34
| Round fire damper manual 02/2021
SOLID AIR ®
CLIMATE SOLUTIONS
•
T +31 598 36 12 21
•
www.solid-air.com
•
Flexible wall installation Applique installation frame
The wall is composed of 2 x 2 plasterboard
boards, 12.5 mm thick, installed on a steel frame
construction. The interior of the wall is filled with
mineral wool (≥ 100 kg/m³). The minimum thickness
of the wall is 100 mm.
Installations
INSTALLATION
Create an opening according to the table below
and build the subframe according to the drawing,
see page 39.
Damper blade must be closed during installation!
1. Place the fire damper in the opening.
2. Fasten the fire damper with screws
(8 pcs, 4.8 x 60 mm).
Test the operation of the damper blade!
1
2
Wall opening dimensions
Damper diameter Ø d (mm)
Applique frame diameter Ø D (mm)
Wall opening (mm)
100
Ø d + 105 mm
Ø d + 115 mm
125-180
Ø d + 95 mm
Ø d + 105 mm
200-315
Ø d + 80 mm
Ø d + 90 mm