists, please contact your local distributor or the service
center.
1. Serial number of Solis Single Phase Inverter;
2. The distributor/dealer of Solis Single Phase Inverter (if available);
3. Installation date.
4. The description of problem (i.e. the alarm message displayed on the LCD and the status
of the LED status indicator lights. Other readings obtained from the Information
submenu (refer to Section 6.2) will also be helpful.);
5. The PV array configuration (e.g. number of panels, capacity of panels, number of
strings, etc.);
6. Your contact details.
Please keep ready with you the following information before contacting us.
.85.
.86.
OV-ILLC
(1052 DATA:0000)
LLC hardware overcurrent
1. Check whether the backup load is overloaded.
2. Restart the system, confirm that the fault
continues.
DSP-B-FAULT
(1036 DATA:0000)
AFCI-Check
(1040 DATA:0000)
ARC- FAULT
(1041 DATA:0000)
The master-slave DSP
communication is abnormal
AFCI self-test failure
AFCI failure
INI-FAULT
(1031 DATA:0000)
AD zero drift overlink
1. Restart the system, confirm that the fault
continues.
1. Verify connections are tight within your PV
system. Arc fault settings can be changed in
advanced settings if further adjustment is
necessary.
Table 8.1 Fault message and description
Message Name
Information Description
Troubleshooting Suggestion